EEP303 LAB REPORT
FAULT STUDIES
SUBMITTED BY:
Vivek Mangal (2010EE50566)
Umang Gupta (2010EE50564)
Mehul Mittal (2010EE50553)
Indra Bhushan (2010EE50548)
Srishti Mahajan (2010EE50561)
Ciddhi Jain (2010EE50011)
Aim: To carry out the following fault studies:
 To compare the severity of different types of faults.
 To observe the effect of transformer connection in fault studies
 To observe the effect of network changes on fault level (only 3 phase fault)
 To observe the effect of neutral connections in fault studies
Introduction:
Observation:
1. Comparison between severity of different types of faults
a) 3- Phase fault, Bus -5 :
Fault current = - 5.05245 j
Line 5 – 4 flow = 1.30946 j
Line 2 – 5 flow = - 3.74299 j
Zero Sequence Positive Sequence Negative Sequence Phase currents
b) SLG fault A to Gnd, Bus -5 :
Fault currents
I0 = - 1.217 j I1 = - 1.217 j I2 = - 1.217 j
Zero Sequence Positive Sequence Negative Sequence Phase currents
Line 5 – 4 flow:
Ia = 0.916 j
Ib = Ic = - 0.03 j
c) LL fault B to C, Bus -5 :
Fault current
I0 = 0 I1 = - 2.526 j I2 = 2.526 j Ic = -Ib = 4.3752
Zero Sequence Positive Sequence Negative Sequence Phase currents
Line 5 – 4 flow:
Ia = 0
Ib = 1.134
Ic = -1.134
d) LLG fault, Bus -5 :
Fault current:
I0 = 0.953 j I1 = - 3.003 j I2 = 2.050 j
Zero Sequence Positive Sequence Negative Sequence Phase currents
Ib = -4.373+1.43i
Ic = 4.373+1.43i
Line 5 – 4 flow:
Ia = 0.778 j
Ib = - 0.531 j
Ic = - 0.223 j
Observation : Severity of fault
Fault Type
Fault
Current
3- Phase 5.05245 j
SLG 0.916 j
LL 4.3752
LLG 4.373+1.43i
The order of severity of fault:
3-phase > LLG > LL > SLG
2. Effect of changes in Transformer in fault studies
All changes in Transformer 2-7
The High voltage side is kept Star-connected.
Star Grounded: 0
Star Ungrounded: 1
Delta: 2
a) 3 – phase fault on bus 5
HV LV Fault Current i(1-6) i(2-7)
0 0 -5.03245 j 2.29824 j 2.75421 j
0 1 -5.03245 j 2.29824 j 2.75421 j
0 2 -5.03245 j 2.29824 j 2.75421 j
Any change in Transformer doesn’t affect the fault current in a 3-phase fault.
b) SLG fault
HV LV Sequence
Fault
Current i(1-6) i(2-7)
0 1 Positive -1.059 j 0.482 j 0.557 j
Negative -1.059 j 0.482 j 0.557 j
Zero -1.059 j 1.059 j 0
0 0 Positive -1.314 j 0.598 j 0.716 j
Negative -1.314 j 0.598 j 0.716 j
Zero -1.314 j 0.479 j 0.835 j
0 2 Positive -1.354 j 0.616 j 0.738 j
Negative -1.354 j 0.616 j 0.738 j
Zero -1.354 j 0.388 j 0.967 j
Zero Sequence Positive Sequence Negative Sequence Phase currents
Note: The sequence diagrams for all configurations are the same.
The fault current order for connections at low voltage side:
Delta > Star-Grounded > Star-Ungrounded
HV LV
Fault
Current
Star - Grnd Star - Ungrnd 1.059 j
Star - Grnd Star - Grnd 1.314 j
Star - Grnd Delta 1.354 j
c) LLG fault
Zero Sequence Positive Sequence Negative Sequence Phase currents
HV LV Sequence
Fault
Current i(1-6) i(2-7)
0 2 Positive -3.092 j 0.191 j -0.191 j
Negative 1.960 j 1.99-0.58j 2.387-1.11j
Zero 1.132 j -1.99-0.58j -2.387-1.11j
0 1 Positive -2.912 j 1.325 j 1.588 j
Negative 2.14 j -0.974 j -1.167 j
Zero 0.772 j -0.772 j 0
0 0 Positive -3.065 j 1.394 j 1.671 j
Negative 1.988 j -0.904 j -1.084 j
Zero 1.077 j -0.393 j -0.684 j
HV LV
Fault
Current
(Ib) Phase
Star - Grnd Star – Ungrnd 4.526 165.18
Star - Grnd Star – Grnd 4.665 159.74
Star - Grnd Delta 4.693 148.79
The fault current order for connections at low voltage side:
Delta > Star-Grounded > Star-Ungrounded
Observation : Transformer connection changes
Transformer connection changes don’t affect the 3-phase fault currents.
For SLG and LLG faults, the fault current order for connections at low voltage side comes out to
be:
Delta > Star-Grounded > Star-Ungrounded
3. Effect of network changes on fault studies
3 – phase fault at bus 5
Normally fault current at bus 5 (Single phase) = - 5.05245 j
a) When Line 2-5 removed
If = -2.11375 j
I(5-4) = 2.11375 j
b) When Line 5-4 removed
If = -4.31755 j
I(2-5) = -4.31755 j
4. Effect of neutral connection
a) 3 – phase fault on bus 5
As observed in part 2 of the experiment, the fault current come out to be the same for Y-
connected LV side of the transformer with Neutral grounded / ungrounded.
b) SLG fault
HV LV
Fault
Current
Star - Ungrnd Star - Ungrnd 1.059 j
Star - Grnd Star - Ungrnd 1.059 j
Star - Grnd Star - Grnd 1.314 j
The fault current is more when the LV and HV side are both neutral-grounded as compared to
other cases.
c) LLG Fault
HV LV
Fault
Current
(Ib) Phase
Star – Ungrnd Star – Ungrnd 4.526 165.18
Star - Grnd Star – Ungrnd 4.526 165.18
Star - Grnd Star – Grnd 4.665 159.74
Observation : Effect of neutral connection
Neutral connection on one side doesn’t affect the current. The fault current increases only when both the
HV and the LV side of the transformer has their neutral grounded.

