Siemens PXC Controller Series Part-1
The PXC Compact Series operates on the Automation Level Network (ALN) or the Field Level Network (FLN).
When connected to the ALN, the PXC Compact uses a logical point firmware database to communicate directly with PXC
Modulars, MBCs, RBCs, MECs, SCUs, and other nodes on the network.
When connected to the MS/TP FLN, the PXC Compact operates as a third-party BACnet device.
When the PXC-16 or PXC-24 is connected to the P1 FLN, it operates as a P1 device.
1.No license is required when using the PXC Compact as an FLN device.
2.PXC Compact on P1 displays as a TEC with application range 3000-3899.
The PXC Compact is available with 16, 24, or 36 point terminations.
Selected PXC-24 and PXC-16 models provide an extended temperature range for the control of rooftop devices.
Optional hot-swappable HOA (Hand/Off/Auto) Modules for the PXC Compact Series enable output points to be manually
placed into HAND, ON/OFF, or AUTO control.
Compact Series Product Overview
The PXC Compact Series (Programmable Controller– Compact) is a high-performance Direct Digital Control (DDC) supervisory equipment
controller, which is an integral part of the APOGEE® Automation System.
The PXC Compact Series offers integrated I/O based on state-of-the-art TX-I/O™ Technology, which provides superior flexibility of point
and signal types, and makes it an optimal solution for Air Handling Unit (AHU) control. The PXC Compact operates stand- alone or
networked to perform complex control, monitoring, and energy management functions without relying on a higher-level processor.
The PXC Compact Series communicates with other field panels or workstations on a peer-to-peer Automation Level Network (ALN), or
on the Field Level Network (FLN), and supports the following communication options:(Ethernet/IP ALN,RS-485 P2)
The PXC Compact is available with 16, 24, or 36 point terminations. Selected models in the Compact Series provide the following
options:
Support for FLN devices.
An extended temperature range for the control of rooftop devices.
Support for Island Bus, which uses TX-I/O modules to expand the number of point terminations for high-speed loop control. For PXC- 36
only.
Compact Series Product Overview
Features
DIN rail mounted device with removable terminal blocks simplifies
installation and servicing.
Proven program sequences to match equipment control applications.
Built-in energy management applications and DDC programs for complete
facility management.
Comprehensive alarm management, historical data trend collection,
operator control, and monitoring functions.
Sophisticated Adaptive Control, a closed loop control algorithm that auto-
adjusts to compensate for load/seasonal changes (License required with
Firmware revision 2.8.18 and higher).
Message control for terminals, printers, pagers, and workstations.
Highly configurable I/O using Siemens state-of- the-art TX-I/O™ Technology.
HMI RS-232 port, which provides laptop connectivity for local operation
and engineering.
Features
Extended battery backup of Real Time Clock.
Persistent database backup and restore within the controller.
Optional HOA (Hand/Off/Auto) module for swappable and configurable HOA
capability.
Optional extended temperature range for rooftop installation.
Optional peer-to-peer communications over industry-standard 10Base-T/100Base-TX
Ethernet networks.
Optional support for FLN devices.
Optional support for P1 Wireless FLN.
Optional operation as a P1 FLN device with default applications.
Optional support for Virtual AEM.
The Compact Series
In addition to building and system management functions, the Compact Series includes several styles of controllers that
flexibly meet application needs.
PXC-16
The PXC-16 provides control of 16 points, including 8 software-configurable universal points.
Point count includes: 3 Universal Input (UI), 5 Universal I/O (U), 2 Digital Input (DI), 3 Analog Output (AOV), and 3 Digital
