Chapter 2: Design Loads for
Buildings
 Chapter Objectives:
 Identify different types of structural loads acting on
steel structures.
 Calculation of structural loads acting on typical steel
buildings according to the latest edition of the ASCE
standards.
Introduction
 Loads and load combinations are to be taken from
the governing building code;
 In the absence of a building code, use the ASCE/SEI
“Minimum Design Loads for Buildings and Other
Structures” provided by the American Society for
Civil Engineers (ASCE) as stated by AISC-LRFD
Manual (pp. 16.1-10).
Design Loads on Steel Structures
ASCE 7-16 Standards AISC-LRFD Manual
For Design of Structural
Elements and Connections
Minimum Design Loads for
Buildings and Other
Structures
Design Loads on Steel Structures
• Examples of common design loads are:
Dead Load (D);
Live Load Due to Occupancy and movable equipment (L);
Roof Live Load (Lr);
Wind Load (W);
Earthquake Load (E).
Load Path and Tributary Areas
• Examples of load path on trusses
supporting
purlins
Truss
roof
The trusses transfer
their loads to the
supporting columns
Each purlin supports an area = its span x
half the distance to the purlin on either side.
The purlins transfer
their loads to the
supporting trusses
Each truss supports an area
= its span x half the distance
to the trusses on either side
Load Path on Trusses
Load Path on Slab-Beam System
Floor Beams and Girders are at the same level
 Slab Metal Decking is used: Slab transfers load along
deck ribs direction
 Slab on conventional wooden formwork: check
Llong/Lshort of slab panel
Load Path on Slab-Beam System
Floor Beams and Girders are at the same level
 Slab Metal Decking is used: Slab transfers load along
deck ribs direction
 Slab on conventional wooden formwork: check
Llong/Lshort of slab panel
Dead Load
• It is the self-weight of all construction materials
incorporated into the building (i.e., Permanent Load).
• Examples:
Structural components (slabs, beams, girders, and
columns).
 Floors, roofs and ceilings materials.
 Exterior walls, cladding, windows, and doors.
 Interior permanent walls and partitions.
Fixed service equipments (heating, air-
conditioning, elevators, cranes, …etc.)
Dead Load
• As a result of its deterministic nature, Dead loads can
be estimated with only a small margin of error.
• Recommended minimum design dead loads in (psf)
and (kN/m2) are provided by Table C3-1 of the ASCE7-
16 Standard.
• Table C3-2, in the ASCE7-16 Standard provides
minimum densities (pcf and kN/m3) for construction
materials.
Dead Load
Dead Load
Dead Load
Dead Load
Dead Load
Dead Load
Example 1
The floor system of a building consists of 5 inch-thick reinforced
concrete slab resting on four steel floor beams, which in turn are
supported by two steel girders as shown in the figure. The cross-
sectional areas of the floor beams and the girders are 14.7 in2 and
52.1 in2, respectively. Determine the dead loads acting on the
beams CG and DH and the girder AD.
(A = 52.1 in2)
Dead Load
Solution
Dead load on beam CG:
from ASCE7-10, Table C3-2 (page 266): gconc = 150 lb/ft3
Based on the tributary area carried by the beam CG:
Load from the concrete slab = gconc * tslab *btributary
Load from R.C. slab = (150 lb/ft3) (5/12 ft) (10 ft) = 625 lb/ft
(A = 52.1 in2)
Dead Load
Dead load on beam CG:
from ASCE7-10, Table C3-2 (page 266): gsteel = 492 lb/ft3
Own weight of the steel beam = gsteel * Area of beam(ft2)
weight of steel beam = (492 lb/ft3) (14.7/144 ft2) = 50 lb/ft
Total uniform dead load = 625 + 50 = 675 lb/ft
(A = 52.1 in2)
Dead Load
Dead load on beam DH:
Based on the tributary area carried by the beam DH:
Load from the concrete slab = gconc * tslab *btributary
= (150 lb/ft3) (5/12 ft) (5 ft)
= 312.5 lb/ft
(A = 52.1 in2)
Dead Load
(A = 52.1 in2)
Dead load on beam DH:
Own weight of the steel beam = gsteel * Area of beam(ft2)
weight of steel beam = (492 lb/ft3) (14.7/144 ft2) = 50 lb/ft