More Related Content

PDF
EEP303: Experiment 2c
PDF
EEP303: Exp 2
PDF
EEP303: Ex 5
PDF
EEP303: Exp1
PDF
EEP301: Exp5
DOCX
EEP301: Dc modular servo motor
PDF
EEP301: Transducer and instrumentation
PDF
Unsymmetrical Fault
EEP303: Experiment 2c
EEP303: Exp 2
EEP303: Ex 5
EEP303: Exp1
EEP301: Exp5
EEP301: Dc modular servo motor
EEP301: Transducer and instrumentation
Unsymmetrical Fault

What's hot (20)

PDF
Power system fault analysis ppt
PDF
EEP303: Exp5
DOC
Questions practice unit iv
DOC
Questions unit3
DOC
Solutions -unit4
PDF
Symmetrical components
PPT
Symmetrical components
DOC
Unit4questions
PDF
EEP303: Cycle ii exp 4
DOC
Questions unit4
PDF
Practice questions
PDF
EEP301: Analog control of DC motor
DOC
Unit1 and 2 sample solutions
DOC
Unit1 And 2 Sample Solutions
DOCX
EEP303: Cycle ii exp 2
DOCX
Practice questions for unit ii
DOC
Unit 1, Power system Analysis
PPT
Network Solving
PPT
Unit 103 power_point_4_resistors
PPT
Meter Shunt (Ammeter)
Power system fault analysis ppt
EEP303: Exp5
Questions practice unit iv
Questions unit3
Solutions -unit4
Symmetrical components
Symmetrical components
Unit4questions
EEP303: Cycle ii exp 4
Questions unit4
Practice questions
EEP301: Analog control of DC motor
Unit1 and 2 sample solutions
Unit1 And 2 Sample Solutions
EEP303: Cycle ii exp 2
Practice questions for unit ii
Unit 1, Power system Analysis
Network Solving
Unit 103 power_point_4_resistors
Meter Shunt (Ammeter)
Ad

Viewers also liked (20)

