Predictive Maintenance of MV Switchgear with
Partial Discharge
R K Gupta
Principal Consulting Electrical Engineer (Power System)
Reliability Engineer
BE Electrical
Protection, Automation, PLC & SCADA, Level 3 MCSA, Colorado USA
IEC 60270 Section 3.1 Notes
“Partial discharges are in general a consequence of local electrical stress
concentrations in the insulation or on the surface of the insulation…”
..“Corona is a form of partial discharge that occurs in gaseous media around
conductors which are remote from solid or liquid insulation…”
..“Partial discharges are often accompanied by emission of sound, light, heat,
and chemical reactions…”
“Localized electrical discharge that only partially bridges the insulation
between conductors and which can or cannot occur adjacent to a conductor.”
Partial Discharge Test
IEEE Standard 400-2001 Notes
“Partial discharge measurement is an important method of assessing the
quality of the insulation of power cable system”
“A partial discharge is an electrical discharge (formation of a streamer or
arc) that does not bridge the entire space between two electrodes.”
“Partial discharges may occur in a “void…at a contaminant…or at the tip of
a well-developed water tree...”
Partial Discharge Test
Partial discharge Taxonomy
Three basic types of PD sources:
 Internal PD
 Surface PD
 Corona PD
Focus on
Internal Discharges
PD Inception Condition
 A free electron is available in the gas inside the void.
 Mechanisms that allow a free electron inside the gas:
a. Ionization by photon/gas molecule collision (background radiation)
b. Schottky emission of electrons from metal and /or dielectric surfaces
(electron injection).
 The external field, fE0, exceeds the inception field, Einc.
The free electron, accelerated by electric field, can trigger an electron
avalanche (PD).
Partial Discharge Process in Solid
Insulator /Air Insulator
 Solid insulators are manufactured to give an even distribution of electrical
stress between the conducting electrodes.
 Manufacturing processes invariably give rise to small cavities or voids in the
insulation bulk. These cavities are usually filled with a gas of lower breakdown
strength than the surrounding solid.
The permittivity of the gas is invariably lower than that of the solid insulation,
causing the field intensity in the cavity to be higher than that in the dielectric.
Therefore under the normal working stress of the insulation, the voltage across
the cavity may exceed the breakdown value and initiate electrical breakdown in
the void.
Equivalent circuit for cavity in insulator
A solid insulator of thickness d contains a
disc shaped cavity of thickness t and area
A, as shown fig. In the equivalent circuit
the capacitance Cc corresponds to the
cavity, Cb corresponds to the capacity of
the dielectric that is in series with Cc and
Ca is the capacitance of the rest of the
dielectric. Given that capacitance C, in
Farads/m2, is given by;
Where;
e0 = permittivity of free space = 8.854 x 10-12 Fm-
1
er = relative permittivity
A = area between electrodes
d = separation of electrodes
Breakdown Strength in Cavity
If we assume that the gas in the cavity (of thickness t) in figure 1 has a relative
permittivity of approximately 1, then:
And,
As Cb and Cc essentially form a capacitive divider, the voltage across the cavity,
Vc, can be expressed as;
Substituting into the above equation gives;
Breakdown Strength in Cavity
Electrical field strength across the cavity (Ec) is given by the equation
Given that in most circumstances t << d and er is greater than 1, it can be seen
that electrical stress in the cavity is greater than that in the surrounding
insulation. This, coupled with the fact that the breakdown strength of the gas is
likely to be significantly lower than that of the insulation, makes the gas in the
void liable to breakdown under normal working conditions.
Breakdown Strength in Cavity
From the equations above it can be seen that the voltage across the dielectric
at which discharge activity will initiate in the cavity, Vai, is given by;
In practice voids in solid insulators are very often approximately spherical.
In this case the field in the void is given by;
Where erc = relative permittivity of gas
in void.
When er >> erc this approximates to:
Relative permittivity and breakdown strengths of some typical high voltage
HV Insulating Material
Voltage and Current in discharging
Cavity
Each time a discharge occurs in the cavity,
charge is transferred from one side of the
cavity to the other until the potential
difference across the cavity is too small to
maintain the discharge. When the insulator
is subject to a sinusoidal alternating voltage,
charge builds up within the void as the
applied voltage increases or decreases. This
causes a series of discharges with charge
first moving in one direction, then the other.
Figure 2 shows how the voltage and current
across a cavity changes with applied voltage.
The dotted curve shows the voltage that would occur across the cavity if the
discharges did not equalize the potential difference across the cavity. As the
voltage Vc reaches the value V+, a discharge takes place and the, the voltage Vc
collapses and the discharge extinguishes. The voltage across the cavity then starts
again increasing until it reaches V+ , when a new discharge occurs. In this way
several discharges may take place during the rising part of the applied voltage.
Similarly, on decreasing the applied voltage the cavity discharges as the voltage
across it reaches V-, In this way groups of discharges are generated by a single
cavity and give rise to positive and negative current pulses on raising and
decreasing the applied voltage respectively.
Voltage and Current in discharging
Cavity
DEGRADING EFFECT IN SOLID
INSULATION
When the gas in a cavity breaks down, the opposite surfaces of the insulation
momentarily become cathode and anode. Some of the electrons hitting the
anode are sufficiently energetic to break the chemical bonds of the insulation
surface. Similarly, bombardment of the cathode by positive ions may cause
damage by increasing the surface temperature and produce local thermal
instability. These degrading effects form small channels and pits in the surface
that can elongate through the insulation. In addition to the ionic
bombardment, chemical degradation may result from active discharge
products, like O3 or NO2, formed in the air by the discharges. The net effect is
slow erosion of the insulating material and a very gradual increase in the size
of the cavity
Electrical Trees
 Electrical trees are comprised of a series of interconnecting channels or discharge
paths with diameters ranging from less than a micron to tens of microns.
