Liquid Leak Detection/LocationLiquid Leak Detection/Location
Systems for piping, raised floors,Systems for piping, raised floors,
semiconductor tools, containmentsemiconductor tools, containment
piping, fuel systems and otherpiping, fuel systems and other
applicationsapplications
Company ProfileCompany Profile
PermAlert is part of Perma-Pipe the largestPermAlert is part of Perma-Pipe the largest
prefabricated – preinsulated pipeprefabricated – preinsulated pipe
manufacturer in the USmanufacturer in the US
PAL-AT Leak Detection was introduced inPAL-AT Leak Detection was introduced in
1988 and was the reason for founding1988 and was the reason for founding
PermAlert ESPPermAlert ESP
Sales Volume of the parent corporationSales Volume of the parent corporation
(MFRI) is about US $178 million with over(MFRI) is about US $178 million with over
500 employees worldwide500 employees worldwide
PAL-AT Cable Systems andPAL-AT Cable Systems and
LiquidWatch Probe SystemsLiquidWatch Probe Systems
PAL-AT uses coaxial cables and probes toPAL-AT uses coaxial cables and probes to
monitor for liquid leakage. The system canmonitor for liquid leakage. The system can
detect and locate leaks, breaks and shorts ondetect and locate leaks, breaks and shorts on
the sensor cable as well as probe activations.the sensor cable as well as probe activations.
LiquidWatch is a probe monitoring systemLiquidWatch is a probe monitoring system
and can monitor up to 64 probes from aand can monitor up to 64 probes from a
single panel. The probes are monitored forsingle panel. The probes are monitored for
activation, breaks and shorts.activation, breaks and shorts.
Time Domain ReflectometryTime Domain Reflectometry
PAL-ATPAL-AT
TDR is a cable measuring technologyTDR is a cable measuring technology
related to sonar and radar. By sendingrelated to sonar and radar. By sending
energy pulses down the centerenergy pulses down the center
conductor of a coaxial cable andconductor of a coaxial cable and
measuring the reflected energy to themeasuring the reflected energy to the
outer braid a map can be stored of theouter braid a map can be stored of the
cable and monitored for change. Whencable and monitored for change. When
change occurs the type of alarm and itschange occurs the type of alarm and its
location is displayed on the panel.location is displayed on the panel.
TDR Trace of Dry CableTDR Trace of Dry Cable
TDR Trace with LeakTDR Trace with Leak
DetectedDetected
TDR Trace of System with Wet CableTDR Trace of System with Wet Cable
TDR Trace showing Growing LeakTDR Trace showing Growing Leak
Map 3 ResponseMap 3 Response
Second Leak DetectedSecond Leak Detected
Monitoring with Liquid on the CableMonitoring with Liquid on the Cable
Break DetectedBreak Detected
Short DetectedShort Detected
Probe ActivatedProbe Activated
PAL-AT PanelsPAL-AT Panels
AT20C - Monitoring up to 2,000’ (600 m) on a singleAT20C - Monitoring up to 2,000’ (600 m) on a single
cablecable
AT50C - Monitoring up to 5,000’ (1500 m) equivalentAT50C - Monitoring up to 5,000’ (1500 m) equivalent
length on a single cablelength on a single cable
AT20K - Monitoring up to 7,500’ (2500 m) equivalentAT20K - Monitoring up to 7,500’ (2500 m) equivalent
length per cable with a maximum of two cableslength per cable with a maximum of two cables
AT40K - Monitoring up to 5,000’ (1500m) equivalentAT40K - Monitoring up to 5,000’ (1500m) equivalent