Output (DO).
PXC-24
The PXC-24 provides control of 24 points, including 16 software-configurable universal points.
Point count includes: 3 Universal Input (UI), 9 Universal I/O (U), 4 Super Universal I/O (X), 3 Analog Output (AOV), 5 Digital
Output (DO).
PXC-36
The PXC-36 provides control of 36 local points, including 24 software-configurable universal points.
Point count includes: 18 Universal I/O (U), 6 Super Universal I/O (X), 4 Digital Input (DI), and 8 Digital Output (DO).
The PXC-36 offers the flexibility of expanding the total point count through a self-forming Island Bus. With the addition of a
TX-I/O Power Supply, up to four TX-I/O modules can be supported. For more information, see the TX-I/O Product Range
Technical Specification Sheet (149-476).
Ethernet or RS-485 ALN • Support for APOGEE P2 ALN through TCP/IP or RS-485
networks.
FLN Support ● The PXC-16 and PXC-24 “F” models with an FLN license
support up to 32 P1 FLN devices when the ALN is
connected to TCP/IP.
● The PXC-36 with an FLN license supports up to 96 P1 FLN
devices when the ALN is connected to
RS-485 or TCP/IP.
● A Wireless FLN may also be used to replace the
traditional P1 FLN cabling with wireless communication
links that form a wireless mesh network. Additional
hardware is required to implement the Wireless FLN.
P1 FLN Operation The PXC-16 and PXC-24 can be configured as a programmable
P1 FLN device. In the P1 FLN mode, the PXC Compact
functions as an equipment controller with customized
programming and default applications.
Available Options
Virtual AEM Support • The Virtual AEM license allows the PXC Compact to connect
an RS-485 APOGEE Automation Level Network or individual
field panels to a P2 Ethernet network without additional
hardware.
Extended Temperature
Operation
• PXC-24 "R" models support extended temperature
operation, allowing for rooftop installations.
Field Panel GO The PXC-36 supports Field Panel GO.
The Field Panel GO license provides a Web-based user
interface for your APOGEE® Building Automation System. It is
an ideal solution for small or remote facilities with field
panels on an Ethernet TCP/IP Automation Level Network
(ALN).
Available Options
PXC Compact Series
PXC16.2-P.A PXC Compact, 16 point, RS-485 ALN
PXC16.2-PE.A PXC Compact, 16 point, Ethernet/IP ALN
PXC24.2-P.A PXC Compact, 24 point, RS-485 ALN
PXC24.2-PE.A PXC Compact, 24 point, Ethernet/IP ALN
PXC24.2-PEF.A PXC Compact, 24 point, Ethernet/IP or RS-485 ALN, P1 FLN or Remote
Ethernet/IP (Virtual AEM) option
PXC24.2-PEF32.A PXC Compact, 24 point, Ethernet/IP, P1 FLN enabled
PXC24.2-PR.A PXC Compact, 24 point, RS-485 ALN, rooftop
PXC24.2-PER.A PXC Compact, 24 point, Ethernet/IP ALN, rooftop
PXC24.2-PERF.A PXC Compact, 24 point, Ethernet/IP or RS-485 ALN, rooftop, P1 FLN or
Remote Ethernet/IP (Virtual AEM) option
PXC36-PE.A PXC Compact, 36 point, Ethernet/IP or RS-485 ALN
PXC36-PEF.A
PXC
PXC Compact, 36 point, Ethernet/IP or RS-485 ALN, Island Bus, P1 FLN
PXC 12D,12ED,22D,22ED,36ED ect
Memory Size and Typical Battery Backup Time
Memory Size and Typical Battery Backup Time.
Compact Model RAM Flash ROM Total Memory Typical Battery Backup
RAM and Real Time Clock
Data1
PXC-16 and PXC-
24
16 MB 8 MB 24 MB Non-rooftop models: 180
days (accumulated)
Rooftop models: 330
days (accumulated)
PXC-16 and PXC-
24 “F” and
“F32”
32 MB 8 MB 40 MB Non-rooftop models
(accumulated): 110 days
(accumulated)
Rooftop models:
(accumulated): 200 days
(accumulated)
PXC-36 64 MB 16 MB 80 MB 60 days (accumulated)
Technical data
Power Requirements • Operating voltage
• Power Consumption (Maximum)
• AC Power and Digital Outputs
• Communication and all other I/O
• 24 Vac ±20% input @ 50/60 Hz
PXC-16: 18 VA @ 24 Vac
PXC-24: 20 VA @ 24 Vac
PXC-36: 35 VA 24 Vac
NEC Class 1 Power Limited
NEC Class 2
Dimensions (L × W × D) • PXC-16 and PXC-24
• PXC-36
10.7" × 5.9" × 2.45" (272 mm × 150 mm × 62
mm)
11.5" × 5.9" × 3.0" (293 mm × 150 mm × 77
