Fuzzy Logic Method in SCADA to Optimize Network Electric
Power Smart Grid
Wasum1
, SholehHadi Pramono2
, Rahmadwati3
Department of Electrical Engineering, University ofBrawijaya, Indonesia
Abstract: Smart grid is one of the solutions in terms of distribution of electricity to make it more effective and
reliable. One of the main functions of the smart grid is to provide an important role in maintaining the reliability
of electricity supply. Some sections in the smart grid include existing equipment at the site and the central
computer. In order to convey the data from the site plant to the central computer, it needs a smart grid
instrument controllers like SCADA. SCADA has a role to monitor, control, and communicate in two-ways
between equipment on the site plant and the central computer. In SCADA systems, we often experience
difficulty in obtaining data such as uncertainty of data and non-precision data. Then a method to overcome it is
needed. In this study, Fuzzy Logic is used to detect network conditions toward the aspects of loading and the
interference of overcurrent. Using four input variables with three and four linguistic value and four output
variable with two linguistic value has resulted in eighty one rule base. Identification of faults was conducted by
how big the DC voltage and the current. Once validated by SCADA systems and the use of Fuzzy Logic, we
obtained 97.53% of the perfection of the system.
Keywords: Fault, Fuzzy Logic, SCADA, Smart grid
I. INTRODUCTION
The needs of electricity in Indonesia has increased every year. It was proved by the increase in the
average growth of 8.6% from 216.8 TWh (Tera Watt Hour) to 457.0 TWh throughout 2016 and 2025. To meet
it, the Indonesian government has tried to build and renew generation facilities, rearrange the transmission
network, and rearrange the distribution network. The obstacle of the government's efforts includes limited
electricity supply due to differences in geographic location so that the electricity weren’t fulfilled. The power
supply in Indonesia is currently using interconnection system that is used by all major islands, while small
islands are still using the isolated system and has reached the electrification ratio up to 88.3% [1].
In recent years, Indonesia is building an interconnection system. It is proven by the efforts of the
government to operate a new power plant, add plant reliability, improve the reliability of the transmission
system, strengthen the transformer in the substation, increase the recovery of electricity supply during faults and
open up the possibility of a hybrid solar power and hybrid thermal power station. The Government's efforts are
aimed to anticipate growth in customer demand, maintain continuity of power supply and maintain, steady
voltage in accordance with the needs and automation of network operation of electricity[2].
Based on the above elaboration, in 2011 Gao and Redfern tried to provide solution by creating a more
effective and reliable electrical distribution. In that study, smart grid system was used. This system had used
smart devices, modern communication systems and reliable management system[3]. Other advantages of this
system were to have a large capacity in monitoring data generated by an integrated, data analysis for supporting
decision, increased security, effectiveness in communication, to meet customer demand and reduce energy
consumption and costs.
Based on the research conducted by Gao and Redfern, Borlase (2013) tried to provide a solution by
creating a control instrument in the smart grid. The instrument was a Supervisory Control and Data Acquisition
(SCADA) [4]. This system referred to a system or combination of systems that and collect data from various
sensors which were located in the site plant. Then they sent the data to a central computer which was then used
to view, manage and control devices in the site plant. Broadly speaking, SCADA installed in the central
computer with SCADA software in it, the appearance of the Graphical User Interface (GUI), front-end data
acquisition equipment, presenting data and information in real-time, intelligent alarm processing, can use thin
clients and web-based clients, using one or more Remote Terminal Unit (RTU) and using a communication
system. Utilization of SCADA systems in the power network aims to obtain data in real-time on the site plant as
it is in the power plants, substations transmission and distribution, feeder distribution, and other devices, giving
orders to the equipment located at the site of the plant with response time ranges between 1-5 seconds.
When we pay attention on its components, SCADA consists of two components, field devices such as
RTU, and central computer. RTU is a microprocessor device which transfers the telemetry data to the central
computer. RTU is located in the plant site. The main functions of RTU are interfacing input/output, collecting
data, presenting data to a central computer, and manipulating the data before it is sent to the central computer.
Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid
www.ijres.org 23 | Page
Meanwhile, the central computer is a computer system that is responsive to the circumstances which occur in
the RTU. In large SCADA system, central computer serves to reduce double data, distribute software, and
record events which occur on each device.
According to the research conducted by Gouzhen et al in 2009, SCADA systems were used for
monitoring, controlling, and two-way communication between the central computer and the photovoltaic power
plant. There were two basic studies in this research. They were a match between the conditions at the plant site
in the central computer and a server configuration SCADA[5].
Every complex system definitely will have some risks. Some risks that occur in the SCADA are the
breakdown of communication between the central computer and the device at the site plant, the unstable data
transmission, and the damage to system which causes faults[6].