length per cable with a maximum of eight cableslength per cable with a maximum of eight cables
AT80K - Monitoring up to 7,500’ (2500 m) equivalentAT80K - Monitoring up to 7,500’ (2500 m) equivalent
length per cable with a maximum of eight cableslength per cable with a maximum of eight cables
Types of CableTypes of Cable
PAL-ATPAL-AT
AGW Gold Sensor cable for use inAGW Gold Sensor cable for use in
containment piping, trenches, trayscontainment piping, trenches, trays
and subfloorsand subfloors
AGT Gold Sensor cable for useAGT Gold Sensor cable for use
in subfloors and trays. More sensitivein subfloors and trays. More sensitive
than AGWthan AGW
TFH Sensor cable for detectingTFH Sensor cable for detecting
hydrocarbons and solvents while ignoringhydrocarbons and solvents while ignoring
waterwater TFHTFH TFHTFH
Types of ProbesTypes of Probes
PAL-AT and LiquidWatchPAL-AT and LiquidWatch
PHL/PWS Solid state probes forPHL/PWS Solid state probes for
hydrocarbon and conductive liquidshydrocarbon and conductive liquids
PSTV/PTHL/PFS Float switches forPSTV/PTHL/PFS Float switches for
high/low levelhigh/low level
PT10 (PAL-AT) Probe integrators andPT10 (PAL-AT) Probe integrators and
PA-10 (LiquidWatch) Probe AdaptorsPA-10 (LiquidWatch) Probe Adaptors
for dry contactsfor dry contacts
LiquidWatchLiquidWatch
LiquidWatch has two basic panels. TheLiquidWatch has two basic panels. The
LW64 is for use in normal classifiedLW64 is for use in normal classified
probe locations while the LW64ISprobe locations while the LW64IS
provides a UL Listed System forprovides a UL Listed System for
monitoring in Class 1, Division 1 Groupsmonitoring in Class 1, Division 1 Groups
C & D locations. The basic panelC & D locations. The basic panel
monitors up to eight probes withmonitors up to eight probes with
modules being added for additionalmodules being added for additional
probe requirements.probe requirements.
ApplicationsApplications
Raised Floors - Data Centers, ISPs, Clean RoomsRaised Floors - Data Centers, ISPs, Clean Rooms
Telecommunication, Semiconductor, Office BldgsTelecommunication, Semiconductor, Office Bldgs
PharmaceuticalPharmaceutical
Piping - Containment piping, single wall piping,Piping - Containment piping, single wall piping,
hydrocarbon piping, waste drainshydrocarbon piping, waste drains
Trenches and Trays - Under wet benches, pipingTrenches and Trays - Under wet benches, piping
and equipmentand equipment
Generators, Electrical Switch Gear andGenerators, Electrical Switch Gear and
Transformers for hydrocarbon leakage or waterTransformers for hydrocarbon leakage or water
seepageseepage
What ever needs liquid leakage detection that aWhat ever needs liquid leakage detection that a
probe or sensor cable can be usedprobe or sensor cable can be used
PermAlert Liquid Leak Detection Systems
PermAlert Liquid Leak Detection Systems
PermAlert Liquid Leak Detection Systems
Palcom SoftwarePalcom Software
PAL-AT and LiquidWatchPAL-AT and LiquidWatch
Palcom allows remote control of up toPalcom allows remote control of up to
254 panels with the ability to review254 panels with the ability to review
TDR traces, review the history of eachTDR traces, review the history of each
unit and to pull down a Cad drawing forunit and to pull down a Cad drawing for
each system for location of leaks,each system for location of leaks,
breaks, shorts or probe activation's.breaks, shorts or probe activation's.