Total uniform dead load = 312.5 + 50 = 362.5 lb/ft
Dead Load
Dead load on girder AD:
The distributed dead load on girder AD is due to its own weight only
Own weight of the girder = gsteel * Area of beam(ft2)
= (492 lb/ft3) (52.1/144 ft2) = 178 lb/ft
(A = 52.1 in2)
Dead Load
(A = 52.1 in2)
10,770 lb10,770 lb
Dead load on girder AD:
The dead load acting on BF is the same as for CG
So, the reactions from BF and CG are the same = 8100 lb
 In general, Live Load varies in magnitude with time
 It is the load resulting from all non-permanent
installations in the building;
 The Live Load value varies from one location to
another inside the building.
 Examples of Live Loads:
 building occupants.
 furniture.
 office equipment.
 movable room partitions,…etc .
Live Load
• Live load on buildings can be divided into two main
components:
1) Sustained Live Load (SLL): weight of relatively
permanent fixtures and furnishings.
2) Transient Live Load (TLL): weight of occupants who
enter and leave the space.
Live Load
Live Load
 In general, live loads are prescribed in building
codes based on occupancy, location, and
importance of the building;
 Due to the uncertainty associated with the
expected value of Live loads, they are estimated
with a much larger margin of error than in dead
load.
 Forms of application of live loads:
I. Uniformly Distributed Live Load;
II. Concentrated Live Load.
Live Load
27
Live Load
 Live loads due to vehicular traffic on highway bridges
the American Association of State Highway and
Transportation Officials (AASHTO) Specification
defines two systems of standard trucks, H trucks and
HS trucks, to represent the vehicular loads for design
purposes.
 Impact Loads: Moving vehicles may bounce or sidesway
as they move over a bridge, and therefore they impart
an impact to the deck. The percentage increase of the
live loads due to impact is called the impact factor, I.
28
Live Load
 Live loads for railroad bridges are specified by the
American Railway Engineering and Maintenance of
Way Association (AREMA) in the Manual for Railway
Engineering.
 Tables 4-1 and C4-1 in the ASCE7-16 Standard
provide minimum values for live loads (Lo) in (psf)
and (kN/m2);
 Live load values (Lo) provided in the tables may be
reduced depending on the tributary area supported
by the structural element under consideration;
 What is the “Tributary Area” and how may it differ
from a structural element to another in the same
building?
Live Load
Live Load
Live Load
Live Load
Live Load
A tributary area for a member is the area that, when
loaded, causes a stress change in the member.
Example (1): Tributary Area for Column Load
LiveLoad
Example (2): Tributary Area for Beam and Column Loads
Live Load
Example (3): Tributary Area for Beam and Column
Loads
Live Load
• Reduction in Live Load: A reduced live load may be
design according to the following
) (S.I. Unites)
where:
L is the reduced design live load per ft2 (m2) of area
supported by the member.
) (Imperial Unites)
K A
15
( 0.25 
LL T
o
used in the
formula:
L  L
K A
4.57
LL T
oL  L ( 0.25 
Live Load
(KLLAT ) > 400 ft2 (37.16 m2 )
where:
Lo is the unreduced design live load per ft2 (m2) of area
supported by the member (from table 4-1 or C4-1)
AT is the tributary area in ft2 (m2).
KLL is the live load element factor (from table4-2)
Live Load
(A = 52.1 in2)
Live Load
Example 1
The plan below shows a floor system of the offices area
in an office building. Use the ASCE7-16 standards to
calculate the live loads acting on the beams CG and DH
and the girder AD.
KLL AT= 2 * 240 = 480 ft2 > 400 ft2 (reduction is needed)
Solution
Live load on beam CG:
From ASCE7-10, Table 4-1, Lo = 50 psf
From ASCE7-10, Table 4-2, KLL for interior beam CG = 2
ATcarried by the beam CG = 10 ft x 24 ft = 240 ft2
Live Load
Live load on beam CG (cont’d):
Total uniform live load = wL = L * bT = 46.75 * 10 = 467.5lb/ft
15 15
480 