SCADA systems often have difficulty in obtaining data from the RTU. Some of the difficulties are the
amount of noise, the uncertainty of data, and the ambiguous data obtained in the SCADA system. To overcome
this, Kumar et al are using Fuzzy Logic. Because Fuzzy Logic is able to cope with the uncertainty and non-
precision data received from the RTU to the central computer. In this methods there is membership function and
rule base that can be adapted to the needs [7]-[8].
Based on the explanation above, this research focuses on the use of Fuzzy Logic in SCADA which is
used to detect faults that occur on the network due to fault of overcurrent and load.
II. MATERIALS
In the SCADA system, the quality of the measurement depends on the transducer and converter,
telemetered to control systems via communication links. One of the components in SCADA located at the site of
plant is RTU in which there are inputs and outputs such as analogue-to-digital converters, digital-to-analogue
converters, analog inputs, digital inputs and digital outputs and communication ports in it.
The data used in this research is data types such as voltages and currents generated by the devices on
site plant and the voltage and current received by the central computer, fault, response time which occurs during
and after faults as well as length of transmission media used.
III. METHOD
3.1. Measurement
For measurement, the data was obtained from the following ways: First, by using the data changes to
large voltages and currents generated by the devices on site plant so that voltage and current received central
computer will adjust magnitude. Second, by using multiple nodes as a source of voltage and current and form a
network, then between the node, a fault was created. It will affect the delivery of data and information to the
central computer. Third, doing the analysis using fuzzy logic by doing data collection first and then process
them to obtain the rule for any condition of input results. Then the data will be saved and will be used by Fuzzy
Logic in determining the output to obtain optimum use of resources and load usage.
3.2. System Scheme
In this study, a scheme of the system as shown in Figure 1 is used.
PC Gateway Hub/SwitchEth
Analog Input
Eth
Digital Input /
Digital Output
Eth
Central Computer
Site
PV #1
1
2
2
PV #2
PV #n
1
2
1
1
2 Status
Metering
Figure 1. System Scheme
Based on Figure 1, it was concluded that: First, PC Gateway is a unit which displays and stores data
generated by the site plant section. Second, PC Gateway will provide data and information in the SCADA
system. Third, status and control of existing equipment at the site plant will be read by a sensor device that has a
digital input and digital output. Fourth, the measurement will be addressed by tools which have inputs analog
sensor. Fifth, the source voltage and current are generated by photovoltaic (VP).
3.3. Fuzzy Logic
In this study, the method of Fuzzy Logic used can be seen in Figure 2.
Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid
www.ijres.org 24 | Page
Input Rule Base Output
Figure 2.Structure of Fuzzy Logic
In fuzification in taking input and has been predetermined the degree of membership. In this study, four
input variables, namely volt1, volt2, volt3 and volt4 are taken. It generates four output variables which are
relay1, relay2, relay3 and relay4. The value of all the linguistic input variables is divided into three: low, normal
and high, while the linguistic value of the output is divided into two: open and close.
Each input variables have low membership function with a voltage range between 0V up to 2V, normal
to the voltage range between 2V up to 9V and high voltage range between 9V up to 10V. Meanwhile, the output
variable has an open membership functions which have a normal stress, and has covered the low and high
voltage.
From the results of fuzification input, eighty one rule base was obtained. This rule base was
implemented on Analog Input tool and displayed in the form of SCADA systems on the PC Gateway. Here are
two of the eighty one rule base obtained: First, when volt1 is low, and volt2 is low, and volt3 is low and volt4 is
low, then relay1 is opened, and relay2 is opened, and relay3 is opened, and relay4 is opened. Secondly, when
volt1 is normal, and volt2 is normal, and volt3 is high, and volt4 is high, then relay1 is opened, and relay2 is
opened, and relay3 is closed, and relay4 is closed.
3.4. SCADA System
In this study, SCADA systems are used to display data and information such as status, control and
measurement of the devices that exist in the plant site and then the data will be sent to the PC Gateway. Then the
data will be stored in the existing database on a PC Gateway that will serve as a log.
Globally, the display of SCADA can be seen in Figure 3.
Menu
#1
Menu
#2
Menu
#nTitle
Clock
Date
Alarm
Chart of Measurement
(Real Time)
Measurement
PV #1
PV #2
PV #n
Control Relay
Status of
Measurement
Figure 3. SCADA Layout
In this study, the SCADA system layout is divided into three sections: Header, Body and Footer. The
Header section is used for the placement of titles, multiple menus which are used, the time and date information.
Meanwhile, the Body section is used to display features such as charts and bar voltage measurements in real-
time generated by PV. In the control relay, it is used to control relays manually or automatically and on the
status of measurement, it is used as a condition of the relay and PV connected/on or disconnected/off on
SCADA systems. Finally, on the Footer it is used to display event and alarm which occur in real-time.
