CALPEDA TRAINING SESSION
VARIOMAT 2 
FREQUENCY 
CONVERTER
1.1 VARIOMAT 2 
TECHNICAL 
SPECIFICATION
VARIOMAT 2 specifications 
Power supply 3~400 VAC ±10% 
Mains frequency 45 Hz ÷ 65 Hz 
Current 
Variomat 2 9TT 9,0 A 
Variomat 2 12TT 12,0 A 
Variomat 2 16TT 16,0 A 
Output voltage TT 3~400 VAC 
Output frequency Up to 70 Hz 
PWM carrier frequency 12,0 kHz (random) 
Enclosure IP65 
Maximum permissible 
16 bar 
working pressure 
Ambient temperature Up to 60°C 
Fluid temperature Up to 60°C 
Mimimum delivery 1 l/min 
Altitude requirements < 1000 m above sea level (inside a room)
1.2 VARIOMAT 2 
INTERFACE
Re-start pressure 
The display allows to visualize the 
re-start pressure of the system, the 
buttons allow to change the re-start 
pressure value. 
Set-point pressure 
The display allows to visualize the set-point pressure of 
the system, the buttons allow to change the set -point 
pressure value. 
Pressure display and start/stop of the frequency converter 
The display allows to visualize the operating pressure of the system, the 
buttons allow to start and stop manually the frequency converter. 
Programming of the nominal current and absorbed current display 
The 2 digit display allows to visualize the nominal motor current (in programming mode) , 
during the operating time of the system the display visualizes the line absorbed current. The 
buttons allow to set and change the nominal motor current. 
Status indications and system reset 
The three leds give the informations about the system operativity, the first led indicates the presence of 
supply, the second led indicates if the pump is operating and the third led indicates if an alarm has 
occurred in the system. The Reset button allows to manually restart the system when an alarm occur.
2.1 VARIOMAT 2 
INSTALLATION OF A NEW SYSTEM
With VARIOMAT 2 it is very easy to create a variable speed system, hereafter 
some guidelines for new installations: 
Check that current distributed by the frequency converter is equal or 
higher than the maximum current absorbed by the electric pump. 
It is always preferable, to guarantee a higher reliability, that motors 
are realized with phase separators and double impregnation. 
If it is necessary a differential protection install a type AS differential 
switch protected against untimely activation and with threshold of 
intervention of 30 mA. 
Supply tension to the frequency converter. On the control panel will light up the 
green led "Power on" and the red led of the button . 
In all displays will appear blinking dashes for the time needed by the frequency 
converter for the set-up. 
At the end of the set-up on the displays will appear the factory value for current 
and pressure: 
- CURRENT 1.5 A 
- SET POINT PRESSURE 3.0 bar 
- RESTART PRESSURE 1.5 bar, 
The display "CURRENT" will start blinking and the yellow led will light up. 
It will be necessary to set all the value (current, set-point pressure, restart 
pressure) to the system value 
To set the value on each parameter it will be necessary to press the 
button in order to unlock the set-up 
After the value insertion press the button (green led lighted) to start the 
system.
2.2 VARIOMAT 2 
BOOSTER SETS
VARIOMAT 2 with his integrated cascade mode allows to create booster 
sets with up to 6 pumps: 
PROCEDURE: 
• Connect the supply cables to the motor. The power supply line of the 
motor must never run parallel to power line. 
• Connect the power supply of both VARIOMAT 2 to a differential switch 
type AS protected against untimely activation and with threshold of 
intervention of 30 mA. 
• By means a proper cable make the connection of wire in external clamps 
(it is possible to use the same cabinet of the differential switch). 
To comply with the standards of electromagnetic 
compatibility, for cable length greater than 1 meter, it is 
recommend the use of a shielded cable with protection sheat 
connected on the ground of both frequency converters. 
To comply with the standards of electromagnetic 
compatibility, for cable length greater than 1 meter, it is 
recommend the use of a shielded cable with protection sheat 
connected on the ground of both frequency converters. 
• Check the current value on the motor plate of the master pump. Set-up 
the current of the Master into the display press the button (green led 
lighted) to start the pump and then the button (red led lighted). 
• Repeat the procedure used for the Master frequency converter in the 
Slave frequency converter.
Press the button (yellow led switched off, 
green led lighted) to unlock the programming. 
Press the button (yellow led switched off, 
green led lighted) to unlock the programming. 
Select the Slave frequency converter (yellow led 
lighted). 
Press the button to transfer the parameters form 
the Master to the Slave (green led lighted). 
To confirm press the button a second time 
(green led lighted). 
Wait few seconds and press the button (yellow 
led lighted) to lock the programming on both 
frequency converters. 
If the communication is working the green led 
will light on both frequency converter. 
Press the button (green led lighted) on the control panel of both frequency converters to start the system.
3.1 VARIOMAT 2 
ERRORS AND 
TROUBLESHOOTING
Hereafter a list of the possible errors that can occur in the VARIOMAT 2 installation and a quick 
troubleshoot guide to check and solve 
DESCRIPTION ERROR 
CODE 
CAUSES 
The frequency converter do not switch on. -- Missing , broken fuse. 
Blockage due to overheating. E1 The frequency converter automatically rearms itself 
when the temperature fall below the safety level. 
Blockage due to low supply voltage 
or high rectified voltage. E2 The frequency converter automatically rearms itself 
when the tension come back in the admitted interval. 
Blockage due to overcurrent in the 
frequency converter. E3 The system stops and automatically re-starts 
after 1 minute for 3 times. 
Blockage due to direct short circuit 
between the phases of output terminals. E4 
Wrong three-phase motor connection. E5 Check the connections. 
Pressure transducer fault. E6 Pressure transducer spoiled. 
Blockage due to missing supply 
phase 
E7 Check the connection to the supply line and tension. 
Blockage due to no water. H1 Lack of water in the suction tank. System automatically 
restarts. 
System pressure higher than the pressure 
generated by the pump. Suction difficulties. 
H2 Check the compatibility of the system with the 
settings. Check the correct priming of the pump. 
Cascade mode communication error. C1 Check the RS 485 connection or that both pumps are 
enabled. The frequency converters which are not working are 
recognizable from the red led "Failure" blinking. The frequency
Variomat2 training