  50*0.935  46.75 psf
 
 
 
K A
L  L 0.25    50 0.25 
LL T
o
wL = 467.5lb/ft
5610 lb 5610 lb
C G
Live Load
Live load on beam DH:
From Table 4-2, KLL for edge beam DH without cantilever slab = 2
ATcarried by the beam DH = (5 ft) (24 ft) = 120 ft2
KLL AT= 2 * 120 = 240 ft2 < 400 ft2 (No reduction is needed)
Live Load
Live load on beam DH (cont’d):
L = Lo= 50 psf
Total uniform live load = wL = L * bT = (50 psf) (5 ft) = 250lb/ft
wL = 250lb/ft
3000 lb 3000 lb
D H
Live Load
1515
720 
 
  50*0.809  40.45 psf

 

 
K A
L  L 0.25    50 0.25 
LL T
o
PL=? PL=?
Live load on girder AD:
From Table 4-2, KLL for edge girder AD without cantilever slab = 2
ATcarried by the girder AD = (30 ft) (24/2 ft) = 360 ft2
KLL AT = 2 * 360 = 720 ft2 >400 ft2 (reduction is needed)
Live Load
Live load on girder AD (cont’d):
PL is the reaction from Beams CG and BF on Girder AD
From the Floor Beam CG Solution:
For a reduction factor of 0.935  PL = 5610 lb
From the Girder AD Solution:
For a reduction factor of 0.809  PL = ???? lb
Live Load
Live load on girder AD (cont’d):
Having:
For a reduction factor of 0.935  PL = 5610 lb
For a reduction factor of 0.809  PL = ???? lb

 
0.935
P  5610  0.809   4854 lbL
PL=4854 lb 4854 lb
Live Load
Roof Live Load
Roof Live Load
Reduction in Flat, Pitched or Curved Roofs Live Load:
Lr = Lo R1 R2 ;
Lr = Lo R1 R2;
where12 < Lr < 20 psf ,or
where 0.58 < Lr < 0.96 kN/m2
where Lr is the reduced roof live load applied to the
horizontal projection of the roof area.
b
a
Roof Live Load
R1 and R2 are reduction factors that are determined as
follows:
 1 for At  200 ft2
structural member considered.

1 t
R 

.2  0.001A for 200  A  600 ft2
1


t
for At  600 ft2
for At  18.58 m2
0.6


in which At is the tributary area supported by the
t1 t
for At  55.74 m2
0.6
for 18.58  A  55.74 m2R 

.2  0.011A
1
1
Roof Live Load
where for pitched roofs:
F = Slope x 12 (i.e., = (a/b) x 12)
and, for arches or domes:
F = (rise-to-span ratio)x32

 for F  4
for 4  F 12
for F  120.6
1
2
R   .2  0.05F
1
b
a
Roof Live Load
 The reduced live load must not be less than 50
percent of Lo for members supporting one floor or a
section of a single floor, nor less than 40 percent of Lo
for members supporting two or more Floors;
 For a column or beam supporting more than one
floor, the term AT represents the sum of the tributary
areas from all floors;
 Reduction in live load is not permitted for public
assembly areas or when the live load is high (>100
psf).
Live Load
Roof Live Load
Example 3
For the three-story building shown in the figures below.
Calculate the design live load supported by the interior
column C located in the first story. Assume a 50 lb/ft2
design live load, Lo, on all floors including the roof.
Solution
Roof live load on Column C:
Lr = Lo R1R2
AT = 20(24) = 480ft2
R1 = 1.2 − 0.001 (480) = 0.72
R2 = 1.0
Lroof = LoR1R2
= 50(0.72)(1.0) = 36.0 psf
Roof Live Load
Roof Live Load
Solution
Floor live load on Column C:
the tributary area for the remaining two floors
AT= 2(480) = 960 ft2
KLL AT= 4 * 960 = 3840 ft2 > 400 ft2
(reduction is needed)
Solution
Total live load on Column C:
Since 24.6 lb/ft2 > 0.4 × 50 lb/ft2 = 20 lb/ft2 (the lower limit)
So, use L = 24.6 lb/ft2.
Load to column = AT(Lroof) + 2AT(Lfloor)
= 480(36.0) + 960(24.6)
= 40,896 lb = 40.9 kips.
Roof Live Load
57
Questions?