Archive DataArchive Data
POWER LOST AT 8985 ON 18/95 RESTORED AT 0853 ON 5/8
YEAR CHANGED FROM 29 TO 98 AT 0853 ON 5/8
CABLE 1 SETUP, WITH LENGTH OF 514 FEET AT 0921 ON 5/8
LEAK DETECTED IN CABLE 3 at 225 FEET AT 1157 ON 5/8
ALARM ON CABLE 3 SILENCED AT 1157 ON 5/8
CABLE 4 SETUP, WITH LENGTH OF 538 FEET AT 1208 ON 5/8
SECURITY CODE 1 ENTERED, LEVEL 250 AT 1210 ON 5/8
NEW CABLE 4 REFERENCE, STORED AS MAP 1 AT 1210 ON 5/8
CABLE 4 MONITORING ON, MAP 1 AT 1210 ON 5/8/98
CABLE 4 RETURNED TO NORMAL AT 1211 ON 5/8
SECURITY CODE 1 ENTERED, LEVEL 250 AT 1217 ON 5/8
CABLE 3 SETUP, WITH LENGTH OF 833 FEET AT 1217 ON 5/8
NEW CABLE 3 REFERENCE, STORED AS MAP 1 AT 1217 ON 5/8
CABLE 3 MONITORING ON, MAP 1 AT 1217 ON 5/8/98
CABLE 3 RETURNED TO NORMAL AT 1218 ON 5/8
SECURITY CODE 1 ENTERED, LEVEL 250 AT 1225 ON 5/8
CABLE 2 SETUP, WITH LENGTH OF 815 FEET AT 1225 ON 5/8
NEW CABLE 2 REFERENCE, STORED AS MAP 1 AT 1225 ON 5/8
CABLE 2 MONITORING ON, MAP 1 AT 1225 ON 5/8/98
CABLE 2 RETURNED TO NORMAL AT 1226 ON 5/8
SECURITY CODE 1 ENTERED, LEVEL 250 AT 1231 ON 5/8
CABLE 1 SETUP, WITH LENGTH OF 514 FEET AT 1231 ON 5/8
NEW CABLE 1 REFERENCE, STORED AS MAP 1 AT 1231 ON 5/8
CABLE 1 MONITORING ON, MAP 1 AT 1231 ON 5/8/98
CABLE 1 RETURNED TO NORMAL AT 1232 ON 5/8
**********End of Archives**********
Benefits of PermAlert’s PAL-Benefits of PermAlert’s PAL-
ATAT
Wet cable startupWet cable startup
Multiple Leak location capabilityMultiple Leak location capability
Location of BreaksLocation of Breaks
Detection of Shorts versus LeaksDetection of Shorts versus Leaks
Not susceptible to contamination from dirt/dust, etc.Not susceptible to contamination from dirt/dust, etc.
Archive History DataArchive History Data
UL Listed, FM Approved, CE Approval availableUL Listed, FM Approved, CE Approval available
Class 1 Div 1 Groups C & D Sensor CircuitsClass 1 Div 1 Groups C & D Sensor Circuits
Up to 8 circuits and 7,500’ (2500 m) per circuitUp to 8 circuits and 7,500’ (2500 m) per circuit
Corrosion resistant sensor cablesCorrosion resistant sensor cables
Different cable types on the same circuitDifferent cable types on the same circuit
EPA third party testedEPA third party tested
Benefits of LiquidWatchBenefits of LiquidWatch
Modular in design allowing for easyModular in design allowing for easy
expansionexpansion
Monitoring of probes for activation and theMonitoring of probes for activation and the
leader cable for breaks and shortsleader cable for breaks and shorts
History log of eventsHistory log of events
UL Listed for Class 1 Div 1, Groups C & DUL Listed for Class 1 Div 1, Groups C & D
locationslocations
Different probe typesDifferent probe types
Probe adaptor to allow interface of any dryProbe adaptor to allow interface of any dry
contact probe devicecontact probe device
Questions and Answer PeriodQuestions and Answer Period

More Related Content

PPT
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...
PDF
válvulas de instrumentação
PDF
소화설비_계통도.pdf
PDF
Mecanica dos fluídos 2a edição revisada
DOCX
CONTROL CALIDAD.DOCX
PDF
Flow assurance and surge analysis
PDF
2-Canadian Professional Engineering And Geoscience Practice And Ethics.pdf
PDF
CONCEPT OF SCADA.pdf
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...
válvulas de instrumentação
소화설비_계통도.pdf
Mecanica dos fluídos 2a edição revisada
CONTROL CALIDAD.DOCX
Flow assurance and surge analysis
2-Canadian Professional Engineering And Geoscience Practice And Ethics.pdf
CONCEPT OF SCADA.pdf

What's hot (20)

PPS
Boiler explosion at exxon mobil singapore
PPTX
subhankar_conv_interlocks.pptx
PDF
Guide Chilean Biotechnology Companies
PDF
P&ID Symbols | Gaurav Singh Rajput
PDF
Pipeline Design for Isothermal, Laminar Flow of Non-Newtonian Fluids
PDF
Process control ch 1
PDF
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
PPTX
Medição de vazão
PDF
HALLIBURTON Reference Letter
PDF
Nylon de Metales Diaz
PDF
Industrial heat tracing solutions
PDF
Icono Parque Flamengo Residencial Lançamento
PDF
Task-based teaching assessment scale and criteria : Oral presentation assessm...
