Electrical Power Systems
Synchronous Generator
By: Mubarek Kurt
 A synchronous machine rotates at a constant speed in the steady
state.
 Unlike induction machines, the rotating air gap field and the rotor
in the synchronous machine rotate at the same speed, called the
synchronous speed.
 Sync. Machine are used primarily as generators of electrical power
(Hydro, nuclear or thermal power stations).
 Like most rotating machines, a synchronous machine can also
operate as both a generator and a motor.
MubarekKurt
 An important feature of a synchronous motor is that it can
draw either lagging or leading reactive current from ac supply
system.
 Its rotor poles are excited by a DC current and its stator
winding (or armature winding) are connected to the AC supply.
MubarekKurt
 The stator of the 3 phase sync. Machine has a 3 phase
distributed winding similar to that of the 3 phase induction
machine.
 The stator winding, which is connected to the ac supply
system, is sometimes called the armature winding. It is
designed for high voltage and current.
 The rotor has a winding called the field winding, which carries
direct current. The field winding on the rotating on the
structure is normally fed from an external dc source through
slip rings and brushes.
MubarekKurt
 Synchronous machines can be broadly divided into 2 groups as
follows:
a) High speed machines with cylindrical (or non-salient pole)
rotors.
b) Low-speed machines with salient pole rotors.
MubarekKurt
MubarekKurt
 Syn. Gen. are by definition sync., meaning that the electrical freq.
is locked in or synchronized with mechanical rate of rotation of the
gen.
 The electrical frequency is synchronized with the mechanical rate
of rotation
 Relationship between magnetic field speed and electrical
frequency,
nm is motor speed in RPM
MubarekKurt
 Determine the rotor speed in RPM of the following 3 phase
synchronous machines
a) f=60Hz, number of poles=6
b) f=50Hz, number of poles=12
c) f=400Hz, number of poles=4
MubarekKurt
The magnitude of the voltage induced in a
given stator phase is
This voltage depends on the flux, ɸ in the
machine, the freq. or speed of rotation, and the
machine construction. The equation can be
simplified as follow
Or
MubarekKurt
• The voltage, Ea is not usually the voltage that
appears at the terminals, Vt of the generator.
• In fact, the only time the internal voltage Ea is
the same as the output voltage, Vt of a phase is
when there is no armature current flowing in
the machine.
• There are some factors that cause the diff.
between Ea and Vt
a) The distortion of the air gap magnetic field by
he current flowing in the stator, called
Armature reaction
b) Self inductance of the armature coilMubarekKurt
 We will explore the effects of the first three factors and derive
a machine model from them.
 The effect of a salient pole shape on the operation of a sync.
Machine will be ignored; in other words, all the machine in
this note are assumed to have non-salient or cyclindrical
rotors.
MubarekKurt
The first effect mentioned, and normally the
largest one is armature reaction.
To understand armature reaction, please refer
below.
The figure shows a 2 pole rotor spinning inside
a 3 phase stator. There is no load connected to
the stator.
The rotor magnetic field BR produces an
internal generated voltage Ea.
With no load, thus Ea=Vt
MubarekKurt
 Now suppose that the gen. is connected to a lagging load. Because
the load is lag. The peak current will occur at an angle behind the
peak voltage.
MubarekKurt
 This current flowing in the stator windings produces a magnetic
field of its own, Bs and produces a voltage of its own in the stator,
Estat.
 With 2 voltages present in the stator winding, the total voltage in
a phase is just sum of internal generated voltage Ea and armature
reaction voltage Estat.
SRnet
statat
BBB
EEV


MubarekKurt
 Since the angle of Ea and BR is the same and the angle of Estat
and Bs are the same, the resulting magnetic field will coincide
with net voltage, Vt.
 First note that, the voltage Estat lies at an angle 90 degree behind
current IA, thus the armature reactionn voltage can be expressed
as
Aat
Astat
jXIEV
jXIE


MubarekKurt
MubarekKurt
 In addition to the effects of armature reaction, the stator coils have
a self inductance, XA and a resistance, RA. Thus,
 Where Xs=Syn. reactance
ASat
As
AAAAAat
IjXEV
XXX
IjRIjXjXIEV