More Related Content

PDF
Steel warehouse design report
PDF
Comparision of ASCE ASCE7-10 to ASCE7-16 Of Wind load
PDF
Seismic Design of Steel Structures-complete course.pdf
PDF
Análisis de Estructuras - Jairo Uribe Escamilla 2da.pdf
PPTX
Seismic Analysis
PDF
local_media8454261933790366398.pdf
PDF
Classification of materials
PPTX
Module 1 elements of design
Steel warehouse design report
Comparision of ASCE ASCE7-10 to ASCE7-16 Of Wind load
Seismic Design of Steel Structures-complete course.pdf
Análisis de Estructuras - Jairo Uribe Escamilla 2da.pdf
Seismic Analysis
local_media8454261933790366398.pdf
Classification of materials
Module 1 elements of design

What's hot (20)

DOC
Chapter 12
PPTX
Design of tension members
PPT
Strut and Tie Model for Pile Cap
PDF
Chapter 6-influence lines for statically determinate structures
PDF
Chapter 12
PDF
Lecture 1 design loads
PPTX
CE 72.52 - Lecture 7 - Strut and Tie Models
PPTX
Braced cut in deep excavation
DOC
Examples on stress distribution
PPTX
Design Procedure of Singly,Doubly & T-Beam(As Per ACI code)
PPTX
Design of column base plates anchor bolt
PDF
Table of Fixed End Moments Formulas
PDF
Chapter 3-analysis of statically determinate trusses
PPT
Column design: as per bs code
PDF
Influence lines for_indeterminate_beams_and_frames
PPTX
Numerical problem bearing capacity terzaghi , group pile capacity (usefulsear...
PDF
Design of purlins
PPSX
Geotechnical Engineering-II [Lec #13: Elastic Settlements]
PPSX
Geotechnical Engineering-II [Lec #9+10: Westergaard Theory]
PPTX
Design of column according ACI codes
Chapter 12
Design of tension members
Strut and Tie Model for Pile Cap
Chapter 6-influence lines for statically determinate structures
Chapter 12
Lecture 1 design loads
CE 72.52 - Lecture 7 - Strut and Tie Models
Braced cut in deep excavation
Examples on stress distribution
Design Procedure of Singly,Doubly & T-Beam(As Per ACI code)
Design of column base plates anchor bolt
Table of Fixed End Moments Formulas
Chapter 3-analysis of statically determinate trusses
Column design: as per bs code
Influence lines for_indeterminate_beams_and_frames
Numerical problem bearing capacity terzaghi , group pile capacity (usefulsear...
Design of purlins
Geotechnical Engineering-II [Lec #13: Elastic Settlements]
Geotechnical Engineering-II [Lec #9+10: Westergaard Theory]
Design of column according ACI codes
Ad

Similar to Chapter 2 design loads(3) (20)

