This document summarizes experiments measuring the sequence impedances of transformers:
(1) A three-phase, two-winding transformer's zero sequence impedance was measured under different connection types and ranged from 0.613 to 2.227 Ohms.
(2) A three-phase, three-winding transformer's positive, negative, and zero sequence impedances were directly measured. The positive sequence impedance between the primary and secondary (Zps) was 0.475 Ohms. The positive sequence impedance between the primary and tertiary (Zpt) was 0.43 Ohms. The positive sequence impedance between the secondary and tertiary (Zst) was 0.47 Ohms.