IV. EXPERIMENT AND RESULTS
4.1. Measurement
In this study, four measurements of solar panel modules are used. This solar panel module serves to
transform solar energy into DC power. These solar panels have each specification Maximum Power (Pmax) of
100W. Figure 4 is voltage measurements which have ever been done. The voltage values measured is up to 10V,
and the smallest time used is milliseconds (ms).
Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid
www.ijres.org 25 | Page
Figure 4. Voltage measurements
In this measurement, it has also been implemented with fuzzy logic membership functions numbers 1-2
which mean low, the rate of ≥ 2 - ≤ 18 which meansnormal and the number >18 which meanshigh. In the
measurement of value of <2 and >18, the graph shown is red. Still in the graph, the triangle mark above
illustrates the highest voltage and the triangle below illustrates the lowest voltage during the measurement taken.
4.2. SCADA System
Tests conducted on the SCADA system aims to determine whether the design results system has
functioned properly and in accordance with the recommended specifications. Tests performed include First,
making sure all devices on the central computer and the site plant have been connected in accordance with the
procedure. Second, making sure that application of SCADA system can be operated in line with expectations.
Third, testing the SCADA system which serves to communicate between devices on the site plant, central
computer and user.
The display of this test is shown in Figure 5.
Figure 5. Display SCADA System Testing
Figure 5 has included some details of which are measurements that have been done in real-time which
amounted PV1 and PV2 of 8,33V and 8,21V, relay status is shown in DI1 to DI4 is ON.
4.3. Scenario of Fault
Scenario of fault in this study is used to test and measure the robustness of the system that has been
created. Several scenarios of faults that have been made can be seen in Figure 6 and Table 1.
PC Gateway Hub/Switch1
Analog Input
Digital Input /
Digital Output
2 4
PV #2
PV #n
3
5
PV #1
Figure 6. Scenario of fault
Table 1. Scenario of fault
Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid
www.ijres.org 26 | Page
No Description
Cable
Length
Response
Time
1 UTP cable is disconnected between the Gateway PC
and Hub / Switch
1m 0,1ms
2 UTP cable is disconnected between Hub/Switch with
Analog Input module and Digital Input module.
2m 0,2ms
3 Negative cable is disconnected between Analog Input
module and PV #1
5m 0,5ms
4 Cable is disconnected between Digital Input module
and the PV #2
5m 0,4ms
5 UTP cable is disconnected between the PC Gateway
and Analog Input module which is connected directly
3m 0,2ms
V. CONCLUSION
The use of Fuzzy Logic was conducted to determine the membership functions of the four input and
four output voltage magnitude condition of the relay. Membership function has obtained eighty-one rule base.
The calculation of Fuzzy Logic has been implemented in Analog Input module and into the SCADA system.
Once validated between SCADA systems and the use of Fuzzy Logic, then we obtained 97.53% of the
perfection of the system or two of the 81 rule base to be evaluated.
ACKNOWLEDGEMENTS
We would like to express many thanks to the Electrical Engineering University of Brawijaya which has
supported our research.
REFERENCES
[1]. Perusahaan Listrik Negara, Rencana Usaha PenyediaanTenagaListrik (RUPTL) PT. PLN (Persero) Tahun
2016-2025, (Jakarta : Perusahaan Listrik Negara, 2016).
[2]. Perusahaan Listrik Negara, Statistik PLN 2014, (Jakarta : Perusahaan Listrik Negara, 2015).
[3]. Gao, C, and Redfern, M.A., A Review of Voltage Control in Smart Grid and Smart Metering Technologies
on Distribution Networks. 46th
International Universities Power Engineering Conference. Germany. 2011.
[4]. Borlase S., Smart Grid: Infrastructure, Technology, and Solutions, (Boca Raton: CRC Press, 2013).
[5]. Guozhen H, Tao C, Changsong C, and Shanxu D. Solution for SCADA System Configuration Reliability
in Photovoltaic Power Plant, IEEE, IPEMC, 2009, 2482-2485.
[6]. Hamoud G, Chen RL, and Bradley I, Risk Assessment of Power System SCADA, 2003, 758-764.
[7]. Kumar P, Jamil M, Thomas MS, and Moinuddin, Fuzzy Approach to Fault Classification for Transmission
Line Protection. IEEE. TENCON, 1999, 1046-1050.
[8]. Naba A., BelajarCepat Fuzzy Logic Menggunakan MATLAB, (Yogyakarta :Andi Publisher, 2008).

More Related Content

PDF
Energy, economic and environmental analysis of fuzzy logic controllers used i...
PDF
Machine learning based multi class fault diagnosis tool for voltage source in...
PDF
Development of a software solution for solar pv power systems sizing and moni...