More Related Content

PDF
Calpeda control panel
PDF
SMC PTE-30-CH Digital Timer
PDF
Affinity quick start guide issue 3
PDF
85 0064-e standard-installation insert_web
PPT
Emmaandpulseox
PDF
85 0065-e deluxe-installation insert_web
Calpeda control panel
SMC PTE-30-CH Digital Timer
Affinity quick start guide issue 3
85 0064-e standard-installation insert_web
Emmaandpulseox
85 0065-e deluxe-installation insert_web

What's hot (20)

PDF
Display saune-finlandese-eng
PDF
85 0067-b5 outdoor-installation insert_web
PDF
Erbe icc-80-50-icc-service-manual
PDF
53254 0320 mach202_20_gl8_gl8000_rca-30k
PDF
APS48Z Quick Start Install.pdf
PDF
PPTX
O-Two eSeries e700 Ventilator fFunction and Operation
PDF
Termostato 24 v proporcional belimo ext-rcp-24
PDF
Manual Tecsun PL 660
PDF
Ax (1)
DOCX
Codigos de averias u (bus comunicaciones)
PDF
85 0066-e ultimate-installation insert_web
PDF
Catalog mikro mikro mu250-user_manual
PDF
Side Swing Gate Opener Installation Manual
PDF
Zmpczm022000.12.03 Operating instructions
PDF
2301 manual (v7.0 - 80384 a) (1) gefran
PDF
Rele Inia Socomec Para Produccion Animal Edif 3 Hat300 V1.3 En
PDF
Gear flow meter and roots flow meter instruction manual wiring and parameter set
PDF
Ace pump section_3
Display saune-finlandese-eng
85 0067-b5 outdoor-installation insert_web
Erbe icc-80-50-icc-service-manual
53254 0320 mach202_20_gl8_gl8000_rca-30k
APS48Z Quick Start Install.pdf
O-Two eSeries e700 Ventilator fFunction and Operation
Termostato 24 v proporcional belimo ext-rcp-24
Manual Tecsun PL 660
Ax (1)
Codigos de averias u (bus comunicaciones)
85 0066-e ultimate-installation insert_web
Catalog mikro mikro mu250-user_manual
Side Swing Gate Opener Installation Manual
Zmpczm022000.12.03 Operating instructions
2301 manual (v7.0 - 80384 a) (1) gefran
Rele Inia Socomec Para Produccion Animal Edif 3 Hat300 V1.3 En
Gear flow meter and roots flow meter instruction manual wiring and parameter set
Ace pump section_3
Ad

Similar to Variomat2 training (20)