PDF
Chapter 1-types of structures and loads
PDF
PPT5-BridgeLoadpdfload and load distribution
PPT
Lec 13-14-15-flexural analysis and design of beams-2007-r
PPT
Lec 13-14-15
PPT
Bs procedure
PDF
PIPERACK
PPT
introduction to bridge engineering design
PPTX
ANALYSIS & DESIGN OF G+3 STORIED REINFORCED CONCRETE BUILDING
PDF
04-LRFD Concept (Steel Structural Design & Prof. Shehab Mourad)
PPTX
Design Proposal of a 5-Storey Steel Building with Cost Analysis
PPT
Cable Stay Bridge construction at Bardhman using LARSA and LUSAS four dimensi...
PDF
Optimization of Precast Post-tensioned Concrete I-Girder Bridge
PPTX
SEMINAR ON -DYNAMIC EARTHQUICK DESIGN OF G+6 STORIED RESIDENTIAL BUILDING (VI...
DOC
Dbr kashmiri gate
PDF
Comparative Study of Pre-Engineered and Conventional Steel Frames for Differe...
PDF
This calculation report is relevant to the structural analysis and design of ...
PDF
PPTX
Staad Pro Intro
PPT
311 C H18
PPTX
staadfinal-180216111555.pptx ssfdggdgfdgfdgfdg
Chapter 1-types of structures and loads
PPT5-BridgeLoadpdfload and load distribution
Lec 13-14-15-flexural analysis and design of beams-2007-r
Lec 13-14-15
Bs procedure
PIPERACK
introduction to bridge engineering design
ANALYSIS & DESIGN OF G+3 STORIED REINFORCED CONCRETE BUILDING
04-LRFD Concept (Steel Structural Design & Prof. Shehab Mourad)
Design Proposal of a 5-Storey Steel Building with Cost Analysis
Cable Stay Bridge construction at Bardhman using LARSA and LUSAS four dimensi...
Optimization of Precast Post-tensioned Concrete I-Girder Bridge
SEMINAR ON -DYNAMIC EARTHQUICK DESIGN OF G+6 STORIED RESIDENTIAL BUILDING (VI...
Dbr kashmiri gate
Comparative Study of Pre-Engineered and Conventional Steel Frames for Differe...
This calculation report is relevant to the structural analysis and design of ...
Staad Pro Intro
311 C H18
staadfinal-180216111555.pptx ssfdggdgfdgfdgfdg
Ad

Recently uploaded (20)

PDF
Abrasive, erosive and cavitation wear.pdf
PPT
Total quality management ppt for engineering students
PPTX
Fundamentals of Mechanical Engineering.pptx
PPTX
Nature of X-rays, X- Ray Equipment, Fluoroscopy
PPTX
Information Storage and Retrieval Techniques Unit III
PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
PDF
22EC502-MICROCONTROLLER AND INTERFACING-8051 MICROCONTROLLER.pdf
PDF
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PPTX
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
PDF
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
PPTX
Module 8- Technological and Communication Skills.pptx
PDF
Design Guidelines and solutions for Plastics parts
PDF
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
PDF
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
PDF
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
PDF
Soil Improvement Techniques Note - Rabbi
PDF
Automation-in-Manufacturing-Chapter-Introduction.pdf
PDF
737-MAX_SRG.pdf student reference guides
PDF
III.4.1.2_The_Space_Environment.p pdffdf
Abrasive, erosive and cavitation wear.pdf
Total quality management ppt for engineering students
Fundamentals of Mechanical Engineering.pptx
Nature of X-rays, X- Ray Equipment, Fluoroscopy
Information Storage and Retrieval Techniques Unit III
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
22EC502-MICROCONTROLLER AND INTERFACING-8051 MICROCONTROLLER.pdf
Artificial Superintelligence (ASI) Alliance Vision Paper.pdf
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
Module 8- Technological and Communication Skills.pptx
Design Guidelines and solutions for Plastics parts
Accra-Kumasi Expressway - Prefeasibility Report Volume 1 of 7.11.2018.pdf
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
Soil Improvement Techniques Note - Rabbi
Automation-in-Manufacturing-Chapter-Introduction.pdf
737-MAX_SRG.pdf student reference guides
III.4.1.2_The_Space_Environment.p pdffdf

Chapter 2 design loads(3)