PDF
Dhiraj power system automation
PDF
23 9754 assessment paper id 0023 (ed l)2
PDF
Automatic Meter Reading using PLC
PDF
Power quality analysis using lab view
PDF
Design of an intelligent nitrogen injection system for fire saftey of power t...
Energy, economic and environmental analysis of fuzzy logic controllers used i...
Machine learning based multi class fault diagnosis tool for voltage source in...
Development of a software solution for solar pv power systems sizing and moni...
Dhiraj power system automation
23 9754 assessment paper id 0023 (ed l)2
Automatic Meter Reading using PLC
Power quality analysis using lab view
Design of an intelligent nitrogen injection system for fire saftey of power t...

What's hot (19)

PDF
A REVIEW OF SELF HEALING SMART GRIDS USING THE MULTIAGENT SYSTEM
PDF
Evaluation of electrical load estimation in Diyala governorate (Baaquba city)...
PDF
Wireless data acquisition for photovoltaic power system copy
PDF
Study on the performance indicators for smart grids: a comprehensive review
PDF
Final paperenhancing distribution system through the use of real time etherne...
PDF
Fulltext 1005224
PDF
Prepaid and Postpaid Energy Meter for Billing System Using Microcontroller an...
PDF
Real time energy data acquisition and alarming system for monitoring power co...
PDF
Real time energy data acquisition and alarming system for monitoring power co...
PDF
A cognitive energy distribution system
PDF
IRJET - Energy Consumption Indicator
PDF
Power System Reliability Assessment in a Complex Restructured Power System
PDF
PDF
Using Alternative Energy Sources Way to Intellectualization and Greater Energ...
PDF
IRJET-A Novel Approach for Automatic Monitoring of Power Consumption using S...
PDF
IRJET-Effect of Network Reconfiguration on Power Quality of Distribution System
PDF
Cired2011 0405 final
PDF
Wide area protection-research_in_the_smart_grid
PDF
Afa wea
A REVIEW OF SELF HEALING SMART GRIDS USING THE MULTIAGENT SYSTEM
Evaluation of electrical load estimation in Diyala governorate (Baaquba city)...
Wireless data acquisition for photovoltaic power system copy
Study on the performance indicators for smart grids: a comprehensive review
Final paperenhancing distribution system through the use of real time etherne...
Fulltext 1005224
Prepaid and Postpaid Energy Meter for Billing System Using Microcontroller an...
Real time energy data acquisition and alarming system for monitoring power co...
Real time energy data acquisition and alarming system for monitoring power co...
A cognitive energy distribution system
IRJET - Energy Consumption Indicator
Power System Reliability Assessment in a Complex Restructured Power System
Using Alternative Energy Sources Way to Intellectualization and Greater Energ...
IRJET-A Novel Approach for Automatic Monitoring of Power Consumption using S...
IRJET-Effect of Network Reconfiguration on Power Quality of Distribution System
Cired2011 0405 final
Wide area protection-research_in_the_smart_grid
Afa wea
Ad

Similar to Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid (20)

PPTX
Application of scada for system automation on smart grid rev2
PDF
Implementation of Automation for the Seamless Identification of Fault in Mode...
PDF
Smart Grid Technology - The Future of Power Network: A Review
PPT
Airtificial Intelligence in Power System
PPTX
Dhiraj seminar # power system automation
PPTX
Dhiraj seminar # power system automation
PPTX
Dhiraj seminar # power system automation
PDF
FUZZY LOGIC APPROACH FOR FAULT DIAGNOSIS OF THREE PHASE TRANSMISSION LINE
PPTX
Smart grid distribution system
PDF
Fuzzy Logic-Based Fault Classification for Transmission Line Analysis
PDF
Research Gate Smart Grid
PDF
Transformer Smart Grid
PDF
IRJET-Comparative Study on Evolution of State of Art Practices on Smart Grid ...
PPTX
The efficacy and challenges of scada an smart grid integration
PDF
Advantages and recent advances of smart energy grid
DOCX
PSOkajaiajajsjsjsushehdydnshC_SKG_RG.docx
PDF
06011696
PDF
Implementation of a decentralized real-time management system for electrical ...
PDF
Smart Grid Technologies in Power Systems An Overview
PDF
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Application of scada for system automation on smart grid rev2
Implementation of Automation for the Seamless Identification of Fault in Mode...
Smart Grid Technology - The Future of Power Network: A Review
Airtificial Intelligence in Power System
Dhiraj seminar # power system automation
Dhiraj seminar # power system automation
Dhiraj seminar # power system automation
FUZZY LOGIC APPROACH FOR FAULT DIAGNOSIS OF THREE PHASE TRANSMISSION LINE
Smart grid distribution system
Fuzzy Logic-Based Fault Classification for Transmission Line Analysis
Research Gate Smart Grid
Transformer Smart Grid
IRJET-Comparative Study on Evolution of State of Art Practices on Smart Grid ...