 Discharge activity in voids will eventually become centered at particular sites
producing deep cavities in the surface. The cavities grow in length along the discharge
axis and the energy of discharge impinging on their tips increases. This combined with
electrical stress concentration by virtue of their point like form, produces increasingly
intense electrical fields at the tips of the discharging cavities.
 Eventually the breakdown strength of the material in the immediate vicinity of the
tip is exceeded. Breakdown follows with the evaporation, in the space of a few
nanoseconds, of a small volume of material.
 This rapid conversion launches small shock waves into the insulation. These waves
create, in time, a structure of fine cracks extending into the insulation. Their name
comes from the dendritic patterns they from in the insulation.
Electrical trees emanate from points of stress enhancement
in insulation. This can be a metal inclusion or a protrusion on
a conductor but in practice they more usually originate from
a void. The exact process by which electrical trees propagate
is still not fully understood, however, it is generally accepted
as being a combination of mechanical and thermal effects.
There are two clear stages in the development of electrical
trees under the application of an alternating voltage, the
inception period, which may be considerable and a much
shorter formative period. Eventually the tree will bridge the
insulation. Discharges continue to occur without breakdown
because space charge sets up a reverse field in the channels
to counter the field between the electrodes. During this
period the channels slowly widen. Eventually the field can no
longer be maintained in the widened channels and
catastrophic breakdown occurs, creating a very large channel
though the insulation.
Electrical Trees
Tracking
 Tracking is the formation of a permanent conducting path across an insulator surface.
Usually the conduction path results from degradation of the insulation. For tracking to occur
the insulation must be a carbon based compound.
 Most high voltage plant is situated outside. In industrial areas, insulators become
contaminated with pollution and dirt from the atmosphere. Where substations are situated
near the sea, salt very quickly covers the plant. In the presence of moisture, these
contaminating layers gives rise to leakage current over the insulator surface. This heats the
surface and through evaporation causes interruption in the moisture film. Large potential
differences are generated over the gaps in the moisture film and small sparks can bridge the
gaps. Heat from the sparks causes carbonization of the insulation and leads to the formation
of permanent carbon tracks on the surface.
Tracking as a phenomenon severely limits the use of organic insulators in outdoor
environments. The rate of tracking depends on the structure of the polymers and can be
significantly reduced by adding appropriate fillers to the polymer which inhibit carbonization.
CORONA
Corona is a partial discharge in regards that gas
breakdown begins at a position of high electric
field but dies out as the electric field decreases
very rapidly as a function of distance from the
highly stressed position. The breakdown can die
out for two reasons;
The region of high field is too small to generate
a fully formed breakdown channel.
The field falls to such a low value, that even a
fully formed breakdown channel cannot
propagate.
Corona forms in partially ionised regions adjacent to conductors and causes a change in the electric field between the
conductor and the ground. In effect, it can be seen as an extension of the conductor. As such, it will effectively reduce
the capacitance between the conductor and ground, as their separation decreases. This causes a drop in the voltage
on the conductor, a potential difference between the conductor and the voltage source and, therefore, a current flow
from the voltage source to the conductor. The electric field in a corona is sufficiently high that when a free electron
occurs, that electron will, on average, generate more than one additional electron (and positive ion). So a corona is
full of positive and negative ions (electrons).
Thus when the field reduces to the extent that the original current ceases to flow, the electric field does not
immediately return to its previously high value. Before that can happen, the positive and negative ions must flow in
the field toward the negative and positive electrodes respectively. As the negative charges are in the form of
electrons, they can propagate sufficiently fast to contribute to the measured partial discharge signal. However
massive positive ions flow so slowly that they typically generate a very small current over a long period of time.
Thus a corona can be thought of as generating a PD signal though three mechanisms. First, the ionisation of a
channel, which tends to look like an extension of the conductor and therefore increases the capacitance of the
conductor to ground. Second rapid migration of electrons toward the positive electrode in a system where negative
charge flows as electrons. And thirdly, flow of positive ions which tends to be too slow to be detected by most PD
measuring systems. The time scale for the first two phenomena is nanoseconds to microseconds, while that for the
third phenomena can be milliseconds or more.
CORONA
Corona tends to be repetitive, as once the region is cleared of charge, it returns to the
conditions which generated it in the first place. Corona in air is sensitive to air velocity and
environmental conditions which affect space charge near the conductor.
In many gases, including air, corona generated by positive and negative voltages differ
substantially. This is due to the physical difference between negative charge carriers
(electrons) and positive charge carriers (positive ions). Electrons being light and mobile
gain kinetic energy very rapidly from an electric field, while positive ions are heavy and
much less mobile. The outside surface of molecules is made up of electrons, so violent
phenomena, which dislodge charge from a molecule, free an electron and simultaneously
create a heavy positive ion. In corona from a negative conductor, electrons propagate
away from the conductor in the direction of corona growth. Thus they can create further
electrons through molecular collisions. In corona from a positive conductor, the electrons
propagate towards the conductor and away from the direction of corona growth. In this
case, electrons are generally detached ahead of the corona tip by photons generated
within the corona.
CORONA
Water Trees
A water tree is a bush or fan like structure developing like an electrical tree, from points of
stress enhancement. Water trees cause a reduction in the insulation's breakdown stress level
which encourages breakdown. Electrical trees can, on occasion, be initiated from a water tree
speeding the breakdown process.
Water trees are more diffuse than electrical trees and
generally grow at lower electrical stresses. Two types of
water tree have been recognized according to where the
tree initiates, ‘bow-tie’ trees and ‘vented’ trees.