  • 1. 1 Chapter 2: Design Loads for Buildings  Chapter Objectives:  Identify different types of structural loads acting on steel structures.  Calculation of structural loads acting on typical steel buildings according to the latest edition of the ASCE standards.
  • 2. Introduction  Loads and load combinations are to be taken from the governing building code;  In the absence of a building code, use the ASCE/SEI “Minimum Design Loads for Buildings and Other Structures” provided by the American Society for Civil Engineers (ASCE) as stated by AISC-LRFD Manual (pp. 16.1-10).
  • 3. Design Loads on Steel Structures ASCE 7-16 Standards AISC-LRFD Manual For Design of Structural Elements and Connections Minimum Design Loads for Buildings and Other Structures
  • 4. Design Loads on Steel Structures • Examples of common design loads are: Dead Load (D); Live Load Due to Occupancy and movable equipment (L); Roof Live Load (Lr); Wind Load (W); Earthquake Load (E).
  • 5. Load Path and Tributary Areas • Examples of load path on trusses
  • 6. supporting purlins Truss roof The trusses transfer their loads to the supporting columns Each purlin supports an area = its span x half the distance to the purlin on either side. The purlins transfer their loads to the supporting trusses Each truss supports an area = its span x half the distance to the trusses on either side Load Path on Trusses
  • 7. Load Path on Slab-Beam System Floor Beams and Girders are at the same level  Slab Metal Decking is used: Slab transfers load along deck ribs direction  Slab on conventional wooden formwork: check Llong/Lshort of slab panel
  • 8. Load Path on Slab-Beam System Floor Beams and Girders are at the same level  Slab Metal Decking is used: Slab transfers load along deck ribs direction  Slab on conventional wooden formwork: check Llong/Lshort of slab panel
  • 9. Dead Load • It is the self-weight of all construction materials incorporated into the building (i.e., Permanent Load). • Examples: Structural components (slabs, beams, girders, and columns).  Floors, roofs and ceilings materials.  Exterior walls, cladding, windows, and doors.  Interior permanent walls and partitions. Fixed service equipments (heating, air- conditioning, elevators, cranes, …etc.)
  • 10. Dead Load • As a result of its deterministic nature, Dead loads can be estimated with only a small margin of error. • Recommended minimum design dead loads in (psf) and (kN/m2) are provided by Table C3-1 of the ASCE7- 16 Standard. • Table C3-2, in the ASCE7-16 Standard provides minimum densities (pcf and kN/m3) for construction materials.
  • 16. Dead Load Example 1 The floor system of a building consists of 5 inch-thick reinforced concrete slab resting on four steel floor beams, which in turn are supported by two steel girders as shown in the figure. The cross- sectional areas of the floor beams and the girders are 14.7 in2 and 52.1 in2, respectively. Determine the dead loads acting on the beams CG and DH and the girder AD. (A = 52.1 in2)
  • 17. Dead Load Solution Dead load on beam CG: from ASCE7-10, Table C3-2 (page 266): gconc = 150 lb/ft3 Based on the tributary area carried by the beam CG: Load from the concrete slab = gconc * tslab *btributary Load from R.C. slab = (150 lb/ft3) (5/12 ft) (10 ft) = 625 lb/ft (A = 52.1 in2)
  • 18. Dead Load Dead load on beam CG: from ASCE7-10, Table C3-2 (page 266): gsteel = 492 lb/ft3 Own weight of the steel beam = gsteel * Area of beam(ft2) weight of steel beam = (492 lb/ft3) (14.7/144 ft2) = 50 lb/ft Total uniform dead load = 625 + 50 = 675 lb/ft (A = 52.1 in2)
  • 19. Dead Load Dead load on beam DH: Based on the tributary area carried by the beam DH: Load from the concrete slab = gconc * tslab *btributary = (150 lb/ft3) (5/12 ft) (5 ft) = 312.5 lb/ft (A = 52.1 in2)