PDF
MASCARÓ, O Custo das decisões arquitetônicas (parte 1).pdf
PDF
Introduction To Pressure Surge In Liquid Systems
PPSX
Control valve sizing, selection & quotation software
DOCX
Eletrotécnica ponte wheatstone
PPTX
Process Control Fundamentals and How to read P&IDs
PPT
Hydropower plant
Boiler explosion at exxon mobil singapore
subhankar_conv_interlocks.pptx
Guide Chilean Biotechnology Companies
P&ID Symbols | Gaurav Singh Rajput
Pipeline Design for Isothermal, Laminar Flow of Non-Newtonian Fluids
Process control ch 1
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
Medição de vazão
HALLIBURTON Reference Letter
Nylon de Metales Diaz
Industrial heat tracing solutions
Icono Parque Flamengo Residencial Lançamento
Task-based teaching assessment scale and criteria : Oral presentation assessm...
MASCARÓ, O Custo das decisões arquitetônicas (parte 1).pdf
Introduction To Pressure Surge In Liquid Systems
Control valve sizing, selection & quotation software
Eletrotécnica ponte wheatstone
Process Control Fundamentals and How to read P&IDs
Hydropower plant
Ad

Viewers also liked (20)

PDF
Transformação digital - Ong Santa Fé
PPTX
3Com NET BUILDER II
DOCX
Mochilas wayuu de la guajira
DOCX
Mochilas arhuacas en lana de ovejo
PPTX
Focus area 2: Chemical Substances
PPTX
Herramienta web 2.0 udelas
PPTX
Bibliografía en formato vancouver
DOCX
ETICA Y DEONTOLOGIA PROFESIONAL - EXAMEN 20% - CORTE III
PPTX
Análisis bromatológicos
DOCX
Resumen analitico sobre Access
PDF
IMPLEMENTATION OF RELIABILITY CENTERED MAINTENANCE IN AIR COMPRESSOR UNIT
PDF
Filter driers for refrigeration system
PPT
Ttk1D Leak Detection
PPT
TTK 1L Filter/Driers
PDF
Pipeline leak detection system
PDF
Odes aux aimés
PDF
ci_with_sphinx_in_flect
PDF
2017 ifma presentation pdf
PPTX
3Com 3C96010C-AC
PDF
Formica Infiniti
Transformação digital - Ong Santa Fé
3Com NET BUILDER II
Mochilas wayuu de la guajira
Mochilas arhuacas en lana de ovejo
Focus area 2: Chemical Substances
Herramienta web 2.0 udelas
Bibliografía en formato vancouver
ETICA Y DEONTOLOGIA PROFESIONAL - EXAMEN 20% - CORTE III
Análisis bromatológicos
Resumen analitico sobre Access
IMPLEMENTATION OF RELIABILITY CENTERED MAINTENANCE IN AIR COMPRESSOR UNIT
Filter driers for refrigeration system
Ttk1D Leak Detection
TTK 1L Filter/Driers
Pipeline leak detection system
Odes aux aimés
ci_with_sphinx_in_flect
2017 ifma presentation pdf
3Com 3C96010C-AC
Formica Infiniti
Ad

Similar to PermAlert Liquid Leak Detection Systems (20)

PDF
1603175957466-TELECOM CABLES .pdf
PDF
Unimed Disposable Patient Supplies Lead Wires, Cable and Sensors for Spo2,ECG...
PDF
Pansw ecg trunk_cable
PDF
Cable Sniffer LV Cable Fault Locator - Operating Manual
PDF
flosmart-CH-WLine-Services-Presentation.pdf
PDF
Drager Polytron Pulsar Fixed Gas Detectors - Spec Sheet
PDF
Panduit tx6000 utp-copcable-w
PPT
WaveAlert Acoustic Pipeline Leak Detection
PPTX
Presentation-Telemetrics Equipments Pvt Ltd
PDF
Drager Polytron Pulsar Duct Mount Fixed Gas Detector - Spec Sheet
PPTX
High Voltage, Inc. Products Presentation Short Version
PPTX
Athens Datacentres And 10 G
PDF
Tray Cables vs AWM Cables vs Service Cables
PDF
Sound Wave (Acoustic Emission)Monitoring and Detection of Bridge Broken Wire.pdf
PDF
Cables NFPA 79
PDF
Drager Polytron 5700 Fixed Gas Detector - Spec Sheet
PDF
Product Preview & Price List - Neptune India
PDF
Trend Networks Catalog
1603175957466-TELECOM CABLES .pdf
Unimed Disposable Patient Supplies Lead Wires, Cable and Sensors for Spo2,ECG...