mm)
Technical data
Digital Input Dedicated Points
• PXC-16: Points 12-13
• PXC-36: Points 25-28
Contact Closure Sensing Dry Contact/Potential
Free inputs only Does not support counter inputs
Open Circuit Voltage: 24 Vdc
Short Circuit Current: 10 mA
Configurable Points
• PXC-16: Points 1-8
• PXC-24: Points 1-16
• PXC-36: Points 1-24
Contact Closure Sensing Dry
Contact/Potential Free inputs only Digital
Input (10 ms settling time)
Supports counter inputs up to 20 Hz,
minimum
pulse duration 20 ms (open or closed
Digital Output Dedicated Points
• PXC-16: Points 14-16
• PXC-24: Points 20-24
• PXC-36: Points 29-36
Class 1 Relay Form-C (NO and NC contacts)
125 Vac, 4A
250 Vac, 2A
Configurable Points using an external
relay
• PXC-24: Points 13-16
• PXC-36: Points 1-6
0 to 24 Vdc, 22 mA max.
Technical data
Analog Output PXC-16: Points 9-11
PXC-24: Points 17-19
0 to 10 Vdc @ 1 mA max.
Resolution:
11 mV Initial Accuracy: ±2% of full range
(32°F to 122°F
(0°C to 50°C) ambient)
Configurable Points, 0 to 10 Vdc
PXC-16: Points 4-8
PXC-24: Points 4-16
PXC-36: Points 1-24
0 to 10 Vdc @ 1 mA max.
Resolution:
11 mV Initial Accuracy: ±2% of full range
(32°F to 122°F
(0°C to 50°C) ambient)
Configurable Points, 0 to 20 mA
PXC-24: Points 13-16
PXC-36: Points 1-6
0 to 20 mA @ 650 Ω max.
Resolution:
22 µA Initial Accuracy: ±2% of full range
(32°F to 122°F
(0°C to 50°C) ambient
Technical data
Analog Input Configurable Points
PXC-16: Points 1-8
PXC-24: Points 1-16
PXC-36: Points 1-24
Voltage (0-10 Vdc) Resolution: 2.2 mV
Current (4-20 mA) Resolution: 4.4 µA 1K Ni RTD @ 32°F (Siemens, JCI, DIN Ni 1K)
Resolution: 0.05 C 1K Pt RTD (375 or 385 alpha) @ 32°F
Resolution: 0.08 C (375), 0.13 C (385) 10K NTC Type 2 or Type 3 Thermistor
Resolution: 0.02 C to 0.10 C100K NTC Type 2 Thermistor
Resolution: 0.14 C to 0.02 C
Operating Environment
Ambient operating temperature 32°F to 122°F (0°C to 50°C)
Ambient operating temperature
with rooftop (extended
temperature) option
-40°F to 158°F (-40°C to 70°C)
Relative Humidity PXC-16 and PXC-24: 5 to 95% rh non-condensing
PXC-36: 5 to 95% rh non-condensing
Mounting Surface PXC-16 and PXC-24: Direct equipment mount, building wall,
or structural member
PXC-36: Building wall or a secure structure
Technical data
Processor and Clock
Speed
• PXC-16 and PXC-24: Freescale MPC852T, 100 MHz
• PXC-36: Freescale MPC885, 133 MHz
Memory
• PXC-16 and PXC-24: 24 MB (16 MB SDRAM, 8 MB Flash ROM)
• PXC-16/24 “F” and “F32”: 40 MB (32 MB SDRAM, 8 MB Flash
ROM)
• PXC-36: 80 MB (64 MB SDRAM, 16 MB Flash ROM)
Battery backup of
Synchronous Dynamic
(SD)
RAM (field replaceable)
• Non-rooftop Models: AA (LR6) 1.5 Volt Alkaline (non-rechargeable)
• PXC-16 and PXC-24: 180 days (accumulated)
• PXC-36: 60 days (accumulated)
• Rooftop (Extended Temperature) Models: AA (LR6) 3.6 Volt Lithium (non-
rechargeable)
• 330 days (accumulated)
Battery backup of Real
Time Clock
• Non-rooftop Models: 10 years
• Rooftop (Extended Temperature) Models: 18 months
Processor, Battery, and Memory
A/D Resolution (analog in) 16 bits
/A Resolution (analog out) 10 bits
Ethernet/IP Automation Level Network
(ALN)
10Base-T or 100Base-TX compliant
RS-485 Automation Level Network
(ALN)
1200 bps to 115.2 Kbps
RS-485 P1 Field Level Network (FLN)
on selected models, license required
4800 bps to 38.4 Kbps
Human-Machine Interface (HMI)
Advanced User Mode
RS-232 compliant, 1200 bps to 115.2 Kbps
USB Device port (for non-smoke
control applications only)
Prior to June 2013
USB 1.1 (12 Mbps) and 2.0 (480 Mbps), Type B female
connector. Self-powered, does not use or supply USB power.
USB 1.0 (1.5 Mbps) and 1.1 (12 Mbps).
USB Host port on selected models
(for ancillary smoke control
applications only).
Prior to June 2013
USB 1.0 (1.5 Mbps), 1.1 (12 Mbps), and 2.0 (480Mbps), Type A female
connector.
USB unit loads (5V, 500 mA).
USB 1.0 (1.5 Mbps) and 1.1 (12 Mbps), Type A female connector.
Communication
OUR PROJECT’S