  • 20. Dead Load (A = 52.1 in2) Dead load on beam DH: Own weight of the steel beam = gsteel * Area of beam(ft2) weight of steel beam = (492 lb/ft3) (14.7/144 ft2) = 50 lb/ft Total uniform dead load = 312.5 + 50 = 362.5 lb/ft
  • 21. Dead Load Dead load on girder AD: The distributed dead load on girder AD is due to its own weight only Own weight of the girder = gsteel * Area of beam(ft2) = (492 lb/ft3) (52.1/144 ft2) = 178 lb/ft (A = 52.1 in2)
  • 22. Dead Load (A = 52.1 in2) 10,770 lb10,770 lb Dead load on girder AD: The dead load acting on BF is the same as for CG So, the reactions from BF and CG are the same = 8100 lb
  • 23.  In general, Live Load varies in magnitude with time  It is the load resulting from all non-permanent installations in the building;  The Live Load value varies from one location to another inside the building.  Examples of Live Loads:  building occupants.  furniture.  office equipment.  movable room partitions,…etc . Live Load
  • 24. • Live load on buildings can be divided into two main components: 1) Sustained Live Load (SLL): weight of relatively permanent fixtures and furnishings. 2) Transient Live Load (TLL): weight of occupants who enter and leave the space. Live Load
  • 26.  In general, live loads are prescribed in building codes based on occupancy, location, and importance of the building;  Due to the uncertainty associated with the expected value of Live loads, they are estimated with a much larger margin of error than in dead load.  Forms of application of live loads: I. Uniformly Distributed Live Load; II. Concentrated Live Load. Live Load
  • 27. 27 Live Load  Live loads due to vehicular traffic on highway bridges the American Association of State Highway and Transportation Officials (AASHTO) Specification defines two systems of standard trucks, H trucks and HS trucks, to represent the vehicular loads for design purposes.
  • 28.  Impact Loads: Moving vehicles may bounce or sidesway as they move over a bridge, and therefore they impart an impact to the deck. The percentage increase of the live loads due to impact is called the impact factor, I. 28 Live Load  Live loads for railroad bridges are specified by the American Railway Engineering and Maintenance of Way Association (AREMA) in the Manual for Railway Engineering.
  • 29.  Tables 4-1 and C4-1 in the ASCE7-16 Standard provide minimum values for live loads (Lo) in (psf) and (kN/m2);  Live load values (Lo) provided in the tables may be reduced depending on the tributary area supported by the structural element under consideration;  What is the “Tributary Area” and how may it differ from a structural element to another in the same building? Live Load
  • 34. A tributary area for a member is the area that, when loaded, causes a stress change in the member. Example (1): Tributary Area for Column Load LiveLoad
  • 35. Example (2): Tributary Area for Beam and Column Loads Live Load
  • 36. Example (3): Tributary Area for Beam and Column Loads Live Load
  • 37. • Reduction in Live Load: A reduced live load may be design according to the following ) (S.I. Unites) where: L is the reduced design live load per ft2 (m2) of area supported by the member. ) (Imperial Unites) K A 15 ( 0.25  LL T o used in the formula: L  L K A 4.57 LL T oL  L ( 0.25  Live Load (KLLAT ) > 400 ft2 (37.16 m2 )
  • 38. where: Lo is the unreduced design live load per ft2 (m2) of area supported by the member (from table 4-1 or C4-1) AT is the tributary area in ft2 (m2). KLL is the live load element factor (from table4-2) Live Load
  • 39. (A = 52.1 in2) Live Load Example 1 The plan below shows a floor system of the offices area in an office building. Use the ASCE7-16 standards to calculate the live loads acting on the beams CG and DH and the girder AD.