DOCX
EEP306: Bit error rate
PPTX
two wattmeter method
PPT
Hydro E
DOCX
Fault tree analysis semiar report
DOC
Unit 2 samplesolutions
PPTX
Power Measurement In 3-phase AC Circuits
PDF
EEL316: BER Manual
PDF
EEP301: Ca06 sample
PDF
EEP301: linear system simulator
PDF
EEL316: Noise generation histogram
PDF
EEL316: PAM TDM
DOCX
EEP301: Process control trainer II
DOCX
EEP301: linear system simulator
PDF
EEP303 Cycle ii exp-1
PDF
EEL316: ASK
PDF
EEL316: FSK
PDF
EEP306: Phase locked loop
PDF
EEL316: CDMA with DSSS
PDF
EEP306: Binary phase shift keying
PDF
EEP303: Exp4
EEP306: Bit error rate
two wattmeter method
Hydro E
Fault tree analysis semiar report
Unit 2 samplesolutions
Power Measurement In 3-phase AC Circuits
EEL316: BER Manual
EEP301: Ca06 sample
EEP301: linear system simulator
EEL316: Noise generation histogram
EEL316: PAM TDM
EEP301: Process control trainer II
EEP301: linear system simulator
EEP303 Cycle ii exp-1
EEL316: ASK
EEL316: FSK
EEP306: Phase locked loop
EEL316: CDMA with DSSS
EEP306: Binary phase shift keying
EEP303: Exp4
Ad

Similar to EEP303: Fault studies (20)

PDF
IRJET- Designing and Simulation of Five Level Three Phase Inverter with P...
PDF
Term question eee 305
PDF
Short circuit calculations
PDF
AC to AC Step Down Cycloconverter
PPT
_7UT6 Tests_en.ppt
DOCX
three phase auto loadshed phase shift system
DOC
Lab sheet
PPTX
eeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeee ppt.pptx
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PDF
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
PDF
Simulation of Three-Phase 50kw Grid Tied Inverter & analyzing its behavior at...
PDF
Line Differential - Test report for Alstom make Micom P546 relay
DOCX
Analysis and Characterization of Different Comparator Topologies
PDF
Phase-Shifted Full-Bridge Zero Voltage Switching DC-DC Converter Design with ...
PDF
Effect of voltage sag and voltage unbalance on induction motor drives
PDF
Soft Computing Technique for the Control of Triple-Lift Luo Converter
PDF
Ijirstv3i7002 170302112524
PDF
Power quality issues and challenges in RES based System
PDF
Transformerless Topology for Grid-Conected Inverters With Unipolar PWM Control
PPTX
Power electronics 2
IRJET- Designing and Simulation of Five Level Three Phase Inverter with P...
Term question eee 305
Short circuit calculations
AC to AC Step Down Cycloconverter
_7UT6 Tests_en.ppt
three phase auto loadshed phase shift system
Lab sheet
eeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeee ppt.pptx
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
Simulation of Three-Phase 50kw Grid Tied Inverter & analyzing its behavior at...
Line Differential - Test report for Alstom make Micom P546 relay
Analysis and Characterization of Different Comparator Topologies
Phase-Shifted Full-Bridge Zero Voltage Switching DC-DC Converter Design with ...
Effect of voltage sag and voltage unbalance on induction motor drives
Soft Computing Technique for the Control of Triple-Lift Luo Converter
Ijirstv3i7002 170302112524
Power quality issues and challenges in RES based System
Transformerless Topology for Grid-Conected Inverters With Unipolar PWM Control
Power electronics 2

More from Umang Gupta (9)

PDF
EEL316: Dpsk - BER & carrier acquisition
PDF
EEL316: Pseudo Random Bit Generation
PDF
EEP306: Quadrature amplitude modulation
PDF
EEP306: pulse width modulation
DOCX
EEP306: Line coding
DOCX
EEP306: Frequency modulation
DOCX
EEP306: Delta modulation
DOCX
EEP306: Amplitude modulation
DOCX
EEP301: Ac position control
EEL316: Dpsk - BER & carrier acquisition
EEL316: Pseudo Random Bit Generation
EEP306: Quadrature amplitude modulation
EEP306: pulse width modulation
EEP306: Line coding
EEP306: Frequency modulation
EEP306: Delta modulation
EEP306: Amplitude modulation
EEP301: Ac position control

Recently uploaded (20)