The efficacy and challenges of scada an smart grid integration
Advantages and recent advances of smart energy grid
PSOkajaiajajsjsjsushehdydnshC_SKG_RG.docx
06011696
Implementation of a decentralized real-time management system for electrical ...
Smart Grid Technologies in Power Systems An Overview
Detection of Power Grid Synchronization Failure on Sensing Frequency and Volt...
Ad

More from IJRESJOURNAL (20)

PDF
Injection Analysis of Hera And Betano New Power Plants At the Interconnection...
PDF
Harmonic AnalysisofDistribution System Due to Embedded Generation Injection
PDF
Decision Support System Implementation for Candidate Selection of the Head of...
PDF
Yield Forecasting to Sustain the Agricultural Transportation UnderStochastic ...
PDF
Injection Analysis of 5 Mwp Photovoltaic Power Plant on 20 Kv Distribution Ne...
PDF
Developing A Prediction Model for Tensile Elastic Modulus of Steel Fiber – Ce...
PDF
Effect of Liquid Viscosity on Sloshing in A Rectangular Tank
PDF
Design and Implementation Decision Support System using MADM Methode for Bank...
PDF
Investigations on The Effects of Different Heat Transfer Coefficients in The ...
PDF
Strategy of Adaptation of Traditional House Architecture Bali Aga
PDF
Design of Universal Measuring Equipment for Bogie Frame
PDF
A Design Of Omni-Directional Mobile Robot Based On Mecanum Wheels
PDF
An Investigation Into The Prevalence of Code Switching in the Teaching of Nat...
PDF
The Filling Up of Yogyakarta Governor Position in Social Harmony Perspective
PDF
Quality Function Deployment And Proactive Quality Techniques Applied to Unive...
PDF
The Analysis And Perspective on Development of Chinese Automotive Heavy-Duty ...
PDF
Research on the Bottom Software of Electronic Control System in Automobile El...
PDF
Risk Based Underwater Inspection (RBUI) For Existing Fixed Platforms In Indon...
PDF
Dynamic Modeling of Four – Rotorcraft
PDF
A New Approach on Proportional Fuzzy Likelihood Ratio orderings of Triangular...
Injection Analysis of Hera And Betano New Power Plants At the Interconnection...
Harmonic AnalysisofDistribution System Due to Embedded Generation Injection
Decision Support System Implementation for Candidate Selection of the Head of...
Yield Forecasting to Sustain the Agricultural Transportation UnderStochastic ...
Injection Analysis of 5 Mwp Photovoltaic Power Plant on 20 Kv Distribution Ne...
Developing A Prediction Model for Tensile Elastic Modulus of Steel Fiber – Ce...
Effect of Liquid Viscosity on Sloshing in A Rectangular Tank
Design and Implementation Decision Support System using MADM Methode for Bank...
Investigations on The Effects of Different Heat Transfer Coefficients in The ...
Strategy of Adaptation of Traditional House Architecture Bali Aga
Design of Universal Measuring Equipment for Bogie Frame
A Design Of Omni-Directional Mobile Robot Based On Mecanum Wheels
An Investigation Into The Prevalence of Code Switching in the Teaching of Nat...
The Filling Up of Yogyakarta Governor Position in Social Harmony Perspective
Quality Function Deployment And Proactive Quality Techniques Applied to Unive...
The Analysis And Perspective on Development of Chinese Automotive Heavy-Duty ...
Research on the Bottom Software of Electronic Control System in Automobile El...
Risk Based Underwater Inspection (RBUI) For Existing Fixed Platforms In Indon...
Dynamic Modeling of Four – Rotorcraft
A New Approach on Proportional Fuzzy Likelihood Ratio orderings of Triangular...

Recently uploaded (20)

PDF
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PPTX
web development for engineering and engineering
PDF
Well-logging-methods_new................
PPTX
Welding lecture in detail for understanding
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PPTX
Sustainable Sites - Green Building Construction
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPTX
UNIT 4 Total Quality Management .pptx
PPTX
Internet of Things (IOT) - A guide to understanding
PDF
Digital Logic Computer Design lecture notes
PPTX
OOP with Java - Java Introduction (Basics)
PDF
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
DOCX
573137875-Attendance-Management-System-original
PPTX
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
July 2025 - Top 10 Read Articles in International Journal of Software Enginee...
UNIT-1 - COAL BASED THERMAL POWER PLANTS
web development for engineering and engineering
Well-logging-methods_new................