  • 40. KLL AT= 2 * 240 = 480 ft2 > 400 ft2 (reduction is needed) Solution Live load on beam CG: From ASCE7-10, Table 4-1, Lo = 50 psf From ASCE7-10, Table 4-2, KLL for interior beam CG = 2 ATcarried by the beam CG = 10 ft x 24 ft = 240 ft2 Live Load
  • 41. Live load on beam CG (cont’d): Total uniform live load = wL = L * bT = 46.75 * 10 = 467.5lb/ft 15 15 480       50*0.935  46.75 psf       K A L  L 0.25    50 0.25  LL T o wL = 467.5lb/ft 5610 lb 5610 lb C G Live Load
  • 42. Live load on beam DH: From Table 4-2, KLL for edge beam DH without cantilever slab = 2 ATcarried by the beam DH = (5 ft) (24 ft) = 120 ft2 KLL AT= 2 * 120 = 240 ft2 < 400 ft2 (No reduction is needed) Live Load
  • 43. Live load on beam DH (cont’d): L = Lo= 50 psf Total uniform live load = wL = L * bT = (50 psf) (5 ft) = 250lb/ft wL = 250lb/ft 3000 lb 3000 lb D H Live Load
  • 44. 1515 720      50*0.809  40.45 psf       K A L  L 0.25    50 0.25  LL T o PL=? PL=? Live load on girder AD: From Table 4-2, KLL for edge girder AD without cantilever slab = 2 ATcarried by the girder AD = (30 ft) (24/2 ft) = 360 ft2 KLL AT = 2 * 360 = 720 ft2 >400 ft2 (reduction is needed) Live Load
  • 45. Live load on girder AD (cont’d): PL is the reaction from Beams CG and BF on Girder AD From the Floor Beam CG Solution: For a reduction factor of 0.935  PL = 5610 lb From the Girder AD Solution: For a reduction factor of 0.809  PL = ???? lb Live Load
  • 46. Live load on girder AD (cont’d): Having: For a reduction factor of 0.935  PL = 5610 lb For a reduction factor of 0.809  PL = ???? lb    0.935 P  5610  0.809   4854 lbL PL=4854 lb 4854 lb Live Load
  • 49. Reduction in Flat, Pitched or Curved Roofs Live Load: Lr = Lo R1 R2 ; Lr = Lo R1 R2; where12 < Lr < 20 psf ,or where 0.58 < Lr < 0.96 kN/m2 where Lr is the reduced roof live load applied to the horizontal projection of the roof area. b a Roof Live Load
  • 50. R1 and R2 are reduction factors that are determined as follows:  1 for At  200 ft2 structural member considered.  1 t R   .2  0.001A for 200  A  600 ft2 1   t for At  600 ft2 for At  18.58 m2 0.6   in which At is the tributary area supported by the t1 t for At  55.74 m2 0.6 for 18.58  A  55.74 m2R   .2  0.011A 1 1 Roof Live Load
  • 51. where for pitched roofs: F = Slope x 12 (i.e., = (a/b) x 12) and, for arches or domes: F = (rise-to-span ratio)x32   for F  4 for 4  F 12 for F  120.6 1 2 R   .2  0.05F 1 b a Roof Live Load
  • 52.  The reduced live load must not be less than 50 percent of Lo for members supporting one floor or a section of a single floor, nor less than 40 percent of Lo for members supporting two or more Floors;  For a column or beam supporting more than one floor, the term AT represents the sum of the tributary areas from all floors;  Reduction in live load is not permitted for public assembly areas or when the live load is high (>100 psf). Live Load
  • 53. Roof Live Load Example 3 For the three-story building shown in the figures below. Calculate the design live load supported by the interior column C located in the first story. Assume a 50 lb/ft2 design live load, Lo, on all floors including the roof.
  • 54. Solution Roof live load on Column C: Lr = Lo R1R2 AT = 20(24) = 480ft2 R1 = 1.2 − 0.001 (480) = 0.72 R2 = 1.0 Lroof = LoR1R2 = 50(0.72)(1.0) = 36.0 psf Roof Live Load
  • 55. Roof Live Load Solution Floor live load on Column C: the tributary area for the remaining two floors AT= 2(480) = 960 ft2 KLL AT= 4 * 960 = 3840 ft2 > 400 ft2 (reduction is needed)
  • 56. Solution Total live load on Column C: Since 24.6 lb/ft2 > 0.4 × 50 lb/ft2 = 20 lb/ft2 (the lower limit) So, use L = 24.6 lb/ft2. Load to column = AT(Lroof) + 2AT(Lfloor) = 480(36.0) + 960(24.6) = 40,896 lb = 40.9 kips. Roof Live Load