PDF
طلمبات تعزيز الضغط GS
PPTX
Hydraulic power pack and actuator system
PDF
Korg sq 10 owners manual (users)
PDF
Tp6253trad
PPT
New microsoft power point slide
PPT
Performance checks dasibi ozone-v2
PDF
Water Temperature
PPTX
Tute 01 - Introduction to Laboratory Equipment.pptx
PDF
Diesel Fire Pump Controllers
PDF
Mikro cotroller manual
PDF
RTCC & AVR
PDF
User manual-475876
PPTX
4 MAXsa 10.pptx
DOCX
Moisture controller report total
PDF
Pressure transmitter dalian zero instrument technology co., ltd china
PDF
Neo coolcam - smart-plug user guide v2 - Zwave
PDF
Mh8 fc um
PDF
Catalog mikro mikro pfr140-user_manual
PPTX
Gsm based transformer fault detection system
PDF
Hgm400 v1.1 en
طلمبات تعزيز الضغط GS
Hydraulic power pack and actuator system
Korg sq 10 owners manual (users)
Tp6253trad
New microsoft power point slide
Performance checks dasibi ozone-v2
Water Temperature
Tute 01 - Introduction to Laboratory Equipment.pptx
Diesel Fire Pump Controllers
Mikro cotroller manual
RTCC & AVR
User manual-475876
4 MAXsa 10.pptx
Moisture controller report total
Pressure transmitter dalian zero instrument technology co., ltd china
Neo coolcam - smart-plug user guide v2 - Zwave
Mh8 fc um
Catalog mikro mikro pfr140-user_manual
Gsm based transformer fault detection system
Hgm400 v1.1 en
Ad

Recently uploaded (20)

PPTX
introduction to high performance computing
PPTX
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
PPT
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
PDF
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
PPTX
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
PPTX
Software Engineering and software moduleing
PDF
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
PDF
distributed database system" (DDBS) is often used to refer to both the distri...
PPT
Occupational Health and Safety Management System
PDF
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
PPTX
Safety Seminar civil to be ensured for safe working.
PPTX
Management Information system : MIS-e-Business Systems.pptx
PPTX
Fundamentals of Mechanical Engineering.pptx
PPTX
Current and future trends in Computer Vision.pptx
PDF
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
PDF
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
PDF
Exploratory_Data_Analysis_Fundamentals.pdf
PDF
Soil Improvement Techniques Note - Rabbi
PDF
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
PDF
737-MAX_SRG.pdf student reference guides
introduction to high performance computing
Graph Data Structures with Types, Traversals, Connectivity, and Real-Life App...
INTRODUCTION -Data Warehousing and Mining-M.Tech- VTU.ppt
BIO-INSPIRED HORMONAL MODULATION AND ADAPTIVE ORCHESTRATION IN S-AI-GPT
CURRICULAM DESIGN engineering FOR CSE 2025.pptx
Software Engineering and software moduleing
COURSE DESCRIPTOR OF SURVEYING R24 SYLLABUS
distributed database system" (DDBS) is often used to refer to both the distri...
Occupational Health and Safety Management System
PREDICTION OF DIABETES FROM ELECTRONIC HEALTH RECORDS
Safety Seminar civil to be ensured for safe working.
Management Information system : MIS-e-Business Systems.pptx
Fundamentals of Mechanical Engineering.pptx
Current and future trends in Computer Vision.pptx
UNIT no 1 INTRODUCTION TO DBMS NOTES.pdf
null (2) bgfbg bfgb bfgb fbfg bfbgf b.pdf
Exploratory_Data_Analysis_Fundamentals.pdf
Soil Improvement Techniques Note - Rabbi
Influence of Green Infrastructure on Residents’ Endorsement of the New Ecolog...
737-MAX_SRG.pdf student reference guides