Welding lecture in detail for understanding
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
Sustainable Sites - Green Building Construction
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
UNIT 4 Total Quality Management .pptx
Internet of Things (IOT) - A guide to understanding
Digital Logic Computer Design lecture notes
OOP with Java - Java Introduction (Basics)
Mohammad Mahdi Farshadian CV - Prospective PhD Student 2026
573137875-Attendance-Management-System-original
Recipes for Real Time Voice AI WebRTC, SLMs and Open Source Software.pptx
Operating System & Kernel Study Guide-1 - converted.pdf
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd

Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid

  • 1. International Journal of Research in Engineering and Science (IJRES) ISSN (Online): 2320-9364, ISSN (Print): 2320-9356 www.ijres.org Volume 5 Issue 1 ǁ January. 2017 ǁ PP.22-26 www.ijres.org 22 | Page Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid Wasum1 , SholehHadi Pramono2 , Rahmadwati3 Department of Electrical Engineering, University ofBrawijaya, Indonesia Abstract: Smart grid is one of the solutions in terms of distribution of electricity to make it more effective and reliable. One of the main functions of the smart grid is to provide an important role in maintaining the reliability of electricity supply. Some sections in the smart grid include existing equipment at the site and the central computer. In order to convey the data from the site plant to the central computer, it needs a smart grid instrument controllers like SCADA. SCADA has a role to monitor, control, and communicate in two-ways between equipment on the site plant and the central computer. In SCADA systems, we often experience difficulty in obtaining data such as uncertainty of data and non-precision data. Then a method to overcome it is needed. In this study, Fuzzy Logic is used to detect network conditions toward the aspects of loading and the interference of overcurrent. Using four input variables with three and four linguistic value and four output variable with two linguistic value has resulted in eighty one rule base. Identification of faults was conducted by how big the DC voltage and the current. Once validated by SCADA systems and the use of Fuzzy Logic, we obtained 97.53% of the perfection of the system. Keywords: Fault, Fuzzy Logic, SCADA, Smart grid I. INTRODUCTION The needs of electricity in Indonesia has increased every year. It was proved by the increase in the average growth of 8.6% from 216.8 TWh (Tera Watt Hour) to 457.0 TWh throughout 2016 and 2025. To meet it, the Indonesian government has tried to build and renew generation facilities, rearrange the transmission network, and rearrange the distribution network. The obstacle of the government's efforts includes limited electricity supply due to differences in geographic location so that the electricity weren’t fulfilled. The power supply in Indonesia is currently using interconnection system that is used by all major islands, while small islands are still using the isolated system and has reached the electrification ratio up to 88.3% [1]. In recent years, Indonesia is building an interconnection system. It is proven by the efforts of the government to operate a new power plant, add plant reliability, improve the reliability of the transmission system, strengthen the transformer in the substation, increase the recovery of electricity supply during faults and open up the possibility of a hybrid solar power and hybrid thermal power station. The Government's efforts are aimed to anticipate growth in customer demand, maintain continuity of power supply and maintain, steady voltage in accordance with the needs and automation of network operation of electricity[2]. Based on the above elaboration, in 2011 Gao and Redfern tried to provide solution by creating a more effective and reliable electrical distribution. In that study, smart grid system was used. This system had used smart devices, modern communication systems and reliable management system[3]. Other advantages of this system were to have a large capacity in monitoring data generated by an integrated, data analysis for supporting decision, increased security, effectiveness in communication, to meet customer demand and reduce energy consumption and costs. Based on the research conducted by Gao and Redfern, Borlase (2013) tried to provide a solution by creating a control instrument in the smart grid. The instrument was a Supervisory Control and Data Acquisition (SCADA) [4]. This system referred to a system or combination of systems that and collect data from various sensors which were located in the site plant. Then they sent the data to a central computer which was then used to view, manage and control devices in the site plant. Broadly speaking, SCADA installed in the central computer with SCADA software in it, the appearance of the Graphical User Interface (GUI), front-end data acquisition equipment, presenting data and information in real-time, intelligent alarm processing, can use thin clients and web-based clients, using one or more Remote Terminal Unit (RTU) and using a communication system. Utilization of SCADA systems in the power network aims to obtain data in real-time on the site plant as it is in the power plants, substations transmission and distribution, feeder distribution, and other devices, giving orders to the equipment located at the site of the plant with response time ranges between 1-5 seconds. When we pay attention on its components, SCADA consists of two components, field devices such as RTU, and central computer. RTU is a microprocessor device which transfers the telemetry data to the central computer. RTU is located in the plant site. The main functions of RTU are interfacing input/output, collecting data, presenting data to a central computer, and manipulating the data before it is sent to the central computer.