MubarekKurt
Full
equivalen
t circuit
MubarekKurt
MubarekKurt
X=leakage reactance, Xa=armature reaction reactance, Xs=Xa+X=
synchronous reactance, Ra=armature resistance, Zs=synchronous
impedance, Vt=terminal voltages and Em=Magnetizing Voltage.
MubarekKurt
MubarekKurt
MubarekKurt
MubarekKurt
- RA assumed to be zero
-  Torque angle
- Maximum torque due to
max power when sin  is
1
MubarekKurt
Basic torque equation:
From power expression Pout = Pconv =
indm
MubarekKurt
 A 3 phase, 5KVA, 208 V, 4 pole, 60 Hz, star connected sync.
Machine has negligible stator winding resistance and a sync.
Reactance of 8 ohms per phase at rated terminal voltage.
 The machine is first operated as a generator in parallel with a
3phase, 208 V, 60 Hz
a) Determine the excitation voltage and the power angle when the
machine is delivering rated KVA at a 0.8 lagging. Draw the
phasor diagram for this condition.
b) If the field excitation current is now increased by 20 %(without
changing the prime mover), find the stator current , power
factor and reactive KVA supplied by the machine.
c) With the field current as in (a) the prime mover power is slowly
increased. What is the steady state stability limit? What are
the corresponding values of the stator (or armature) current,
PF, and reactive power at the max. power transfer condition?
Draw the phasor diagram for this condition.
MubarekKurt
Purpose of test is to determine these parameters:
a) Field current and flux relationship (and therefore between the
field current and Ea)
b) Synchronous reactance
c) Armature resistance
Open circuit and short circuit tests should be performed in order to
get all parameters
MubarekKurt
Procedures:
1) Generators is rotated at the rated speed
2) No load is connected at the terminals and field current, If is
set to zero.
3) Field current is increased from 0 to maximum and the
terminal Voltage Vt is measured at each step along the way.
With terminal open IA=0, Ea=Vt
4) Record values and plot graph of the terminal voltage and
field current value. This plot is called open circuit
characteristic (OCC) of a generator.
MubarekKurt
IA = 0, so EA = V, possible to plot EA or VT vs IF
graph. It is possible to find internal generated
voltage for any given field current
The iron saturated, mmf
getting slow down due to
increasing reluctance of the
iron
MubarekKurt
Procedures of short circuit test:
1) Generator is rotated at rated speed
2) Adjust field current to 0
3) Short circuit the terminals through a set of ammeters.
4) Measure armature current, Ia or line current as the field
current is increased and plot the graph. This graph is
known as short-circuit characteristic (SCC).
MubarekKurt
The net magnetic field is very small, the
iron is not saturated, so the relationship
is linearMubarekKurt
From the both tests. EA from OCC while IA
from SCC
MubarekKurt
 The resistance is usually determined by applying a DC voltage
to 2 of the stator terminals.
 For Y connection: Ra=R/2=Vdc/(2Idc)
 For Delta connection: Ra=3R/2 =3Vdc/(2Idc)
MubarekKurt
Where,± (+ for lag. Pf, - for lead Pf)
%%
)sin()cos( 22
Vfl
VflVnl
VR
VIaXsVIaRaVnl flfl