Bow-tie trees are initiated in the bulk of the insulating
material, often from a void, and grow towards the
conducting screens. They clearly derive their name from
the pattern they form. Vented trees grow from one of
the conducting screens into the insulation bulk
PD Testing Methods
 Online Partial Discharge Testing
Ultrasonic
Transient Earth Voltage
High Frequency Current Transformer
Electrical Method (Inductive & Capacitive)
 Offline Partial Discharge Testing
Capacitance Voltage Divider( CVD) method
Ultrasonic
Electrical arcs in the air and corona effects emit sounds and ultrasounds. The basic
electrical problems that produce distinct ultrasound waves that can be detected
by Ultrasonic Testing include partial discharge, corona and tracking. Ultrasonic
measurement is most powerful on a comparative basis and will significantly
increase the reliability of correct detection of partial discharge.
Ranges of Ultrasonic detection
Center frequency 40 KHz
Bandwidth 38kHz-48kHz
Acoustic Airborne
Airborne acoustic (ultrasonic) radiation through air from corona and surface
discharges in the plant
Ultrasonic / Acoustic Airborne
Test Method
Background Noise Measurement
If any reading is made with the sensor flat on a surface (not over a vent or
air gap) this can be discounted as background noise.
AA/Ultrasonic Sensor Attachment Requirements
 There must be a clear air path (line of sight) from the sensor to the
discharge source, i.e. a vent or hole in the plant housing.
 Fully enclosed air insulated switchgear with no grills, vents, air gaps etc,
will not be suitable for Airborne Acoustic measurements.
Transient Earth Voltage
Transient Earth Voltage (TEV) PD signals
are generated by internal partial discharges
in switchgear, cable terminations, motors
and transformers. TEV signals are in a
higher frequency range of between 4MHz –
100MHz and are oscillatory in general. The
resultant PD signals are measured in dB
(decibels), as is the convention for on-line
s w i t c h g e a r t e s t i n g .
Background Noise Measurement
TEV measurements can be affected by background electrical noise in the
substation. Sources include:
Power electronic switching, e.g. from DC power supplies.
Corona from outdoor switchyards.
High frequency communication systems, e.g. two-way radios
TEV Test Method
The TEV sensor should be placed flat
against the metal-clad switchgear close to
vents or gaskets or seams on the metal-
clad housing. The LEDs will light to show
the measured PD level. The user MUST
hold the unit whilst in use.
It is recommended to place the TEV
sensor at multiple points on the plant for
example on the cable boxes and front and
back of each switchgear panel.
TEV Test Method
High Frequency Current Transformer
(HFCT) sensor which is clipped around
the earth strap of the cable. These
pulses are generally in the frequency
range of between 200kHz – 4MHz and
are typically mono polar in shape. The
unit measures the Cable PD pulses in
pico Coulombs (pC’s) by measuring the
charge content (area under the mono
polar pulse).
High Frequency Current Transformer
Procedure for HFCT PD Measurement
Background Noise Measurement
HFCT measurements can be affected by background electrical noise sources
inside and outside the substation. Sources include:
Radio frequency interference from local radio transmission
Corona from outdoor switchyards.
To measure the background noise level, attach the HFCT to the earthing
conduit of a de-energized feeder, or a nearby LV earth.
Electrical Method
Capacitive Sensor
The Capacitive Sensor measures the electric field on the cable and cable joint.
Sensors are designed to detects the quick variations of electrical fields caused by
PD. The probe is a coated metal plate that create a capacitor between the cable
and the plate. This capacitive coupler allows to read the PD activity on surface.
The PD signal is detected by a capacitive probe, then amplified by the
equipment in radio frequency bandwidth. The signal amplitude is proportional
to the discharge energy.
ULD 40 ( Ultrasonic Detector)
The ULD-40 is an ultrasonic detector designed for corona and arcing
inspections for predictive maintenance in electric utilities.
Main Applications
 Electrical Inspections: corona effect localization, arcs on
shields.
 General Mechanical Inspections: motors, compressors, gears,
bearing monitoring.
Gas, air, pressure leaks, leak detection without pressure or
vacuum.
Aerospace Sector: airplane doors and windows, air tightness
Detection of Electrical Arcs and Corona
Effects
Electrical arcs in the air and corona
effects emit sounds and ultrasounds. The
role of the ULD-40 consists of capturing
emitted ultrasounds and of translating
them into the audible range. The ULD-40
accurately pinpoints and identifies
corona effects and arcs that may be
encountered on any type of high voltage
installation simply by scanning around
the suspected area.
 Portable expert system for detection of partial discharges
 Increase your network reliability and workers security
XDP
 It is an instrument that enables to quantify the intensity of the high
frequency electric field signal emitted by the partial discharge of a
component, and to translate it into decibels (dB)
 A decibel (dB) is a unit that expresses the intensity of a signal in
relations to a reference on the logarithmic scale
XDP
With the XDP
 Follow up on ageing process of the critical components’ insulation
 Perform Quality Control of the insulators during installation or repair
 Safety control prior to work on energize equipment
XDP Advantages
 Portable
 Verification done under normal charge of the electric network – No
service interruption
 Quick readings
 Very sensible
 Pinpoints the problem
 Our 3rd generation of PD Detector
XDP Technical Specifications
 Peak measurement value in dB relative to 15 picoCoulomb
 Peak detection with a fast numeric circuit
 Fast numeric processor (DSP) for instant analysis results
 Wave’s shape inspection in high frequency to determine PD proximity
XDP Technical Specifications…
 LCD (Liquid Crystal Display) displays wave form
and dB reading
 Easy to read, big letter casings
 Upload/download capability
 PC (Windows) interface for PD readings
analysis/trending
XDP Technical Specifications…
 Dynamic range of 40 dB
 Up to 64 readings recording capability
 Bandwidth of 300 kHz to 70 MHz
 Sampling frequency of 30 MHz
 Sampling period of 16 cycles (50 or 60 HZ)
 Built-in Real Time Clock
XDP Technical Specifications…
 Keeps in memory up to 10 PD signatures for quick PD recognition
 Quick auto-verification procedure for high reliability
 8 hour battery autonomy
 The smaller PD Expert System on the market
 203 X 114 X 51 mm (8 X 4.5 X 2 in.)
 0,86 kg (1,9 lbs)
XDP Applications
 Cable & accessories
 Joint
 Elbow
 T
 Custom
 Switchgears
 Distribution Transformers
 Etc.