  • 2. Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid www.ijres.org 23 | Page Meanwhile, the central computer is a computer system that is responsive to the circumstances which occur in the RTU. In large SCADA system, central computer serves to reduce double data, distribute software, and record events which occur on each device. According to the research conducted by Gouzhen et al in 2009, SCADA systems were used for monitoring, controlling, and two-way communication between the central computer and the photovoltaic power plant. There were two basic studies in this research. They were a match between the conditions at the plant site in the central computer and a server configuration SCADA[5]. Every complex system definitely will have some risks. Some risks that occur in the SCADA are the breakdown of communication between the central computer and the device at the site plant, the unstable data transmission, and the damage to system which causes faults[6]. SCADA systems often have difficulty in obtaining data from the RTU. Some of the difficulties are the amount of noise, the uncertainty of data, and the ambiguous data obtained in the SCADA system. To overcome this, Kumar et al are using Fuzzy Logic. Because Fuzzy Logic is able to cope with the uncertainty and non- precision data received from the RTU to the central computer. In this methods there is membership function and rule base that can be adapted to the needs [7]-[8]. Based on the explanation above, this research focuses on the use of Fuzzy Logic in SCADA which is used to detect faults that occur on the network due to fault of overcurrent and load. II. MATERIALS In the SCADA system, the quality of the measurement depends on the transducer and converter, telemetered to control systems via communication links. One of the components in SCADA located at the site of plant is RTU in which there are inputs and outputs such as analogue-to-digital converters, digital-to-analogue converters, analog inputs, digital inputs and digital outputs and communication ports in it. The data used in this research is data types such as voltages and currents generated by the devices on site plant and the voltage and current received by the central computer, fault, response time which occurs during and after faults as well as length of transmission media used. III. METHOD 3.1. Measurement For measurement, the data was obtained from the following ways: First, by using the data changes to large voltages and currents generated by the devices on site plant so that voltage and current received central computer will adjust magnitude. Second, by using multiple nodes as a source of voltage and current and form a network, then between the node, a fault was created. It will affect the delivery of data and information to the central computer. Third, doing the analysis using fuzzy logic by doing data collection first and then process them to obtain the rule for any condition of input results. Then the data will be saved and will be used by Fuzzy Logic in determining the output to obtain optimum use of resources and load usage. 3.2. System Scheme In this study, a scheme of the system as shown in Figure 1 is used. PC Gateway Hub/SwitchEth Analog Input Eth Digital Input / Digital Output Eth Central Computer Site PV #1 1 2 2 PV #2 PV #n 1 2 1 1 2 Status Metering Figure 1. System Scheme Based on Figure 1, it was concluded that: First, PC Gateway is a unit which displays and stores data generated by the site plant section. Second, PC Gateway will provide data and information in the SCADA system. Third, status and control of existing equipment at the site plant will be read by a sensor device that has a digital input and digital output. Fourth, the measurement will be addressed by tools which have inputs analog sensor. Fifth, the source voltage and current are generated by photovoltaic (VP). 3.3. Fuzzy Logic In this study, the method of Fuzzy Logic used can be seen in Figure 2.
  • 3. Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid www.ijres.org 24 | Page Input Rule Base Output Figure 2.Structure of Fuzzy Logic In fuzification in taking input and has been predetermined the degree of membership. In this study, four input variables, namely volt1, volt2, volt3 and volt4 are taken. It generates four output variables which are relay1, relay2, relay3 and relay4. The value of all the linguistic input variables is divided into three: low, normal and high, while the linguistic value of the output is divided into two: open and close. Each input variables have low membership function with a voltage range between 0V up to 2V, normal to the voltage range between 2V up to 9V and high voltage range between 9V up to 10V. Meanwhile, the output variable has an open membership functions which have a normal stress, and has covered the low and high voltage. From the results of fuzification input, eighty one rule base was obtained. This rule base was implemented on Analog Input tool and displayed in the form of SCADA systems on the PC Gateway. Here are two of the eighty one rule base obtained: First, when volt1 is low, and volt2 is low, and volt3 is low and volt4 is low, then relay1 is opened, and relay2 is opened, and relay3 is opened, and relay4 is opened. Secondly, when volt1 is normal, and volt2 is normal, and volt3 is high, and volt4 is high, then relay1 is opened, and relay2 is opened, and relay3 is closed, and relay4 is closed. 3.4. SCADA System In this study, SCADA systems are used to display data and information such as status, control and measurement of the devices that exist in the plant site and then the data will be sent to the PC Gateway. Then the data will be stored in the existing database on a PC Gateway that will serve as a log. Globally, the display of SCADA can be seen in Figure 3. Menu #1 Menu #2 Menu #nTitle Clock Date Alarm Chart of Measurement (Real Time) Measurement PV #1 PV #2 PV #n Control Relay Status of Measurement Figure 3. SCADA Layout In this study, the SCADA system layout is divided into three sections: Header, Body and Footer. The Header section is used for the placement of titles, multiple menus which are used, the time and date information. Meanwhile, the Body section is used to display features such as charts and bar voltage measurements in real- time generated by PV. In the control relay, it is used to control relays manually or automatically and on the status of measurement, it is used as a condition of the relay and PV connected/on or disconnected/off on SCADA systems. Finally, on the Footer it is used to display event and alarm which occur in real-time. IV. EXPERIMENT AND RESULTS 4.1. Measurement In this study, four measurements of solar panel modules are used. This solar panel module serves to transform solar energy into DC power. These solar panels have each specification Maximum Power (Pmax) of 100W. Figure 4 is voltage measurements which have ever been done. The voltage values measured is up to 10V, and the smallest time used is milliseconds (ms).