Pansw ecg trunk_cable
Cable Sniffer LV Cable Fault Locator - Operating Manual
flosmart-CH-WLine-Services-Presentation.pdf
Drager Polytron Pulsar Fixed Gas Detectors - Spec Sheet
Panduit tx6000 utp-copcable-w
WaveAlert Acoustic Pipeline Leak Detection
Presentation-Telemetrics Equipments Pvt Ltd
Drager Polytron Pulsar Duct Mount Fixed Gas Detector - Spec Sheet
High Voltage, Inc. Products Presentation Short Version
Athens Datacentres And 10 G
Tray Cables vs AWM Cables vs Service Cables
Sound Wave (Acoustic Emission)Monitoring and Detection of Bridge Broken Wire.pdf
Cables NFPA 79
Drager Polytron 5700 Fixed Gas Detector - Spec Sheet
Product Preview & Price List - Neptune India
Trend Networks Catalog

Recently uploaded (20)

PDF
distributed database system" (DDBS) is often used to refer to both the distri...
PDF
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
PDF
BIO-INSPIRED ARCHITECTURE FOR PARSIMONIOUS CONVERSATIONAL INTELLIGENCE : THE ...
PDF
22EC502-MICROCONTROLLER AND INTERFACING-8051 MICROCONTROLLER.pdf
PDF
Categorization of Factors Affecting Classification Algorithms Selection
PPTX
Chemical Technological Processes, Feasibility Study and Chemical Process Indu...
PPTX
Information Storage and Retrieval Techniques Unit III
PDF
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
PPTX
Software Engineering and software moduleing
PPTX
Amdahl’s law is explained in the above power point presentations
PDF
Soil Improvement Techniques Note - Rabbi
PPTX
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
PDF
Improvement effect of pyrolyzed agro-food biochar on the properties of.pdf
PPT
Total quality management ppt for engineering students
PDF
Exploratory_Data_Analysis_Fundamentals.pdf
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PPTX
introduction to high performance computing
PPTX
Feature types and data preprocessing steps
PPTX
Current and future trends in Computer Vision.pptx
PPTX
Fundamentals of safety and accident prevention -final (1).pptx
distributed database system" (DDBS) is often used to refer to both the distri...
EXPLORING LEARNING ENGAGEMENT FACTORS INFLUENCING BEHAVIORAL, COGNITIVE, AND ...
BIO-INSPIRED ARCHITECTURE FOR PARSIMONIOUS CONVERSATIONAL INTELLIGENCE : THE ...
22EC502-MICROCONTROLLER AND INTERFACING-8051 MICROCONTROLLER.pdf
Categorization of Factors Affecting Classification Algorithms Selection
Chemical Technological Processes, Feasibility Study and Chemical Process Indu...