The Handling Rod
The use of the Spatula, which is a surface sensor, with the 61 cm (24 in.)
handling rod does not required direct access to the conductor
The Capacitive Sensor
 The Capacitive Sensor measures the electric field on the cable and
cable joint Our Capacitive Sensor uses a flexible Spatula easily
adaptable to the cable joint form
How it works
 The XDP detects the quick variations of electrical fields caused by PD
 The probe is a coated metal plate that create a capacitor between the
cable and the plate
 This capacitive coupler allows to read the PD activity on surface
 It is moved along joints and on cable insulation jacket, in order to
detect the presence of PD activity
 The PD signal is detected by a capacitive probe, then amplified by the XDP
in radio frequency bandwidth
 The signal amplitude is proportional to the discharge energy
 The energy is displayed on the XDP in dB (relative value)
How to use the Spatula Sensor
 Check the reference value on a regular basis to make sure that the XDP
works well
 Turn off the XDP
 Connect the reference module
 Connect the Spatula Sensor
 Place the sensor on the module in a way to make it cling around it
as much as possible
Check the reference value…
 Activate the XDP
 On the numeric display, you must read the displayed value on the sensor’s
case
 This technique will allow you to detect a PD activity even in an
environment with normal to high ambient noise (12 – 20 dB)
 Always adjust the spatula the way it fit as much as possible around the
cable and cable joint
 Always use the handling rod
Inductive Probe
 Applications
 Terminations
 Shielded cables
 Cable joints with grounding braid
A B
C
D
Quality control of a 12 dB ambient noise
splice
 Without defect
 A = 10dB
 B = 12dB
 C = 12dB
 D = 10dB
 With defect
 A = 12dB
 B = 14dB
 C = 34dB
 D = 16dB
PD activities level classification
 Level 1: Free of Partial Discharge activity. No necessary action at this time.
Retest within 12 to 18 months (< 12dB)
 Level 2: Moderate levels of Partial Discharge activity. Retest within 1 year
(12 – 20dB)
 Level 3: High level of Partial Discharge activity. Repair or replacement
required (20 – 35dB)
PD activities level classification…
 Level 4: Very high level of Partial Discharge activity (> 35dB)
 We strongly recommend to restrict the access to the area
 Repair or replacement required as soon as possible
Thank you

More Related Content

PDF
Cable fault location methods (Megger)
PPT
Seminar on Partial Discharge detection methods
PPTX
Current Transformer.pptx
PPTX
Power Transformer Protection
PDF
Sf6 circuit breakers
PDF
Testing of Transformers.
PDF
Sample calculation-for-differential-relays
PPT
Power System Protection course - Part I
Cable fault location methods (Megger)
Seminar on Partial Discharge detection methods
Current Transformer.pptx
Power Transformer Protection
Sf6 circuit breakers
Testing of Transformers.
Sample calculation-for-differential-relays
Power System Protection course - Part I

What's hot (20)

ODP
Transformers protection, an introduction
PPTX
Tap changer
PDF
RTCC & AVR
PDF
Switchgear presentation
PPTX
switchgear and protection by vala kamlesh
PDF
Transformer & OLTC
PDF
Practical handbook-for-relay-protection-engineers
PDF
Generator protection calculations settings
PPT
Transformer design and protection
PPTX
Protection & switchgear
PPTX
BREAKDOWN OF SOLID DIELECTRICS|BREAKDOWN IN SOLIDS|HIGH VOLTAGE ENGINEERINGo...
PPTX
Ppt on protection of power transformers
PDF
Power transformer protection
PPTX
Switchgear presentation
PPTX
220 KV Substation Operation & Maintenance
PDF
Transformer overcurrent
PDF
Blackout Avoidance & Undervoltage Load Shedding
PPTX
Partial discharge testing
PPTX
Substation grounding
PDF
Chapter 09 - Measurement of Partial Discharge
Transformers protection, an introduction
Tap changer
RTCC & AVR
Switchgear presentation
switchgear and protection by vala kamlesh
Transformer & OLTC
Practical handbook-for-relay-protection-engineers
Generator protection calculations settings
Transformer design and protection
Protection & switchgear
BREAKDOWN OF SOLID DIELECTRICS|BREAKDOWN IN SOLIDS|HIGH VOLTAGE ENGINEERINGo...