 
MubarekKurt
 A 3 phase syn. Gen. rated at 50 kVA, 220 V, 60 Hz is Y
connected. The test results are given below. Find Ra, Zs and
Xs.
 Resistance test: V=2, I=22
 SCT: I1=I2=I3=rated current, If=22 A
 OCT: If=22 A, V=95 V
MubarekKurt
 A 200kVA, 480 V, 50 Hz, Y-connected syn. Gen. with a rated
field current of 5 A was tested, and the following data were
taken:
 Vt,oc at the rated If was measured to be 540 V.
 IL,sc at the rated If was found to be 300 A.
 When a dc voltage of 10 V was applied to 2 of the terminals, a
current of 25 A was measured. Find Ra & Xs
MubarekKurt
A 2300-V 1000-kVA 0.8-PF-lagging 60-Hz two-pole Y-connected
synchronous generator has a synchronous reactance of 1.1 Ω and an
armature resistance of 0.15 Ω. At 60 Hz, its friction and windage
losses are 24 kW, and its core losses are 18 kW. The field circuit has
a dc voltage of 200 V, and the maximum IF is 10 A. The resistance of
the field circuit is adjustable over the range from 20 to 200 Ω. The
OCC of this generator is shown in Figure.
(a) How much field current is required to make VT equal to 2300 V
when the generator is running at no load?
(b) What is the internal generated voltage of this machine at rated
conditions?
(c) How much field current is required to make VT equal to 2300 V
when the generator is running at rated conditions?
(d) How much power and torque must the generator’s prime mover
be capable of supplying?
(e) Construct a capability curve for this generator.
MubarekKurt
MubarekKurt
 A 480V, 50 Hz, Y-connected, 6 pole syn. Gen. has a per-phase syn. Reactance of
1 ohm. Its full load armature current is 60 A at 0.8 PF lagging. This gen. has
friction and windage losses of 1.5 kW and core losses of 1 kW at 60 Hz full
load. Since the armature resistance is being ignored, assume that i2R
negligible. The field current has been adjusted so that the terminal voltage is
480 V at no load.
a) What is the speed of this generator.
b) What is the terminal voltage of this generator if the following are true?
1. It is loaded with the rated current at 0.8 PF lagging.
2. It is loaded with the rated current at 1.0 PF
3. It is loaded with the rated current at 0.8 PF leading.
c) What is the efficiency of this generator when it is operating at the rated
current and 0.8 PF leading?
d) How much shaft torque must be applied by the prime mover at full load?
How large is the induced countertorque.
e) What is the voltage regulation of this generator at 0.8 PF lagging?at 1
PF?at 0.8 PF leading.
MubarekKurt
 A three syn. Gen has the following data;
a) The rated kVA=1250V
b) Rated voltage= 6000V
c) Mode of connection of the armature winding is star.
d) Ra=0.45 ohm, Xs=6.5 ohm.
The machine supplies full load current at 0.85 lagging at normal
rated voltage. Find the terminal voltage at the same excitation
and the load current at 0.85 leading.
MubarekKurt
 At a particular current in the field winding, the short-circuit
armature current of the syn. Gen. attains the value 255 A,
when the open circuit generated nemf becomes 1550 V.
Determine the terminal potential difference when the load
current is 225 A at the 6.63 kV and lagging power factor is 0.8.
assume the armature resistance top be 2.5 ohm
MubarekKurt
 A 1000 kVA, 1200 V 3 phase alternator is Y connected. Its
resistance per phase is 0.12 ohm and the reactance per phase
is 1.5 ohm, Find its voltage regulation if it supplies rates load
at:
a) PF=1
b) PF=0.9 lagging
c) PF = 0.9 Leading
d) What would the no-load line voltage be in part (c)
MubarekKurt
 Repeat previous example but the alternator is delta connected
MubarekKurt
 There are 2 factors that determine the power limits of electric
machines.
 One is mechanical torque on the shaft of the machine, and the
other is the heating of the machine’s windings.
 In all practical syn. Motors and generators, the shaft is strong
enough mechanically to handle a much larger steady state
power than the machine is rated for, so the practical steady
state limits are set by heating in the machine windings.
MubarekKurt
 The stator and rotor heat limits, together with any external
limits on a syn. Gen. can be expressed in graphical form by a
gen. capability diagram.
 A capability diagram is a plot of complex power, S=P+jQ. It is
derived from the phasor diagram of the generator., assuming
that the V is constant at the machine rated voltage.
MubarekKurt
MubarekKurt
Problem statement;
 Notice that for some possible current angles the required EA
exceeds EA,max. If the generator were operated at the rated
armature current and these power factors, the field winding would
burn up.
 Based upon these limits, there is a need to plot the capability of
the synchronous generator. This is so that it can be shown
graphically the limits of the generator.
 A capability diagram is a plot of complex power S=P+jQ. The
capability curve can be derived back from the voltage phasor of the
synchronous generator.
MubarekKurt
 