Information Storage and Retrieval Techniques Unit III
Human-AI Collaboration: Balancing Agentic AI and Autonomy in Hybrid Systems
Software Engineering and software moduleing
Amdahl’s law is explained in the above power point presentations
Soil Improvement Techniques Note - Rabbi
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
Improvement effect of pyrolyzed agro-food biochar on the properties of.pdf
Total quality management ppt for engineering students
Exploratory_Data_Analysis_Fundamentals.pdf
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
introduction to high performance computing
Feature types and data preprocessing steps
Current and future trends in Computer Vision.pptx
Fundamentals of safety and accident prevention -final (1).pptx

PermAlert Liquid Leak Detection Systems

  • 1. Liquid Leak Detection/LocationLiquid Leak Detection/Location Systems for piping, raised floors,Systems for piping, raised floors, semiconductor tools, containmentsemiconductor tools, containment piping, fuel systems and otherpiping, fuel systems and other applicationsapplications
  • 2. Company ProfileCompany Profile PermAlert is part of Perma-Pipe the largestPermAlert is part of Perma-Pipe the largest prefabricated – preinsulated pipeprefabricated – preinsulated pipe manufacturer in the USmanufacturer in the US PAL-AT Leak Detection was introduced inPAL-AT Leak Detection was introduced in 1988 and was the reason for founding1988 and was the reason for founding PermAlert ESPPermAlert ESP Sales Volume of the parent corporationSales Volume of the parent corporation (MFRI) is about US $178 million with over(MFRI) is about US $178 million with over 500 employees worldwide500 employees worldwide
  • 3. PAL-AT Cable Systems andPAL-AT Cable Systems and LiquidWatch Probe SystemsLiquidWatch Probe Systems PAL-AT uses coaxial cables and probes toPAL-AT uses coaxial cables and probes to monitor for liquid leakage. The system canmonitor for liquid leakage. The system can detect and locate leaks, breaks and shorts ondetect and locate leaks, breaks and shorts on the sensor cable as well as probe activations.the sensor cable as well as probe activations. LiquidWatch is a probe monitoring systemLiquidWatch is a probe monitoring system and can monitor up to 64 probes from aand can monitor up to 64 probes from a single panel. The probes are monitored forsingle panel. The probes are monitored for activation, breaks and shorts.activation, breaks and shorts.
  • 4. Time Domain ReflectometryTime Domain Reflectometry PAL-ATPAL-AT TDR is a cable measuring technologyTDR is a cable measuring technology related to sonar and radar. By sendingrelated to sonar and radar. By sending energy pulses down the centerenergy pulses down the center conductor of a coaxial cable andconductor of a coaxial cable and measuring the reflected energy to themeasuring the reflected energy to the outer braid a map can be stored of theouter braid a map can be stored of the cable and monitored for change. Whencable and monitored for change. When change occurs the type of alarm and itschange occurs the type of alarm and its location is displayed on the panel.location is displayed on the panel.
  • 5. TDR Trace of Dry CableTDR Trace of Dry Cable
  • 6. TDR Trace with LeakTDR Trace with Leak DetectedDetected
  • 7. TDR Trace of System with Wet CableTDR Trace of System with Wet Cable
  • 8. TDR Trace showing Growing LeakTDR Trace showing Growing Leak
  • 9. Map 3 ResponseMap 3 Response
  • 10. Second Leak DetectedSecond Leak Detected
  • 11. Monitoring with Liquid on the CableMonitoring with Liquid on the Cable
  • 15. PAL-AT PanelsPAL-AT Panels AT20C - Monitoring up to 2,000’ (600 m) on a singleAT20C - Monitoring up to 2,000’ (600 m) on a single cablecable AT50C - Monitoring up to 5,000’ (1500 m) equivalentAT50C - Monitoring up to 5,000’ (1500 m) equivalent length on a single cablelength on a single cable AT20K - Monitoring up to 7,500’ (2500 m) equivalentAT20K - Monitoring up to 7,500’ (2500 m) equivalent length per cable with a maximum of two cableslength per cable with a maximum of two cables AT40K - Monitoring up to 5,000’ (1500m) equivalentAT40K - Monitoring up to 5,000’ (1500m) equivalent length per cable with a maximum of eight cableslength per cable with a maximum of eight cables AT80K - Monitoring up to 7,500’ (2500 m) equivalentAT80K - Monitoring up to 7,500’ (2500 m) equivalent length per cable with a maximum of eight cableslength per cable with a maximum of eight cables
  • 16. Types of CableTypes of Cable PAL-ATPAL-AT AGW Gold Sensor cable for use inAGW Gold Sensor cable for use in containment piping, trenches, trayscontainment piping, trenches, trays and subfloorsand subfloors AGT Gold Sensor cable for useAGT Gold Sensor cable for use in subfloors and trays. More sensitivein subfloors and trays. More sensitive than AGWthan AGW TFH Sensor cable for detectingTFH Sensor cable for detecting hydrocarbons and solvents while ignoringhydrocarbons and solvents while ignoring waterwater TFHTFH TFHTFH
  • 17. Types of ProbesTypes of Probes PAL-AT and LiquidWatchPAL-AT and LiquidWatch PHL/PWS Solid state probes forPHL/PWS Solid state probes for hydrocarbon and conductive liquidshydrocarbon and conductive liquids PSTV/PTHL/PFS Float switches forPSTV/PTHL/PFS Float switches for high/low levelhigh/low level PT10 (PAL-AT) Probe integrators andPT10 (PAL-AT) Probe integrators and PA-10 (LiquidWatch) Probe AdaptorsPA-10 (LiquidWatch) Probe Adaptors for dry contactsfor dry contacts
  • 18. LiquidWatchLiquidWatch LiquidWatch has two basic panels. TheLiquidWatch has two basic panels. The LW64 is for use in normal classifiedLW64 is for use in normal classified probe locations while the LW64ISprobe locations while the LW64IS provides a UL Listed System forprovides a UL Listed System for monitoring in Class 1, Division 1 Groupsmonitoring in Class 1, Division 1 Groups C & D locations. The basic panelC & D locations. The basic panel monitors up to eight probes withmonitors up to eight probes with modules being added for additionalmodules being added for additional probe requirements.probe requirements.