Ppt on protection of power transformers
Power transformer protection
Switchgear presentation
220 KV Substation Operation & Maintenance
Transformer overcurrent
Blackout Avoidance & Undervoltage Load Shedding
Partial discharge testing
Substation grounding
Chapter 09 - Measurement of Partial Discharge
Ad

Similar to Partial Discharge Test - Switchgear (20)

PPTX
Breakdown due to Internal Discharges and Surface Breakdown
PPTX
Mechanism for breakdown for
PPTX
PPTX
Solid breakdown (2) (1)
PDF
03 partial discharge theory cutler-hammer
PDF
PD_Presentation_1.pdf
PPSX
Lecture 1 - Basics of High Voltage Engineering .ppsx
PDF
High_Voltage_Engineering_2E.pdf
PPTX
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
PPT
UNIT I - HVE.ppt
PPTX
Highvolatage enegineering updated.pptx
PPTX
transformer dignostics on high voltage
PDF
Insulation and Dielectric Breakdown Design Paper SM54
PPT
High voltage switchgear charged detection
PPTX
Week-High voltage engineering presentstion
PPT
Streamer theory of breakdown
PDF
Partial Discharge Techniques For Measuring Condition Of MV & HV Switchgear
PDF
04a Breakdown of Solid Insulation.pdf
PPT
IQ_Partial_Discharge_Presentation_complete.ppt
PPT
IQ_Partial_Discharge_Presentation.ppt
Breakdown due to Internal Discharges and Surface Breakdown
Mechanism for breakdown for
Solid breakdown (2) (1)
03 partial discharge theory cutler-hammer
PD_Presentation_1.pdf
Lecture 1 - Basics of High Voltage Engineering .ppsx
High_Voltage_Engineering_2E.pdf
1502957341lectrure_3_KUET [Autosaved] [Autosaved].pptx
UNIT I - HVE.ppt
Highvolatage enegineering updated.pptx
transformer dignostics on high voltage
Insulation and Dielectric Breakdown Design Paper SM54
High voltage switchgear charged detection
Week-High voltage engineering presentstion
Streamer theory of breakdown
Partial Discharge Techniques For Measuring Condition Of MV & HV Switchgear
04a Breakdown of Solid Insulation.pdf
IQ_Partial_Discharge_Presentation_complete.ppt
IQ_Partial_Discharge_Presentation.ppt
Ad

More from RajuGupta88 (6)

PPTX
OFFLINE MOTOR TEST R K GUPTA
PPTX
Condition Based Asset Management R K Gupta
PDF
TRANSFORMER TESTING DISSOLVED GAS ANALYSIS
PDF
TRANSFORMER TEST acceptance criteria
PDF
TRANSFORMER SAMPLE REPORT DGA PHYSICAL CONDITION
PPT
Motor Current Signature Analysis R K Gupta
OFFLINE MOTOR TEST R K GUPTA
Condition Based Asset Management R K Gupta
TRANSFORMER TESTING DISSOLVED GAS ANALYSIS
TRANSFORMER TEST acceptance criteria
TRANSFORMER SAMPLE REPORT DGA PHYSICAL CONDITION
Motor Current Signature Analysis R K Gupta

Recently uploaded (20)

PPT
Mechanical Engineering MATERIALS Selection
PDF
Structs to JSON How Go Powers REST APIs.pdf
PDF
Embodied AI: Ushering in the Next Era of Intelligent Systems
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PPTX
UNIT-1 - COAL BASED THERMAL POWER PLANTS
PPTX
Sustainable Sites - Green Building Construction
PPTX
Lecture Notes Electrical Wiring System Components
PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
PDF
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
PPTX
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PDF
PPT on Performance Review to get promotions
PDF
Operating System & Kernel Study Guide-1 - converted.pdf
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PPTX
OOP with Java - Java Introduction (Basics)
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PPTX
Foundation to blockchain - A guide to Blockchain Tech
PDF
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PPTX
CYBER-CRIMES AND SECURITY A guide to understanding
Mechanical Engineering MATERIALS Selection
Structs to JSON How Go Powers REST APIs.pdf
Embodied AI: Ushering in the Next Era of Intelligent Systems
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
UNIT-1 - COAL BASED THERMAL POWER PLANTS
Sustainable Sites - Green Building Construction
Lecture Notes Electrical Wiring System Components
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
Evaluating the Democratization of the Turkish Armed Forces from a Normative P...
MET 305 2019 SCHEME MODULE 2 COMPLETE.pptx
PPT on Performance Review to get promotions
Operating System & Kernel Study Guide-1 - converted.pdf
Model Code of Practice - Construction Work - 21102022 .pdf
OOP with Java - Java Introduction (Basics)
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
Foundation to blockchain - A guide to Blockchain Tech
BMEC211 - INTRODUCTION TO MECHATRONICS-1.pdf
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
CYBER-CRIMES AND SECURITY A guide to understanding

Partial Discharge Test - Switchgear

  • 1. Predictive Maintenance of MV Switchgear with Partial Discharge R K Gupta Principal Consulting Electrical Engineer (Power System) Reliability Engineer BE Electrical Protection, Automation, PLC & SCADA, Level 3 MCSA, Colorado USA
  • 2. IEC 60270 Section 3.1 Notes “Partial discharges are in general a consequence of local electrical stress concentrations in the insulation or on the surface of the insulation…” ..“Corona is a form of partial discharge that occurs in gaseous media around conductors which are remote from solid or liquid insulation…” ..“Partial discharges are often accompanied by emission of sound, light, heat, and chemical reactions…” “Localized electrical discharge that only partially bridges the insulation between conductors and which can or cannot occur adjacent to a conductor.” Partial Discharge Test
  • 3. IEEE Standard 400-2001 Notes “Partial discharge measurement is an important method of assessing the quality of the insulation of power cable system” “A partial discharge is an electrical discharge (formation of a streamer or arc) that does not bridge the entire space between two electrodes.” “Partial discharges may occur in a “void…at a contaminant…or at the tip of a well-developed water tree...” Partial Discharge Test
  • 4. Partial discharge Taxonomy Three basic types of PD sources:  Internal PD  Surface PD  Corona PD Focus on Internal Discharges
  • 5. PD Inception Condition  A free electron is available in the gas inside the void.  Mechanisms that allow a free electron inside the gas: a. Ionization by photon/gas molecule collision (background radiation) b. Schottky emission of electrons from metal and /or dielectric surfaces (electron injection).  The external field, fE0, exceeds the inception field, Einc. The free electron, accelerated by electric field, can trigger an electron avalanche (PD).
  • 6. Partial Discharge Process in Solid Insulator /Air Insulator  Solid insulators are manufactured to give an even distribution of electrical stress between the conducting electrodes.  Manufacturing processes invariably give rise to small cavities or voids in the insulation bulk. These cavities are usually filled with a gas of lower breakdown strength than the surrounding solid. The permittivity of the gas is invariably lower than that of the solid insulation, causing the field intensity in the cavity to be higher than that in the dielectric. Therefore under the normal working stress of the insulation, the voltage across the cavity may exceed the breakdown value and initiate electrical breakdown in the void.