  • 4. Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid www.ijres.org 25 | Page Figure 4. Voltage measurements In this measurement, it has also been implemented with fuzzy logic membership functions numbers 1-2 which mean low, the rate of ≥ 2 - ≤ 18 which meansnormal and the number >18 which meanshigh. In the measurement of value of <2 and >18, the graph shown is red. Still in the graph, the triangle mark above illustrates the highest voltage and the triangle below illustrates the lowest voltage during the measurement taken. 4.2. SCADA System Tests conducted on the SCADA system aims to determine whether the design results system has functioned properly and in accordance with the recommended specifications. Tests performed include First, making sure all devices on the central computer and the site plant have been connected in accordance with the procedure. Second, making sure that application of SCADA system can be operated in line with expectations. Third, testing the SCADA system which serves to communicate between devices on the site plant, central computer and user. The display of this test is shown in Figure 5. Figure 5. Display SCADA System Testing Figure 5 has included some details of which are measurements that have been done in real-time which amounted PV1 and PV2 of 8,33V and 8,21V, relay status is shown in DI1 to DI4 is ON. 4.3. Scenario of Fault Scenario of fault in this study is used to test and measure the robustness of the system that has been created. Several scenarios of faults that have been made can be seen in Figure 6 and Table 1. PC Gateway Hub/Switch1 Analog Input Digital Input / Digital Output 2 4 PV #2 PV #n 3 5 PV #1 Figure 6. Scenario of fault Table 1. Scenario of fault
  • 5. Fuzzy Logic Method in SCADA to Optimize Network Electric Power Smart Grid www.ijres.org 26 | Page No Description Cable Length Response Time 1 UTP cable is disconnected between the Gateway PC and Hub / Switch 1m 0,1ms 2 UTP cable is disconnected between Hub/Switch with Analog Input module and Digital Input module. 2m 0,2ms 3 Negative cable is disconnected between Analog Input module and PV #1 5m 0,5ms 4 Cable is disconnected between Digital Input module and the PV #2 5m 0,4ms 5 UTP cable is disconnected between the PC Gateway and Analog Input module which is connected directly 3m 0,2ms V. CONCLUSION The use of Fuzzy Logic was conducted to determine the membership functions of the four input and four output voltage magnitude condition of the relay. Membership function has obtained eighty-one rule base. The calculation of Fuzzy Logic has been implemented in Analog Input module and into the SCADA system. Once validated between SCADA systems and the use of Fuzzy Logic, then we obtained 97.53% of the perfection of the system or two of the 81 rule base to be evaluated. ACKNOWLEDGEMENTS We would like to express many thanks to the Electrical Engineering University of Brawijaya which has supported our research. REFERENCES [1]. Perusahaan Listrik Negara, Rencana Usaha PenyediaanTenagaListrik (RUPTL) PT. PLN (Persero) Tahun 2016-2025, (Jakarta : Perusahaan Listrik Negara, 2016). [2]. Perusahaan Listrik Negara, Statistik PLN 2014, (Jakarta : Perusahaan Listrik Negara, 2015). [3]. Gao, C, and Redfern, M.A., A Review of Voltage Control in Smart Grid and Smart Metering Technologies on Distribution Networks. 46th International Universities Power Engineering Conference. Germany. 2011. [4]. Borlase S., Smart Grid: Infrastructure, Technology, and Solutions, (Boca Raton: CRC Press, 2013). [5]. Guozhen H, Tao C, Changsong C, and Shanxu D. Solution for SCADA System Configuration Reliability in Photovoltaic Power Plant, IEEE, IPEMC, 2009, 2482-2485. [6]. Hamoud G, Chen RL, and Bradley I, Risk Assessment of Power System SCADA, 2003, 758-764. [7]. Kumar P, Jamil M, Thomas MS, and Moinuddin, Fuzzy Approach to Fault Classification for Transmission Line Protection. IEEE. TENCON, 1999, 1046-1050. [8]. Naba A., BelajarCepat Fuzzy Logic Menggunakan MATLAB, (Yogyakarta :Andi Publisher, 2008).