  • 19. ApplicationsApplications Raised Floors - Data Centers, ISPs, Clean RoomsRaised Floors - Data Centers, ISPs, Clean Rooms Telecommunication, Semiconductor, Office BldgsTelecommunication, Semiconductor, Office Bldgs PharmaceuticalPharmaceutical Piping - Containment piping, single wall piping,Piping - Containment piping, single wall piping, hydrocarbon piping, waste drainshydrocarbon piping, waste drains Trenches and Trays - Under wet benches, pipingTrenches and Trays - Under wet benches, piping and equipmentand equipment Generators, Electrical Switch Gear andGenerators, Electrical Switch Gear and Transformers for hydrocarbon leakage or waterTransformers for hydrocarbon leakage or water seepageseepage What ever needs liquid leakage detection that aWhat ever needs liquid leakage detection that a probe or sensor cable can be usedprobe or sensor cable can be used
  • 23. Palcom SoftwarePalcom Software PAL-AT and LiquidWatchPAL-AT and LiquidWatch Palcom allows remote control of up toPalcom allows remote control of up to 254 panels with the ability to review254 panels with the ability to review TDR traces, review the history of eachTDR traces, review the history of each unit and to pull down a Cad drawing forunit and to pull down a Cad drawing for each system for location of leaks,each system for location of leaks, breaks, shorts or probe activation's.breaks, shorts or probe activation's.
  • 24. Archive DataArchive Data POWER LOST AT 8985 ON 18/95 RESTORED AT 0853 ON 5/8 YEAR CHANGED FROM 29 TO 98 AT 0853 ON 5/8 CABLE 1 SETUP, WITH LENGTH OF 514 FEET AT 0921 ON 5/8 LEAK DETECTED IN CABLE 3 at 225 FEET AT 1157 ON 5/8 ALARM ON CABLE 3 SILENCED AT 1157 ON 5/8 CABLE 4 SETUP, WITH LENGTH OF 538 FEET AT 1208 ON 5/8 SECURITY CODE 1 ENTERED, LEVEL 250 AT 1210 ON 5/8 NEW CABLE 4 REFERENCE, STORED AS MAP 1 AT 1210 ON 5/8 CABLE 4 MONITORING ON, MAP 1 AT 1210 ON 5/8/98 CABLE 4 RETURNED TO NORMAL AT 1211 ON 5/8 SECURITY CODE 1 ENTERED, LEVEL 250 AT 1217 ON 5/8 CABLE 3 SETUP, WITH LENGTH OF 833 FEET AT 1217 ON 5/8 NEW CABLE 3 REFERENCE, STORED AS MAP 1 AT 1217 ON 5/8 CABLE 3 MONITORING ON, MAP 1 AT 1217 ON 5/8/98 CABLE 3 RETURNED TO NORMAL AT 1218 ON 5/8 SECURITY CODE 1 ENTERED, LEVEL 250 AT 1225 ON 5/8 CABLE 2 SETUP, WITH LENGTH OF 815 FEET AT 1225 ON 5/8 NEW CABLE 2 REFERENCE, STORED AS MAP 1 AT 1225 ON 5/8 CABLE 2 MONITORING ON, MAP 1 AT 1225 ON 5/8/98 CABLE 2 RETURNED TO NORMAL AT 1226 ON 5/8 SECURITY CODE 1 ENTERED, LEVEL 250 AT 1231 ON 5/8 CABLE 1 SETUP, WITH LENGTH OF 514 FEET AT 1231 ON 5/8 NEW CABLE 1 REFERENCE, STORED AS MAP 1 AT 1231 ON 5/8 CABLE 1 MONITORING ON, MAP 1 AT 1231 ON 5/8/98 CABLE 1 RETURNED TO NORMAL AT 1232 ON 5/8 **********End of Archives**********