  • 7. Equivalent circuit for cavity in insulator A solid insulator of thickness d contains a disc shaped cavity of thickness t and area A, as shown fig. In the equivalent circuit the capacitance Cc corresponds to the cavity, Cb corresponds to the capacity of the dielectric that is in series with Cc and Ca is the capacitance of the rest of the dielectric. Given that capacitance C, in Farads/m2, is given by; Where; e0 = permittivity of free space = 8.854 x 10-12 Fm- 1 er = relative permittivity A = area between electrodes d = separation of electrodes
  • 8. Breakdown Strength in Cavity If we assume that the gas in the cavity (of thickness t) in figure 1 has a relative permittivity of approximately 1, then: And, As Cb and Cc essentially form a capacitive divider, the voltage across the cavity, Vc, can be expressed as; Substituting into the above equation gives;
  • 9. Breakdown Strength in Cavity Electrical field strength across the cavity (Ec) is given by the equation Given that in most circumstances t << d and er is greater than 1, it can be seen that electrical stress in the cavity is greater than that in the surrounding insulation. This, coupled with the fact that the breakdown strength of the gas is likely to be significantly lower than that of the insulation, makes the gas in the void liable to breakdown under normal working conditions.
  • 10. Breakdown Strength in Cavity From the equations above it can be seen that the voltage across the dielectric at which discharge activity will initiate in the cavity, Vai, is given by; In practice voids in solid insulators are very often approximately spherical. In this case the field in the void is given by; Where erc = relative permittivity of gas in void. When er >> erc this approximates to:
  • 11. Relative permittivity and breakdown strengths of some typical high voltage HV Insulating Material
  • 12. Voltage and Current in discharging Cavity Each time a discharge occurs in the cavity, charge is transferred from one side of the cavity to the other until the potential difference across the cavity is too small to maintain the discharge. When the insulator is subject to a sinusoidal alternating voltage, charge builds up within the void as the applied voltage increases or decreases. This causes a series of discharges with charge first moving in one direction, then the other. Figure 2 shows how the voltage and current across a cavity changes with applied voltage.
  • 13. The dotted curve shows the voltage that would occur across the cavity if the discharges did not equalize the potential difference across the cavity. As the voltage Vc reaches the value V+, a discharge takes place and the, the voltage Vc collapses and the discharge extinguishes. The voltage across the cavity then starts again increasing until it reaches V+ , when a new discharge occurs. In this way several discharges may take place during the rising part of the applied voltage. Similarly, on decreasing the applied voltage the cavity discharges as the voltage across it reaches V-, In this way groups of discharges are generated by a single cavity and give rise to positive and negative current pulses on raising and decreasing the applied voltage respectively. Voltage and Current in discharging Cavity
  • 14. DEGRADING EFFECT IN SOLID INSULATION When the gas in a cavity breaks down, the opposite surfaces of the insulation momentarily become cathode and anode. Some of the electrons hitting the anode are sufficiently energetic to break the chemical bonds of the insulation surface. Similarly, bombardment of the cathode by positive ions may cause damage by increasing the surface temperature and produce local thermal instability. These degrading effects form small channels and pits in the surface that can elongate through the insulation. In addition to the ionic bombardment, chemical degradation may result from active discharge products, like O3 or NO2, formed in the air by the discharges. The net effect is slow erosion of the insulating material and a very gradual increase in the size of the cavity
  • 15. Electrical Trees  Electrical trees are comprised of a series of interconnecting channels or discharge paths with diameters ranging from less than a micron to tens of microns.  Discharge activity in voids will eventually become centered at particular sites producing deep cavities in the surface. The cavities grow in length along the discharge axis and the energy of discharge impinging on their tips increases. This combined with electrical stress concentration by virtue of their point like form, produces increasingly intense electrical fields at the tips of the discharging cavities.  Eventually the breakdown strength of the material in the immediate vicinity of the tip is exceeded. Breakdown follows with the evaporation, in the space of a few nanoseconds, of a small volume of material.  This rapid conversion launches small shock waves into the insulation. These waves create, in time, a structure of fine cracks extending into the insulation. Their name comes from the dendritic patterns they from in the insulation.
  • 16. Electrical trees emanate from points of stress enhancement in insulation. This can be a metal inclusion or a protrusion on a conductor but in practice they more usually originate from a void. The exact process by which electrical trees propagate is still not fully understood, however, it is generally accepted as being a combination of mechanical and thermal effects. There are two clear stages in the development of electrical trees under the application of an alternating voltage, the inception period, which may be considerable and a much shorter formative period. Eventually the tree will bridge the insulation. Discharges continue to occur without breakdown because space charge sets up a reverse field in the channels to counter the field between the electrodes. During this period the channels slowly widen. Eventually the field can no longer be maintained in the widened channels and catastrophic breakdown occurs, creating a very large channel though the insulation. Electrical Trees
  • 17. Tracking  Tracking is the formation of a permanent conducting path across an insulator surface. Usually the conduction path results from degradation of the insulation. For tracking to occur the insulation must be a carbon based compound.  Most high voltage plant is situated outside. In industrial areas, insulators become contaminated with pollution and dirt from the atmosphere. Where substations are situated near the sea, salt very quickly covers the plant. In the presence of moisture, these contaminating layers gives rise to leakage current over the insulator surface. This heats the surface and through evaporation causes interruption in the moisture film. Large potential differences are generated over the gaps in the moisture film and small sparks can bridge the gaps. Heat from the sparks causes carbonization of the insulation and leads to the formation of permanent carbon tracks on the surface. Tracking as a phenomenon severely limits the use of organic insulators in outdoor environments. The rate of tracking depends on the structure of the polymers and can be significantly reduced by adding appropriate fillers to the polymer which inhibit carbonization.