More Related Content

PPTX
Siemens PXC Controller Series Part-2
PPT
ITC 16 Zone Voice Evacuation & PA Sound System
PPTX
Honeywell PLC ML-200R Communcation & Networking
PPTX
Communication protocols
PDF
Distributed Control System Basics
PPT
Asi presentation 08
PPTX
YOKOGAWA CENTUM CS 3000 R3
PPTX
PLC Brief
Siemens PXC Controller Series Part-2
ITC 16 Zone Voice Evacuation & PA Sound System
Honeywell PLC ML-200R Communcation & Networking
Communication protocols
Distributed Control System Basics
Asi presentation 08
YOKOGAWA CENTUM CS 3000 R3
PLC Brief

What's hot (20)

PPTX
Communication Protocols
PPTX
Communication protocols
PPTX
Siemens Desigo part 1
PDF
PLC data types and addressing
PDF
SCADA PPT.pdf
PPS
day 3: Control Concepts & BMS
PPTX
DCS an overview
PPT
DCS PRESENTATION
PPT
CENTUM CS300 R3
PPT
Ip network audio system for office
PPTX
Basics of Automation, PLC and SCADA
PPTX
DCS - Distributed Control System
PPT
Modbus Data Communication Systems
PDF
Fieldbus Tutorial Part 1 - Fieldbus Overview
PPTX
Hart Protocol Introduction
PPTX
Yokogawa Centum-VP-Engneering-Course.pptx
PPT
Delta v advanced control overview_en
PPTX
Honeywell PLC TRAINING GUIDE created by deepak gorai
PPTX
SIEMENS PXG3.L BACnet/IP Router
Communication Protocols
Communication protocols
Siemens Desigo part 1
PLC data types and addressing
SCADA PPT.pdf
day 3: Control Concepts & BMS
DCS an overview
DCS PRESENTATION
CENTUM CS300 R3
Ip network audio system for office
Basics of Automation, PLC and SCADA
DCS - Distributed Control System
Modbus Data Communication Systems
Fieldbus Tutorial Part 1 - Fieldbus Overview
Hart Protocol Introduction
Yokogawa Centum-VP-Engneering-Course.pptx
Delta v advanced control overview_en
Honeywell PLC TRAINING GUIDE created by deepak gorai
SIEMENS PXG3.L BACnet/IP Router
Ad

Similar to Siemens PXC Controller Series Part-1 (20)

PPTX
Siemens Automation Station Compact Model PXC52
PPTX
Allenbradley Control Logix PLC Network Architecture
PDF
Ds bac 1xxxxx-91403501_e
PDF
1.Siemens Desigo PX Controller Overview.pdf
PDF
Ms 9200 udls(e)
PPT
03 Mcu Day 2009 (C2000) 8 13 Editado
PPT
Wireless agro automation system
PPT
Data Acquisition PCU400 Network Manager rel1.ppt
PDF
SISTEMA DE CONTROL MICRONET PLUS PARA TURBINAS TM2500
PDF
Sync2IP 2 Port and 4 Port Sync to LAN Adapter
PDF
Peek Traffic Controller PTC 1
PDF
ES-200X Ficha técnica.pdf
PPTX
FAR/MARS Avionics CDR
PDF
cisco-n9k-c92160yc-x-datasheet.pdf
PDF
Rapid control prototyping system for power electronics
PPTX
RFID Based Toll Gate System
PDF
Cps fire safety
PDF
Keletron KNX PL110-132 energy manager presales
PDF
Catalog PLC Mitsubishi Fx 3G 60MR
PDF
Brochure bac 5801-02-sb-003_c
Siemens Automation Station Compact Model PXC52
Allenbradley Control Logix PLC Network Architecture
Ds bac 1xxxxx-91403501_e
1.Siemens Desigo PX Controller Overview.pdf
Ms 9200 udls(e)
03 Mcu Day 2009 (C2000) 8 13 Editado
Wireless agro automation system
Data Acquisition PCU400 Network Manager rel1.ppt
SISTEMA DE CONTROL MICRONET PLUS PARA TURBINAS TM2500
Sync2IP 2 Port and 4 Port Sync to LAN Adapter
Peek Traffic Controller PTC 1
ES-200X Ficha técnica.pdf
FAR/MARS Avionics CDR
cisco-n9k-c92160yc-x-datasheet.pdf
Rapid control prototyping system for power electronics
RFID Based Toll Gate System
Cps fire safety
Keletron KNX PL110-132 energy manager presales
Catalog PLC Mitsubishi Fx 3G 60MR
Brochure bac 5801-02-sb-003_c
Ad