PPTX
Pharmacology of Heart Failure /Pharmacotherapy of CHF
PPTX
human mycosis Human fungal infections are called human mycosis..pptx
PPTX
Cell Types and Its function , kingdom of life
PDF
01-Introduction-to-Information-Management.pdf
PPTX
Institutional Correction lecture only . . .
PPTX
master seminar digital applications in india
PPTX
GDM (1) (1).pptx small presentation for students
PDF
The Lost Whites of Pakistan by Jahanzaib Mughal.pdf
PDF
Black Hat USA 2025 - Micro ICS Summit - ICS/OT Threat Landscape
PDF
RMMM.pdf make it easy to upload and study
PPTX
IMMUNITY IMMUNITY refers to protection against infection, and the immune syst...
PDF
3rd Neelam Sanjeevareddy Memorial Lecture.pdf
PPTX
Renaissance Architecture: A Journey from Faith to Humanism
PDF
Pre independence Education in Inndia.pdf
PPTX
school management -TNTEU- B.Ed., Semester II Unit 1.pptx
PDF
FourierSeries-QuestionsWithAnswers(Part-A).pdf
PDF
O5-L3 Freight Transport Ops (International) V1.pdf
PDF
BÀI TẬP BỔ TRỢ 4 KỸ NĂNG TIẾNG ANH 9 GLOBAL SUCCESS - CẢ NĂM - BÁM SÁT FORM Đ...
PDF
Basic Mud Logging Guide for educational purpose
PPTX
Lesson notes of climatology university.
Pharmacology of Heart Failure /Pharmacotherapy of CHF
human mycosis Human fungal infections are called human mycosis..pptx
Cell Types and Its function , kingdom of life
01-Introduction-to-Information-Management.pdf
Institutional Correction lecture only . . .
master seminar digital applications in india
GDM (1) (1).pptx small presentation for students
The Lost Whites of Pakistan by Jahanzaib Mughal.pdf
Black Hat USA 2025 - Micro ICS Summit - ICS/OT Threat Landscape
RMMM.pdf make it easy to upload and study
IMMUNITY IMMUNITY refers to protection against infection, and the immune syst...
3rd Neelam Sanjeevareddy Memorial Lecture.pdf
Renaissance Architecture: A Journey from Faith to Humanism
Pre independence Education in Inndia.pdf
school management -TNTEU- B.Ed., Semester II Unit 1.pptx
FourierSeries-QuestionsWithAnswers(Part-A).pdf
O5-L3 Freight Transport Ops (International) V1.pdf
BÀI TẬP BỔ TRỢ 4 KỸ NĂNG TIẾNG ANH 9 GLOBAL SUCCESS - CẢ NĂM - BÁM SÁT FORM Đ...
Basic Mud Logging Guide for educational purpose
Lesson notes of climatology university.