  • 18. CORONA Corona is a partial discharge in regards that gas breakdown begins at a position of high electric field but dies out as the electric field decreases very rapidly as a function of distance from the highly stressed position. The breakdown can die out for two reasons; The region of high field is too small to generate a fully formed breakdown channel. The field falls to such a low value, that even a fully formed breakdown channel cannot propagate.
  • 19. Corona forms in partially ionised regions adjacent to conductors and causes a change in the electric field between the conductor and the ground. In effect, it can be seen as an extension of the conductor. As such, it will effectively reduce the capacitance between the conductor and ground, as their separation decreases. This causes a drop in the voltage on the conductor, a potential difference between the conductor and the voltage source and, therefore, a current flow from the voltage source to the conductor. The electric field in a corona is sufficiently high that when a free electron occurs, that electron will, on average, generate more than one additional electron (and positive ion). So a corona is full of positive and negative ions (electrons). Thus when the field reduces to the extent that the original current ceases to flow, the electric field does not immediately return to its previously high value. Before that can happen, the positive and negative ions must flow in the field toward the negative and positive electrodes respectively. As the negative charges are in the form of electrons, they can propagate sufficiently fast to contribute to the measured partial discharge signal. However massive positive ions flow so slowly that they typically generate a very small current over a long period of time. Thus a corona can be thought of as generating a PD signal though three mechanisms. First, the ionisation of a channel, which tends to look like an extension of the conductor and therefore increases the capacitance of the conductor to ground. Second rapid migration of electrons toward the positive electrode in a system where negative charge flows as electrons. And thirdly, flow of positive ions which tends to be too slow to be detected by most PD measuring systems. The time scale for the first two phenomena is nanoseconds to microseconds, while that for the third phenomena can be milliseconds or more. CORONA
  • 20. Corona tends to be repetitive, as once the region is cleared of charge, it returns to the conditions which generated it in the first place. Corona in air is sensitive to air velocity and environmental conditions which affect space charge near the conductor. In many gases, including air, corona generated by positive and negative voltages differ substantially. This is due to the physical difference between negative charge carriers (electrons) and positive charge carriers (positive ions). Electrons being light and mobile gain kinetic energy very rapidly from an electric field, while positive ions are heavy and much less mobile. The outside surface of molecules is made up of electrons, so violent phenomena, which dislodge charge from a molecule, free an electron and simultaneously create a heavy positive ion. In corona from a negative conductor, electrons propagate away from the conductor in the direction of corona growth. Thus they can create further electrons through molecular collisions. In corona from a positive conductor, the electrons propagate towards the conductor and away from the direction of corona growth. In this case, electrons are generally detached ahead of the corona tip by photons generated within the corona. CORONA
  • 21. Water Trees A water tree is a bush or fan like structure developing like an electrical tree, from points of stress enhancement. Water trees cause a reduction in the insulation's breakdown stress level which encourages breakdown. Electrical trees can, on occasion, be initiated from a water tree speeding the breakdown process. Water trees are more diffuse than electrical trees and generally grow at lower electrical stresses. Two types of water tree have been recognized according to where the tree initiates, ‘bow-tie’ trees and ‘vented’ trees. Bow-tie trees are initiated in the bulk of the insulating material, often from a void, and grow towards the conducting screens. They clearly derive their name from the pattern they form. Vented trees grow from one of the conducting screens into the insulation bulk
  • 22. PD Testing Methods  Online Partial Discharge Testing Ultrasonic Transient Earth Voltage High Frequency Current Transformer Electrical Method (Inductive & Capacitive)  Offline Partial Discharge Testing Capacitance Voltage Divider( CVD) method
  • 23. Ultrasonic Electrical arcs in the air and corona effects emit sounds and ultrasounds. The basic electrical problems that produce distinct ultrasound waves that can be detected by Ultrasonic Testing include partial discharge, corona and tracking. Ultrasonic measurement is most powerful on a comparative basis and will significantly increase the reliability of correct detection of partial discharge. Ranges of Ultrasonic detection Center frequency 40 KHz Bandwidth 38kHz-48kHz Acoustic Airborne Airborne acoustic (ultrasonic) radiation through air from corona and surface discharges in the plant
  • 24. Ultrasonic / Acoustic Airborne Test Method Background Noise Measurement If any reading is made with the sensor flat on a surface (not over a vent or air gap) this can be discounted as background noise. AA/Ultrasonic Sensor Attachment Requirements  There must be a clear air path (line of sight) from the sensor to the discharge source, i.e. a vent or hole in the plant housing.  Fully enclosed air insulated switchgear with no grills, vents, air gaps etc, will not be suitable for Airborne Acoustic measurements.
  • 25. Transient Earth Voltage Transient Earth Voltage (TEV) PD signals are generated by internal partial discharges in switchgear, cable terminations, motors and transformers. TEV signals are in a higher frequency range of between 4MHz – 100MHz and are oscillatory in general. The resultant PD signals are measured in dB (decibels), as is the convention for on-line s w i t c h g e a r t e s t i n g .
  • 26. Background Noise Measurement TEV measurements can be affected by background electrical noise in the substation. Sources include: Power electronic switching, e.g. from DC power supplies. Corona from outdoor switchyards. High frequency communication systems, e.g. two-way radios TEV Test Method
  • 27. The TEV sensor should be placed flat against the metal-clad switchgear close to vents or gaskets or seams on the metal- clad housing. The LEDs will light to show the measured PD level. The user MUST hold the unit whilst in use. It is recommended to place the TEV sensor at multiple points on the plant for example on the cable boxes and front and back of each switchgear panel. TEV Test Method
  • 28. High Frequency Current Transformer (HFCT) sensor which is clipped around the earth strap of the cable. These pulses are generally in the frequency range of between 200kHz – 4MHz and are typically mono polar in shape. The unit measures the Cable PD pulses in pico Coulombs (pC’s) by measuring the charge content (area under the mono polar pulse). High Frequency Current Transformer
  • 29. Procedure for HFCT PD Measurement Background Noise Measurement HFCT measurements can be affected by background electrical noise sources inside and outside the substation. Sources include: Radio frequency interference from local radio transmission Corona from outdoor switchyards. To measure the background noise level, attach the HFCT to the earthing conduit of a de-energized feeder, or a nearby LV earth.