SS X
V
V
X
V
Q 

 33

S
A
E
X
VE
D 3

On the voltage axes, the origin of the phasor diagram is at -
Vf on the horizontal axis, so the origin on the power
diagram is at:
The field current is proportional to the machine’s flux,
and the flux is proportional to EA = Kfw. The length
corresponding to EA on the power diagram is:
The armature current IA is proportional to XSIA , and the
length corresponding to XSIA on the power diagram is 3VfI-
A.
MubarekKurt
MubarekKurt
Reasons for operating in parallel:
a) Handling larger loads.
b) Maintenance can be done w/t power disruption.
c) Increasing system reliability.
d) Increased efficiency.
MubarekKurt
Condition required:
1) RMS line voltage must be equal.
2) Both have same phase sequence.
3) Output phase angles are same.
4) Must have a slightly higher frequency for new generator. It
will change slowly.
MubarekKurt
 Frequency rating: the frequency at the system.
 Voltage rating: voltage generated that depend on flux and
speed.
 Apparent power rating: maximum power with maximum
armature current.
 Power factor rating:
MubarekKurt
A 480-V 400-kVA 0.85-PF-lagging 50-Hz four-pole Δ-connected
generator is driven by a 500-hp diesel engine and is used as a standby
or emergency generator. This machine can also be paralleled with the
normal power supply (a very large power system) if desired.
(a) What are the conditions required for paralleling the emergency
generator with the existing power system? What is the generator’s rate
of shaft rotation after paralleling occurs?
(b) If the generator is connected to the power system and is initially
floating on the line, sketch the resulting magnetic fields and phasor
diagram.
(c) The governor setting on the diesel is now increased. Show both by
means of house diagrams and by means of phasor diagrams what
happens to the generator. How much reactive power does the generator
supply now?
(d) With the diesel generator now supplying real power to the power
system, what happens to the generator as its field current is increased
and decreased? Show this behavior both with phasor diagrams and with
house diagrams.
MubarekKurt
A 13.8-kV 10-MVA 0.8-PF-lagging 60-Hz two-pole Y-connected
steam-turbine generator has a synchronous reactance of 12 Ω per
phase and an armature resistance of 1.5 Ω per phase. This
generator is operating in parallel with a large power system
(infinite bus).
(a) What is the magnitude of EA at rated conditions?
(b) What is the torque angle of the generator at rated conditions?
(c) If the field current is constant, what is the maximum power
possible out of this generator? How much reserve power or torque
does this generator have at full load?
(d) At the absolute maximum power possible, how much reactive
power will this generator be supplying or consuming? Sketch the
corresponding phasor diagram. (Assume IF is still unchanged.)
MubarekKurt

More Related Content

PDF
Electrical machines 2 AC Machines
PPTX
induction generator final.pptx
PPTX
Synchronous machines
PPT
Motor drives
PDF
THREE PHASE INDUCTION MOTOR, Rotating Magnetic Field (RMF), Slip, Constructio...
PPTX
Frequency Control of Power Systems
PPTX
electrical machines
PDF
Three phase induction motors
Electrical machines 2 AC Machines
induction generator final.pptx
Synchronous machines
Motor drives
THREE PHASE INDUCTION MOTOR, Rotating Magnetic Field (RMF), Slip, Constructio...
Frequency Control of Power Systems
electrical machines
Three phase induction motors

What's hot (20)

PPTX
UNSYMMETRICAL FAULTS IN POWER SYSTEM
PDF
Synchronous generators
PPTX
Working principle of synchronous generator,Synchronous motor, Working princip...
PDF
Automatic load frequency control
PDF
Synchronous generator
PPTX
Lectures synchronous machines(1)
PPT
Synchronous motor
PPTX
Braking methods of induction motor
PPTX
Synchronous generator
PPT
armature Winding
PDF
Chapter 5
PPT
single-phase-induction-motor.ppt
PPTX
Parallel operation of alternators 1
PPTX
Induction machines
PPTX
Electrical Machines - II
PPTX
Induction Motor Drives
PPTX
V Curve and Inverted V Curves
PPTX
Gcsc gto thyristor controlled series capacitor
PPTX
Induction motor modelling and applications
PPTX
Linear Induction Motor
UNSYMMETRICAL FAULTS IN POWER SYSTEM
Synchronous generators
Working principle of synchronous generator,Synchronous motor, Working princip...
Automatic load frequency control
Synchronous generator
Lectures synchronous machines(1)
Synchronous motor
Braking methods of induction motor
Synchronous generator
armature Winding
Chapter 5
single-phase-induction-motor.ppt
Parallel operation of alternators 1
Induction machines
Electrical Machines - II
Induction Motor Drives
V Curve and Inverted V Curves
Gcsc gto thyristor controlled series capacitor
Induction motor modelling and applications
Linear Induction Motor
Ad

Viewers also liked (20)

PPTX
Estimation of Synchronous Generator Parameters from On-line Measurements
PPTX
Synchronous generators
PDF
Synchronous machines
PPTX
Synchronous generator
PPT
Synchronous generator by pankaj chaudhary
PDF
Synchronous generators
DOC
Chapter 4 synchronous machine
DOCX
SYNCHRONOUS MOTOR PROJECT REPORT
PPTX
Synchronous machine Mitesh Kumar
PPTX
EMEC-II, unit 1
PDF
synchronos machines
PPSX
Excitation System & capability curve of synchronous generator
PPT
14+synchronous+motors
PPTX
Synchronous motor drive
PDF
Generation overview
DOC
Ayaz ahmed
PDF
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...
PPT
Meeting w3 chapter 2 part 1
PDF
1st cycle emec lab orientation
PPT
Meditation + guided imagery field guide
Estimation of Synchronous Generator Parameters from On-line Measurements
Synchronous generators
Synchronous machines
Synchronous generator
Synchronous generator by pankaj chaudhary
Synchronous generators
Chapter 4 synchronous machine
SYNCHRONOUS MOTOR PROJECT REPORT
Synchronous machine Mitesh Kumar
EMEC-II, unit 1
synchronos machines
Excitation System & capability curve of synchronous generator
14+synchronous+motors
Synchronous motor drive
Generation overview
Ayaz ahmed
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...
Meeting w3 chapter 2 part 1
1st cycle emec lab orientation
Meditation + guided imagery field guide
Ad