More from CONTROLS & SYSTEMS (19)

PPTX
Siemens synco 700 controller commissioning communication part 2
PPTX
Synco tm 700 controller operation and commissioning part 1
PPTX
Siemens Compact Room Automation Stations
PPTX
Siemens Differential pressure sensor qbm4000
PPTX
SIEMENS RWD CONTROLLER SERIES
PPTX
Siemens Terminal Box Controller (APOGEE Automation System )
PPTX
Siemens Web interface PXG 3.W100
PPTX
Siemens Air velocity sensor
PPTX
Siemens MICRO VFD part 1
PPTX
Siemens Zone Valve & Actuators
PPTX
Siemens Touch Panel (PXM40) Display
PPTX
SIEMENS HMI PXM10 DISPLAY
PPTX
Siemens GBB/GIB Rotary Actuator Installation Instructions
PPTX
Siemens BACnet Actuating Terminal Equipment Controller (ATEC) Installation In...
PPTX
Air Damper Actuators siemens
PPTX
Air Damper Actuators GSD
PPTX
Fire safety solutions for clean rooms.
PPTX
Siemens Duct sensor
PPTX
Control system
Siemens synco 700 controller commissioning communication part 2
Synco tm 700 controller operation and commissioning part 1
Siemens Compact Room Automation Stations
Siemens Differential pressure sensor qbm4000
SIEMENS RWD CONTROLLER SERIES
Siemens Terminal Box Controller (APOGEE Automation System )
Siemens Web interface PXG 3.W100
Siemens Air velocity sensor
Siemens MICRO VFD part 1
Siemens Zone Valve & Actuators
Siemens Touch Panel (PXM40) Display
SIEMENS HMI PXM10 DISPLAY
Siemens GBB/GIB Rotary Actuator Installation Instructions
Siemens BACnet Actuating Terminal Equipment Controller (ATEC) Installation In...
Air Damper Actuators siemens
Air Damper Actuators GSD
Fire safety solutions for clean rooms.
Siemens Duct sensor
Control system

Recently uploaded (20)

PPTX
Construction Project Organization Group 2.pptx
PPTX
additive manufacturing of ss316l using mig welding
DOCX
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
PDF
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
PDF
Well-logging-methods_new................
PPTX
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
PDF
composite construction of structures.pdf
PPTX
Internet of Things (IOT) - A guide to understanding
DOCX
573137875-Attendance-Management-System-original
PPTX
OOP with Java - Java Introduction (Basics)
PPTX
CH1 Production IntroductoryConcepts.pptx
PPTX
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
PDF
R24 SURVEYING LAB MANUAL for civil enggi
PPTX
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
PPTX
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
PDF
Model Code of Practice - Construction Work - 21102022 .pdf
PPTX
Sustainable Sites - Green Building Construction
PDF
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
PDF
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
PDF
Digital Logic Computer Design lecture notes
Construction Project Organization Group 2.pptx
additive manufacturing of ss316l using mig welding
ASol_English-Language-Literature-Set-1-27-02-2023-converted.docx
TFEC-4-2020-Design-Guide-for-Timber-Roof-Trusses.pdf
Well-logging-methods_new................
CARTOGRAPHY AND GEOINFORMATION VISUALIZATION chapter1 NPTE (2).pptx
composite construction of structures.pdf
Internet of Things (IOT) - A guide to understanding
573137875-Attendance-Management-System-original
OOP with Java - Java Introduction (Basics)
CH1 Production IntroductoryConcepts.pptx
IOT PPTs Week 10 Lecture Material.pptx of NPTEL Smart Cities contd
R24 SURVEYING LAB MANUAL for civil enggi
FINAL REVIEW FOR COPD DIANOSIS FOR PULMONARY DISEASE.pptx
Engineering Ethics, Safety and Environment [Autosaved] (1).pptx
Model Code of Practice - Construction Work - 21102022 .pdf
Sustainable Sites - Green Building Construction
The CXO Playbook 2025 – Future-Ready Strategies for C-Suite Leaders Cerebrai...
Mitigating Risks through Effective Management for Enhancing Organizational Pe...
Digital Logic Computer Design lecture notes