  • 25. Benefits of PermAlert’s PAL-Benefits of PermAlert’s PAL- ATAT Wet cable startupWet cable startup Multiple Leak location capabilityMultiple Leak location capability Location of BreaksLocation of Breaks Detection of Shorts versus LeaksDetection of Shorts versus Leaks Not susceptible to contamination from dirt/dust, etc.Not susceptible to contamination from dirt/dust, etc. Archive History DataArchive History Data UL Listed, FM Approved, CE Approval availableUL Listed, FM Approved, CE Approval available Class 1 Div 1 Groups C & D Sensor CircuitsClass 1 Div 1 Groups C & D Sensor Circuits Up to 8 circuits and 7,500’ (2500 m) per circuitUp to 8 circuits and 7,500’ (2500 m) per circuit Corrosion resistant sensor cablesCorrosion resistant sensor cables Different cable types on the same circuitDifferent cable types on the same circuit EPA third party testedEPA third party tested
  • 26. Benefits of LiquidWatchBenefits of LiquidWatch Modular in design allowing for easyModular in design allowing for easy expansionexpansion Monitoring of probes for activation and theMonitoring of probes for activation and the leader cable for breaks and shortsleader cable for breaks and shorts History log of eventsHistory log of events UL Listed for Class 1 Div 1, Groups C & DUL Listed for Class 1 Div 1, Groups C & D locationslocations Different probe typesDifferent probe types Probe adaptor to allow interface of any dryProbe adaptor to allow interface of any dry contact probe devicecontact probe device
  • 27. Questions and Answer PeriodQuestions and Answer Period

Editor's Notes

  • #7: System is 180’ long and this trace shows the condition of a dry cable with no connector problems. Like sonar and radar the signal has to stabilize. Always install 50’ of jumper at the front and a minimum of 20’ at the back of the sensor string so we are monitoring the flat area of the graph for changes.
  • #8: Leak detected at 60’. The dielectric change between the center conductor and outer braid (liquid displacing air) causes the echo change which causes the alarm. By measuring the time to the change we can obtain the distance to the problem.
  • #9: We are now monitoring the system with the cable wet at 60’. We are looking for changes that would signify a growing leak or a new leak.
  • #10: A growing leak has occurred with more cable being wetted changing the echo signature and the PAL-AT realarms.
  • #11: Monitoring with wetted cable at 60’.
  • #12: Alarm detected at 127’ due to liquid accumulation in the cable. This leak is detected even though wetness exists on the cable at 60’.
  • #13: Monitoring with two wet locations, looking for additional changes. System can monitor effectively with 100’ of wetted cable. After that point the accuracy degrades up to 150’ wetted. After 150’ wetted the system may not monitor since our energy pulse is low voltage and may not be able to go thru the accumulated liquid.
  • #14: Break alarm detected and located on the system. The panel knows that there is supposed to be 180’ of cable but is not only sensing 129’ which causes an alarm.
  • #15: Short detected on the cable at 129’. Signature is opposite of a break and has a harmonic.
  • #16: Point sensor activated. Looks similar to a short but the end of cable still exists and no harmonic.
  • #17: Large panel selection to allow matching up to customers needs.
  • #19: Probes can also be used with LiquidWatch panel. LiquidWatch can monitor up to 64 probes.
  • #26: Example History data downloaded from PAL-AT unit.