Similar to Electrical Power Systems Synchronous Generator (20)

PDF
Synchronous Generator.pdf
PDF
synchronous generators
PPT
DC Machines with explanation in detail of everything
PPTX
dipSS SNJS SNJS JQNSSKSSIJIJISJJ SQNJNS .pptx
PDF
Assignment & solution (selected)
PPTX
Electrical Power Systems 3 phase apparatus
DOCX
New microsoft word document
PDF
Lecture 07 synchronous machines
PPT
16888242.ppt
PPTX
DC Machinesmechnacial engernerring .pptx
PPT
DC_Machines_week_4.ppt
PPT
DC_Machines.ppt
PDF
Some Aspects on 3-Phase Bridge Inverter (180 Degree Mode)
PDF
Dc machines
PDF
ac_machinery_im.pdf
PPT
1337683699.3104Lecture 07 - Synchronous machines.ppt
PPTX
BASICS OF SYNCHROUS MACHINE AS ELECTRICAL MACHINE.pptx
PPTX
Electrical machines lecture notes
PPT
Synchmachine
PPT
Lecture dc machines
Synchronous Generator.pdf
synchronous generators
DC Machines with explanation in detail of everything
dipSS SNJS SNJS JQNSSKSSIJIJISJJ SQNJNS .pptx
Assignment & solution (selected)
Electrical Power Systems 3 phase apparatus
New microsoft word document
Lecture 07 synchronous machines
16888242.ppt
DC Machinesmechnacial engernerring .pptx
DC_Machines_week_4.ppt
DC_Machines.ppt
Some Aspects on 3-Phase Bridge Inverter (180 Degree Mode)
Dc machines
ac_machinery_im.pdf
1337683699.3104Lecture 07 - Synchronous machines.ppt
BASICS OF SYNCHROUS MACHINE AS ELECTRICAL MACHINE.pptx
Electrical machines lecture notes
Synchmachine
Lecture dc machines

Recently uploaded (20)

PPT
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
PPTX
Internet of Things (IOT) - A guide to understanding
PPT
Mechanical Engineering MATERIALS Selection
PPTX
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PDF
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
PPT
Project quality management in manufacturing
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
PPTX
additive manufacturing of ss316l using mig welding
PPTX
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
PPTX
bas. eng. economics group 4 presentation 1.pptx
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
Lecture Notes Electrical Wiring System Components
PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
CRASH COURSE IN ALTERNATIVE PLUMBING CLASS
Internet of Things (IOT) - A guide to understanding
Mechanical Engineering MATERIALS Selection
M Tech Sem 1 Civil Engineering Environmental Sciences.pptx
R24 SURVEYING LAB MANUAL for civil enggi
SM_6th-Sem__Cse_Internet-of-Things.pdf IOT
Project quality management in manufacturing
Embodied AI: Ushering in the Next Era of Intelligent Systems
additive manufacturing of ss316l using mig welding
MCN 401 KTU-2019-PPE KITS-MODULE 2.pptx
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
CYBER-CRIMES AND SECURITY A guide to understanding
bas. eng. economics group 4 presentation 1.pptx
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
UNIT-1 - COAL BASED THERMAL POWER PLANTS
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
Lecture Notes Electrical Wiring System Components
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx

Electrical Power Systems Synchronous Generator

  • 1. Electrical Power Systems Synchronous Generator By: Mubarek Kurt
  • 2.  A synchronous machine rotates at a constant speed in the steady state.  Unlike induction machines, the rotating air gap field and the rotor in the synchronous machine rotate at the same speed, called the synchronous speed.  Sync. Machine are used primarily as generators of electrical power (Hydro, nuclear or thermal power stations).  Like most rotating machines, a synchronous machine can also operate as both a generator and a motor. MubarekKurt
  • 3.  An important feature of a synchronous motor is that it can draw either lagging or leading reactive current from ac supply system.  Its rotor poles are excited by a DC current and its stator winding (or armature winding) are connected to the AC supply. MubarekKurt
  • 4.  The stator of the 3 phase sync. Machine has a 3 phase distributed winding similar to that of the 3 phase induction machine.  The stator winding, which is connected to the ac supply system, is sometimes called the armature winding. It is designed for high voltage and current.  The rotor has a winding called the field winding, which carries direct current. The field winding on the rotating on the structure is normally fed from an external dc source through slip rings and brushes. MubarekKurt
  • 5.  Synchronous machines can be broadly divided into 2 groups as follows: a) High speed machines with cylindrical (or non-salient pole) rotors. b) Low-speed machines with salient pole rotors. MubarekKurt
  • 7.  Syn. Gen. are by definition sync., meaning that the electrical freq. is locked in or synchronized with mechanical rate of rotation of the gen.  The electrical frequency is synchronized with the mechanical rate of rotation  Relationship between magnetic field speed and electrical frequency, nm is motor speed in RPM MubarekKurt
  • 8.  Determine the rotor speed in RPM of the following 3 phase synchronous machines a) f=60Hz, number of poles=6 b) f=50Hz, number of poles=12 c) f=400Hz, number of poles=4 MubarekKurt
  • 9. The magnitude of the voltage induced in a given stator phase is This voltage depends on the flux, ɸ in the machine, the freq. or speed of rotation, and the machine construction. The equation can be simplified as follow Or MubarekKurt
  • 10. • The voltage, Ea is not usually the voltage that appears at the terminals, Vt of the generator. • In fact, the only time the internal voltage Ea is the same as the output voltage, Vt of a phase is when there is no armature current flowing in the machine. • There are some factors that cause the diff. between Ea and Vt a) The distortion of the air gap magnetic field by he current flowing in the stator, called Armature reaction b) Self inductance of the armature coilMubarekKurt
  • 11.  We will explore the effects of the first three factors and derive a machine model from them.  The effect of a salient pole shape on the operation of a sync. Machine will be ignored; in other words, all the machine in this note are assumed to have non-salient or cyclindrical rotors. MubarekKurt
  • 12. The first effect mentioned, and normally the largest one is armature reaction. To understand armature reaction, please refer below. The figure shows a 2 pole rotor spinning inside a 3 phase stator. There is no load connected to the stator. The rotor magnetic field BR produces an internal generated voltage Ea. With no load, thus Ea=Vt MubarekKurt
  • 13.  Now suppose that the gen. is connected to a lagging load. Because the load is lag. The peak current will occur at an angle behind the peak voltage. MubarekKurt
  • 14.  This current flowing in the stator windings produces a magnetic field of its own, Bs and produces a voltage of its own in the stator, Estat.  With 2 voltages present in the stator winding, the total voltage in a phase is just sum of internal generated voltage Ea and armature reaction voltage Estat. SRnet statat BBB EEV   MubarekKurt
  • 15.  Since the angle of Ea and BR is the same and the angle of Estat and Bs are the same, the resulting magnetic field will coincide with net voltage, Vt.  First note that, the voltage Estat lies at an angle 90 degree behind current IA, thus the armature reactionn voltage can be expressed as Aat Astat jXIEV jXIE   MubarekKurt
  • 17.  In addition to the effects of armature reaction, the stator coils have a self inductance, XA and a resistance, RA. Thus,  Where Xs=Syn. reactance ASat As AAAAAat IjXEV XXX IjRIjXjXIEV    MubarekKurt
  • 20. X=leakage reactance, Xa=armature reaction reactance, Xs=Xa+X= synchronous reactance, Ra=armature resistance, Zs=synchronous impedance, Vt=terminal voltages and Em=Magnetizing Voltage. MubarekKurt
  • 24. - RA assumed to be zero -  Torque angle - Maximum torque due to max power when sin  is 1 MubarekKurt
  • 25. Basic torque equation: From power expression Pout = Pconv = indm MubarekKurt