Variomat2 training

  • 3. 1.1 VARIOMAT 2 TECHNICAL SPECIFICATION
  • 4. VARIOMAT 2 specifications Power supply 3~400 VAC ±10% Mains frequency 45 Hz ÷ 65 Hz Current Variomat 2 9TT 9,0 A Variomat 2 12TT 12,0 A Variomat 2 16TT 16,0 A Output voltage TT 3~400 VAC Output frequency Up to 70 Hz PWM carrier frequency 12,0 kHz (random) Enclosure IP65 Maximum permissible 16 bar working pressure Ambient temperature Up to 60°C Fluid temperature Up to 60°C Mimimum delivery 1 l/min Altitude requirements < 1000 m above sea level (inside a room)
  • 5. 1.2 VARIOMAT 2 INTERFACE
  • 6. Re-start pressure The display allows to visualize the re-start pressure of the system, the buttons allow to change the re-start pressure value. Set-point pressure The display allows to visualize the set-point pressure of the system, the buttons allow to change the set -point pressure value. Pressure display and start/stop of the frequency converter The display allows to visualize the operating pressure of the system, the buttons allow to start and stop manually the frequency converter. Programming of the nominal current and absorbed current display The 2 digit display allows to visualize the nominal motor current (in programming mode) , during the operating time of the system the display visualizes the line absorbed current. The buttons allow to set and change the nominal motor current. Status indications and system reset The three leds give the informations about the system operativity, the first led indicates the presence of supply, the second led indicates if the pump is operating and the third led indicates if an alarm has occurred in the system. The Reset button allows to manually restart the system when an alarm occur.
  • 7. 2.1 VARIOMAT 2 INSTALLATION OF A NEW SYSTEM
  • 8. With VARIOMAT 2 it is very easy to create a variable speed system, hereafter some guidelines for new installations: Check that current distributed by the frequency converter is equal or higher than the maximum current absorbed by the electric pump. It is always preferable, to guarantee a higher reliability, that motors are realized with phase separators and double impregnation. If it is necessary a differential protection install a type AS differential switch protected against untimely activation and with threshold of intervention of 30 mA. Supply tension to the frequency converter. On the control panel will light up the green led "Power on" and the red led of the button . In all displays will appear blinking dashes for the time needed by the frequency converter for the set-up. At the end of the set-up on the displays will appear the factory value for current and pressure: - CURRENT 1.5 A - SET POINT PRESSURE 3.0 bar - RESTART PRESSURE 1.5 bar, The display "CURRENT" will start blinking and the yellow led will light up. It will be necessary to set all the value (current, set-point pressure, restart pressure) to the system value To set the value on each parameter it will be necessary to press the button in order to unlock the set-up After the value insertion press the button (green led lighted) to start the system.
  • 9. 2.2 VARIOMAT 2 BOOSTER SETS
  • 10. VARIOMAT 2 with his integrated cascade mode allows to create booster sets with up to 6 pumps: PROCEDURE: • Connect the supply cables to the motor. The power supply line of the motor must never run parallel to power line. • Connect the power supply of both VARIOMAT 2 to a differential switch type AS protected against untimely activation and with threshold of intervention of 30 mA. • By means a proper cable make the connection of wire in external clamps (it is possible to use the same cabinet of the differential switch). To comply with the standards of electromagnetic compatibility, for cable length greater than 1 meter, it is recommend the use of a shielded cable with protection sheat connected on the ground of both frequency converters. To comply with the standards of electromagnetic compatibility, for cable length greater than 1 meter, it is recommend the use of a shielded cable with protection sheat connected on the ground of both frequency converters. • Check the current value on the motor plate of the master pump. Set-up the current of the Master into the display press the button (green led lighted) to start the pump and then the button (red led lighted). • Repeat the procedure used for the Master frequency converter in the Slave frequency converter.
  • 11. Press the button (yellow led switched off, green led lighted) to unlock the programming. Press the button (yellow led switched off, green led lighted) to unlock the programming. Select the Slave frequency converter (yellow led lighted). Press the button to transfer the parameters form the Master to the Slave (green led lighted). To confirm press the button a second time (green led lighted). Wait few seconds and press the button (yellow led lighted) to lock the programming on both frequency converters. If the communication is working the green led will light on both frequency converter. Press the button (green led lighted) on the control panel of both frequency converters to start the system.
  • 12. 3.1 VARIOMAT 2 ERRORS AND TROUBLESHOOTING
  • 13. Hereafter a list of the possible errors that can occur in the VARIOMAT 2 installation and a quick troubleshoot guide to check and solve DESCRIPTION ERROR CODE CAUSES The frequency converter do not switch on. -- Missing , broken fuse. Blockage due to overheating. E1 The frequency converter automatically rearms itself when the temperature fall below the safety level. Blockage due to low supply voltage or high rectified voltage. E2 The frequency converter automatically rearms itself when the tension come back in the admitted interval. Blockage due to overcurrent in the frequency converter. E3 The system stops and automatically re-starts after 1 minute for 3 times. Blockage due to direct short circuit between the phases of output terminals. E4 Wrong three-phase motor connection. E5 Check the connections. Pressure transducer fault. E6 Pressure transducer spoiled. Blockage due to missing supply phase E7 Check the connection to the supply line and tension. Blockage due to no water. H1 Lack of water in the suction tank. System automatically restarts. System pressure higher than the pressure generated by the pump. Suction difficulties. H2 Check the compatibility of the system with the settings. Check the correct priming of the pump. Cascade mode communication error. C1 Check the RS 485 connection or that both pumps are enabled. The frequency converters which are not working are recognizable from the red led "Failure" blinking. The frequency