  • 30. Electrical Method Capacitive Sensor The Capacitive Sensor measures the electric field on the cable and cable joint. Sensors are designed to detects the quick variations of electrical fields caused by PD. The probe is a coated metal plate that create a capacitor between the cable and the plate. This capacitive coupler allows to read the PD activity on surface. The PD signal is detected by a capacitive probe, then amplified by the equipment in radio frequency bandwidth. The signal amplitude is proportional to the discharge energy.
  • 31. ULD 40 ( Ultrasonic Detector) The ULD-40 is an ultrasonic detector designed for corona and arcing inspections for predictive maintenance in electric utilities. Main Applications  Electrical Inspections: corona effect localization, arcs on shields.  General Mechanical Inspections: motors, compressors, gears, bearing monitoring. Gas, air, pressure leaks, leak detection without pressure or vacuum. Aerospace Sector: airplane doors and windows, air tightness
  • 32. Detection of Electrical Arcs and Corona Effects Electrical arcs in the air and corona effects emit sounds and ultrasounds. The role of the ULD-40 consists of capturing emitted ultrasounds and of translating them into the audible range. The ULD-40 accurately pinpoints and identifies corona effects and arcs that may be encountered on any type of high voltage installation simply by scanning around the suspected area.
  • 33.  Portable expert system for detection of partial discharges  Increase your network reliability and workers security XDP
  • 34.  It is an instrument that enables to quantify the intensity of the high frequency electric field signal emitted by the partial discharge of a component, and to translate it into decibels (dB)  A decibel (dB) is a unit that expresses the intensity of a signal in relations to a reference on the logarithmic scale XDP
  • 35. With the XDP  Follow up on ageing process of the critical components’ insulation  Perform Quality Control of the insulators during installation or repair  Safety control prior to work on energize equipment
  • 36. XDP Advantages  Portable  Verification done under normal charge of the electric network – No service interruption  Quick readings  Very sensible  Pinpoints the problem  Our 3rd generation of PD Detector
  • 37. XDP Technical Specifications  Peak measurement value in dB relative to 15 picoCoulomb  Peak detection with a fast numeric circuit  Fast numeric processor (DSP) for instant analysis results  Wave’s shape inspection in high frequency to determine PD proximity
  • 38. XDP Technical Specifications…  LCD (Liquid Crystal Display) displays wave form and dB reading  Easy to read, big letter casings  Upload/download capability  PC (Windows) interface for PD readings analysis/trending
  • 39. XDP Technical Specifications…  Dynamic range of 40 dB  Up to 64 readings recording capability  Bandwidth of 300 kHz to 70 MHz  Sampling frequency of 30 MHz  Sampling period of 16 cycles (50 or 60 HZ)  Built-in Real Time Clock
  • 40. XDP Technical Specifications…  Keeps in memory up to 10 PD signatures for quick PD recognition  Quick auto-verification procedure for high reliability  8 hour battery autonomy  The smaller PD Expert System on the market  203 X 114 X 51 mm (8 X 4.5 X 2 in.)  0,86 kg (1,9 lbs)
  • 41. XDP Applications  Cable & accessories  Joint  Elbow  T  Custom  Switchgears  Distribution Transformers  Etc.
  • 42. The Handling Rod The use of the Spatula, which is a surface sensor, with the 61 cm (24 in.) handling rod does not required direct access to the conductor
  • 43. The Capacitive Sensor  The Capacitive Sensor measures the electric field on the cable and cable joint Our Capacitive Sensor uses a flexible Spatula easily adaptable to the cable joint form
  • 44. How it works  The XDP detects the quick variations of electrical fields caused by PD  The probe is a coated metal plate that create a capacitor between the cable and the plate  This capacitive coupler allows to read the PD activity on surface  It is moved along joints and on cable insulation jacket, in order to detect the presence of PD activity
  • 45.  The PD signal is detected by a capacitive probe, then amplified by the XDP in radio frequency bandwidth  The signal amplitude is proportional to the discharge energy  The energy is displayed on the XDP in dB (relative value)
  • 46. How to use the Spatula Sensor  Check the reference value on a regular basis to make sure that the XDP works well  Turn off the XDP  Connect the reference module  Connect the Spatula Sensor  Place the sensor on the module in a way to make it cling around it as much as possible
  • 47. Check the reference value…  Activate the XDP  On the numeric display, you must read the displayed value on the sensor’s case
  • 48.  This technique will allow you to detect a PD activity even in an environment with normal to high ambient noise (12 – 20 dB)  Always adjust the spatula the way it fit as much as possible around the cable and cable joint  Always use the handling rod
  • 49. Inductive Probe  Applications  Terminations  Shielded cables  Cable joints with grounding braid
  • 51. Quality control of a 12 dB ambient noise splice  Without defect  A = 10dB  B = 12dB  C = 12dB  D = 10dB  With defect  A = 12dB  B = 14dB  C = 34dB  D = 16dB
  • 52. PD activities level classification  Level 1: Free of Partial Discharge activity. No necessary action at this time. Retest within 12 to 18 months (< 12dB)  Level 2: Moderate levels of Partial Discharge activity. Retest within 1 year (12 – 20dB)  Level 3: High level of Partial Discharge activity. Repair or replacement required (20 – 35dB)
  • 53. PD activities level classification…  Level 4: Very high level of Partial Discharge activity (> 35dB)  We strongly recommend to restrict the access to the area  Repair or replacement required as soon as possible