  • 26.  A 3 phase, 5KVA, 208 V, 4 pole, 60 Hz, star connected sync. Machine has negligible stator winding resistance and a sync. Reactance of 8 ohms per phase at rated terminal voltage.  The machine is first operated as a generator in parallel with a 3phase, 208 V, 60 Hz a) Determine the excitation voltage and the power angle when the machine is delivering rated KVA at a 0.8 lagging. Draw the phasor diagram for this condition. b) If the field excitation current is now increased by 20 %(without changing the prime mover), find the stator current , power factor and reactive KVA supplied by the machine. c) With the field current as in (a) the prime mover power is slowly increased. What is the steady state stability limit? What are the corresponding values of the stator (or armature) current, PF, and reactive power at the max. power transfer condition? Draw the phasor diagram for this condition. MubarekKurt
  • 27. Purpose of test is to determine these parameters: a) Field current and flux relationship (and therefore between the field current and Ea) b) Synchronous reactance c) Armature resistance Open circuit and short circuit tests should be performed in order to get all parameters MubarekKurt
  • 28. Procedures: 1) Generators is rotated at the rated speed 2) No load is connected at the terminals and field current, If is set to zero. 3) Field current is increased from 0 to maximum and the terminal Voltage Vt is measured at each step along the way. With terminal open IA=0, Ea=Vt 4) Record values and plot graph of the terminal voltage and field current value. This plot is called open circuit characteristic (OCC) of a generator. MubarekKurt
  • 29. IA = 0, so EA = V, possible to plot EA or VT vs IF graph. It is possible to find internal generated voltage for any given field current The iron saturated, mmf getting slow down due to increasing reluctance of the iron MubarekKurt
  • 30. Procedures of short circuit test: 1) Generator is rotated at rated speed 2) Adjust field current to 0 3) Short circuit the terminals through a set of ammeters. 4) Measure armature current, Ia or line current as the field current is increased and plot the graph. This graph is known as short-circuit characteristic (SCC). MubarekKurt
  • 31. The net magnetic field is very small, the iron is not saturated, so the relationship is linearMubarekKurt
  • 32. From the both tests. EA from OCC while IA from SCC MubarekKurt
  • 33.  The resistance is usually determined by applying a DC voltage to 2 of the stator terminals.  For Y connection: Ra=R/2=Vdc/(2Idc)  For Delta connection: Ra=3R/2 =3Vdc/(2Idc) MubarekKurt
  • 34. Where,± (+ for lag. Pf, - for lead Pf) %% )sin()cos( 22 Vfl VflVnl VR VIaXsVIaRaVnl flfl     MubarekKurt
  • 35.  A 3 phase syn. Gen. rated at 50 kVA, 220 V, 60 Hz is Y connected. The test results are given below. Find Ra, Zs and Xs.  Resistance test: V=2, I=22  SCT: I1=I2=I3=rated current, If=22 A  OCT: If=22 A, V=95 V MubarekKurt
  • 36.  A 200kVA, 480 V, 50 Hz, Y-connected syn. Gen. with a rated field current of 5 A was tested, and the following data were taken:  Vt,oc at the rated If was measured to be 540 V.  IL,sc at the rated If was found to be 300 A.  When a dc voltage of 10 V was applied to 2 of the terminals, a current of 25 A was measured. Find Ra & Xs MubarekKurt
  • 37. A 2300-V 1000-kVA 0.8-PF-lagging 60-Hz two-pole Y-connected synchronous generator has a synchronous reactance of 1.1 Ω and an armature resistance of 0.15 Ω. At 60 Hz, its friction and windage losses are 24 kW, and its core losses are 18 kW. The field circuit has a dc voltage of 200 V, and the maximum IF is 10 A. The resistance of the field circuit is adjustable over the range from 20 to 200 Ω. The OCC of this generator is shown in Figure. (a) How much field current is required to make VT equal to 2300 V when the generator is running at no load? (b) What is the internal generated voltage of this machine at rated conditions? (c) How much field current is required to make VT equal to 2300 V when the generator is running at rated conditions? (d) How much power and torque must the generator’s prime mover be capable of supplying? (e) Construct a capability curve for this generator. MubarekKurt
  • 39.  A 480V, 50 Hz, Y-connected, 6 pole syn. Gen. has a per-phase syn. Reactance of 1 ohm. Its full load armature current is 60 A at 0.8 PF lagging. This gen. has friction and windage losses of 1.5 kW and core losses of 1 kW at 60 Hz full load. Since the armature resistance is being ignored, assume that i2R negligible. The field current has been adjusted so that the terminal voltage is 480 V at no load. a) What is the speed of this generator. b) What is the terminal voltage of this generator if the following are true? 1. It is loaded with the rated current at 0.8 PF lagging. 2. It is loaded with the rated current at 1.0 PF 3. It is loaded with the rated current at 0.8 PF leading. c) What is the efficiency of this generator when it is operating at the rated current and 0.8 PF leading? d) How much shaft torque must be applied by the prime mover at full load? How large is the induced countertorque. e) What is the voltage regulation of this generator at 0.8 PF lagging?at 1 PF?at 0.8 PF leading. MubarekKurt
  • 40.  A three syn. Gen has the following data; a) The rated kVA=1250V b) Rated voltage= 6000V c) Mode of connection of the armature winding is star. d) Ra=0.45 ohm, Xs=6.5 ohm. The machine supplies full load current at 0.85 lagging at normal rated voltage. Find the terminal voltage at the same excitation and the load current at 0.85 leading. MubarekKurt