EEP303: Fault studies

  • 1. EEP303 LAB REPORT FAULT STUDIES SUBMITTED BY: Vivek Mangal (2010EE50566) Umang Gupta (2010EE50564) Mehul Mittal (2010EE50553) Indra Bhushan (2010EE50548) Srishti Mahajan (2010EE50561) Ciddhi Jain (2010EE50011)
  • 2. Aim: To carry out the following fault studies:  To compare the severity of different types of faults.  To observe the effect of transformer connection in fault studies  To observe the effect of network changes on fault level (only 3 phase fault)  To observe the effect of neutral connections in fault studies Introduction: Observation: 1. Comparison between severity of different types of faults a) 3- Phase fault, Bus -5 : Fault current = - 5.05245 j Line 5 – 4 flow = 1.30946 j Line 2 – 5 flow = - 3.74299 j Zero Sequence Positive Sequence Negative Sequence Phase currents
  • 3. b) SLG fault A to Gnd, Bus -5 : Fault currents I0 = - 1.217 j I1 = - 1.217 j I2 = - 1.217 j Zero Sequence Positive Sequence Negative Sequence Phase currents Line 5 – 4 flow: Ia = 0.916 j Ib = Ic = - 0.03 j c) LL fault B to C, Bus -5 : Fault current I0 = 0 I1 = - 2.526 j I2 = 2.526 j Ic = -Ib = 4.3752 Zero Sequence Positive Sequence Negative Sequence Phase currents Line 5 – 4 flow: Ia = 0 Ib = 1.134 Ic = -1.134 d) LLG fault, Bus -5 : Fault current: I0 = 0.953 j I1 = - 3.003 j I2 = 2.050 j
  • 4. Zero Sequence Positive Sequence Negative Sequence Phase currents Ib = -4.373+1.43i Ic = 4.373+1.43i Line 5 – 4 flow: Ia = 0.778 j Ib = - 0.531 j Ic = - 0.223 j Observation : Severity of fault Fault Type Fault Current 3- Phase 5.05245 j SLG 0.916 j LL 4.3752 LLG 4.373+1.43i The order of severity of fault: 3-phase > LLG > LL > SLG 2. Effect of changes in Transformer in fault studies All changes in Transformer 2-7 The High voltage side is kept Star-connected. Star Grounded: 0 Star Ungrounded: 1 Delta: 2 a) 3 – phase fault on bus 5 HV LV Fault Current i(1-6) i(2-7) 0 0 -5.03245 j 2.29824 j 2.75421 j 0 1 -5.03245 j 2.29824 j 2.75421 j 0 2 -5.03245 j 2.29824 j 2.75421 j Any change in Transformer doesn’t affect the fault current in a 3-phase fault.
  • 5. b) SLG fault HV LV Sequence Fault Current i(1-6) i(2-7) 0 1 Positive -1.059 j 0.482 j 0.557 j Negative -1.059 j 0.482 j 0.557 j Zero -1.059 j 1.059 j 0 0 0 Positive -1.314 j 0.598 j 0.716 j Negative -1.314 j 0.598 j 0.716 j Zero -1.314 j 0.479 j 0.835 j 0 2 Positive -1.354 j 0.616 j 0.738 j Negative -1.354 j 0.616 j 0.738 j Zero -1.354 j 0.388 j 0.967 j Zero Sequence Positive Sequence Negative Sequence Phase currents Note: The sequence diagrams for all configurations are the same. The fault current order for connections at low voltage side: Delta > Star-Grounded > Star-Ungrounded HV LV Fault Current Star - Grnd Star - Ungrnd 1.059 j Star - Grnd Star - Grnd 1.314 j Star - Grnd Delta 1.354 j c) LLG fault Zero Sequence Positive Sequence Negative Sequence Phase currents
  • 6. HV LV Sequence Fault Current i(1-6) i(2-7) 0 2 Positive -3.092 j 0.191 j -0.191 j Negative 1.960 j 1.99-0.58j 2.387-1.11j Zero 1.132 j -1.99-0.58j -2.387-1.11j 0 1 Positive -2.912 j 1.325 j 1.588 j Negative 2.14 j -0.974 j -1.167 j Zero 0.772 j -0.772 j 0 0 0 Positive -3.065 j 1.394 j 1.671 j Negative 1.988 j -0.904 j -1.084 j Zero 1.077 j -0.393 j -0.684 j HV LV Fault Current (Ib) Phase Star - Grnd Star – Ungrnd 4.526 165.18 Star - Grnd Star – Grnd 4.665 159.74 Star - Grnd Delta 4.693 148.79 The fault current order for connections at low voltage side: Delta > Star-Grounded > Star-Ungrounded Observation : Transformer connection changes Transformer connection changes don’t affect the 3-phase fault currents. For SLG and LLG faults, the fault current order for connections at low voltage side comes out to be: Delta > Star-Grounded > Star-Ungrounded 3. Effect of network changes on fault studies 3 – phase fault at bus 5 Normally fault current at bus 5 (Single phase) = - 5.05245 j a) When Line 2-5 removed If = -2.11375 j I(5-4) = 2.11375 j b) When Line 5-4 removed If = -4.31755 j I(2-5) = -4.31755 j
  • 7. 4. Effect of neutral connection a) 3 – phase fault on bus 5 As observed in part 2 of the experiment, the fault current come out to be the same for Y- connected LV side of the transformer with Neutral grounded / ungrounded. b) SLG fault HV LV Fault Current Star - Ungrnd Star - Ungrnd 1.059 j Star - Grnd Star - Ungrnd 1.059 j Star - Grnd Star - Grnd 1.314 j The fault current is more when the LV and HV side are both neutral-grounded as compared to other cases. c) LLG Fault HV LV Fault Current (Ib) Phase Star – Ungrnd Star – Ungrnd 4.526 165.18 Star - Grnd Star – Ungrnd 4.526 165.18 Star - Grnd Star – Grnd 4.665 159.74 Observation : Effect of neutral connection Neutral connection on one side doesn’t affect the current. The fault current increases only when both the HV and the LV side of the transformer has their neutral grounded.