  • 41.  At a particular current in the field winding, the short-circuit armature current of the syn. Gen. attains the value 255 A, when the open circuit generated nemf becomes 1550 V. Determine the terminal potential difference when the load current is 225 A at the 6.63 kV and lagging power factor is 0.8. assume the armature resistance top be 2.5 ohm MubarekKurt
  • 42.  A 1000 kVA, 1200 V 3 phase alternator is Y connected. Its resistance per phase is 0.12 ohm and the reactance per phase is 1.5 ohm, Find its voltage regulation if it supplies rates load at: a) PF=1 b) PF=0.9 lagging c) PF = 0.9 Leading d) What would the no-load line voltage be in part (c) MubarekKurt
  • 43.  Repeat previous example but the alternator is delta connected MubarekKurt
  • 44.  There are 2 factors that determine the power limits of electric machines.  One is mechanical torque on the shaft of the machine, and the other is the heating of the machine’s windings.  In all practical syn. Motors and generators, the shaft is strong enough mechanically to handle a much larger steady state power than the machine is rated for, so the practical steady state limits are set by heating in the machine windings. MubarekKurt
  • 45.  The stator and rotor heat limits, together with any external limits on a syn. Gen. can be expressed in graphical form by a gen. capability diagram.  A capability diagram is a plot of complex power, S=P+jQ. It is derived from the phasor diagram of the generator., assuming that the V is constant at the machine rated voltage. MubarekKurt
  • 47. Problem statement;  Notice that for some possible current angles the required EA exceeds EA,max. If the generator were operated at the rated armature current and these power factors, the field winding would burn up.  Based upon these limits, there is a need to plot the capability of the synchronous generator. This is so that it can be shown graphically the limits of the generator.  A capability diagram is a plot of complex power S=P+jQ. The capability curve can be derived back from the voltage phasor of the synchronous generator. MubarekKurt
  • 48.   SS X V V X V Q    33  S A E X VE D 3  On the voltage axes, the origin of the phasor diagram is at - Vf on the horizontal axis, so the origin on the power diagram is at: The field current is proportional to the machine’s flux, and the flux is proportional to EA = Kfw. The length corresponding to EA on the power diagram is: The armature current IA is proportional to XSIA , and the length corresponding to XSIA on the power diagram is 3VfI- A. MubarekKurt
  • 50. Reasons for operating in parallel: a) Handling larger loads. b) Maintenance can be done w/t power disruption. c) Increasing system reliability. d) Increased efficiency. MubarekKurt
  • 51. Condition required: 1) RMS line voltage must be equal. 2) Both have same phase sequence. 3) Output phase angles are same. 4) Must have a slightly higher frequency for new generator. It will change slowly. MubarekKurt
  • 52.  Frequency rating: the frequency at the system.  Voltage rating: voltage generated that depend on flux and speed.  Apparent power rating: maximum power with maximum armature current.  Power factor rating: MubarekKurt
  • 53. A 480-V 400-kVA 0.85-PF-lagging 50-Hz four-pole Δ-connected generator is driven by a 500-hp diesel engine and is used as a standby or emergency generator. This machine can also be paralleled with the normal power supply (a very large power system) if desired. (a) What are the conditions required for paralleling the emergency generator with the existing power system? What is the generator’s rate of shaft rotation after paralleling occurs? (b) If the generator is connected to the power system and is initially floating on the line, sketch the resulting magnetic fields and phasor diagram. (c) The governor setting on the diesel is now increased. Show both by means of house diagrams and by means of phasor diagrams what happens to the generator. How much reactive power does the generator supply now? (d) With the diesel generator now supplying real power to the power system, what happens to the generator as its field current is increased and decreased? Show this behavior both with phasor diagrams and with house diagrams. MubarekKurt
  • 54. A 13.8-kV 10-MVA 0.8-PF-lagging 60-Hz two-pole Y-connected steam-turbine generator has a synchronous reactance of 12 Ω per phase and an armature resistance of 1.5 Ω per phase. This generator is operating in parallel with a large power system (infinite bus). (a) What is the magnitude of EA at rated conditions? (b) What is the torque angle of the generator at rated conditions? (c) If the field current is constant, what is the maximum power possible out of this generator? How much reserve power or torque does this generator have at full load? (d) At the absolute maximum power possible, how much reactive power will this generator be supplying or consuming? Sketch the corresponding phasor diagram. (Assume IF is still unchanged.) MubarekKurt