Siemens PXC Controller Series Part-1

  • 1. Siemens PXC Controller Series Part-1
  • 2. The PXC Compact Series operates on the Automation Level Network (ALN) or the Field Level Network (FLN). When connected to the ALN, the PXC Compact uses a logical point firmware database to communicate directly with PXC Modulars, MBCs, RBCs, MECs, SCUs, and other nodes on the network. When connected to the MS/TP FLN, the PXC Compact operates as a third-party BACnet device. When the PXC-16 or PXC-24 is connected to the P1 FLN, it operates as a P1 device. 1.No license is required when using the PXC Compact as an FLN device. 2.PXC Compact on P1 displays as a TEC with application range 3000-3899. The PXC Compact is available with 16, 24, or 36 point terminations. Selected PXC-24 and PXC-16 models provide an extended temperature range for the control of rooftop devices. Optional hot-swappable HOA (Hand/Off/Auto) Modules for the PXC Compact Series enable output points to be manually placed into HAND, ON/OFF, or AUTO control. Compact Series Product Overview
  • 3. The PXC Compact Series (Programmable Controller– Compact) is a high-performance Direct Digital Control (DDC) supervisory equipment controller, which is an integral part of the APOGEE® Automation System. The PXC Compact Series offers integrated I/O based on state-of-the-art TX-I/O™ Technology, which provides superior flexibility of point and signal types, and makes it an optimal solution for Air Handling Unit (AHU) control. The PXC Compact operates stand- alone or networked to perform complex control, monitoring, and energy management functions without relying on a higher-level processor. The PXC Compact Series communicates with other field panels or workstations on a peer-to-peer Automation Level Network (ALN), or on the Field Level Network (FLN), and supports the following communication options:(Ethernet/IP ALN,RS-485 P2) The PXC Compact is available with 16, 24, or 36 point terminations. Selected models in the Compact Series provide the following options: Support for FLN devices. An extended temperature range for the control of rooftop devices. Support for Island Bus, which uses TX-I/O modules to expand the number of point terminations for high-speed loop control. For PXC- 36 only. Compact Series Product Overview
  • 4. Features DIN rail mounted device with removable terminal blocks simplifies installation and servicing. Proven program sequences to match equipment control applications. Built-in energy management applications and DDC programs for complete facility management. Comprehensive alarm management, historical data trend collection, operator control, and monitoring functions. Sophisticated Adaptive Control, a closed loop control algorithm that auto- adjusts to compensate for load/seasonal changes (License required with Firmware revision 2.8.18 and higher). Message control for terminals, printers, pagers, and workstations. Highly configurable I/O using Siemens state-of- the-art TX-I/O™ Technology. HMI RS-232 port, which provides laptop connectivity for local operation and engineering.
  • 5. Features Extended battery backup of Real Time Clock. Persistent database backup and restore within the controller. Optional HOA (Hand/Off/Auto) module for swappable and configurable HOA capability. Optional extended temperature range for rooftop installation. Optional peer-to-peer communications over industry-standard 10Base-T/100Base-TX Ethernet networks. Optional support for FLN devices. Optional support for P1 Wireless FLN. Optional operation as a P1 FLN device with default applications. Optional support for Virtual AEM.
  • 6. The Compact Series In addition to building and system management functions, the Compact Series includes several styles of controllers that flexibly meet application needs. PXC-16 The PXC-16 provides control of 16 points, including 8 software-configurable universal points. Point count includes: 3 Universal Input (UI), 5 Universal I/O (U), 2 Digital Input (DI), 3 Analog Output (AOV), and 3 Digital Output (DO). PXC-24 The PXC-24 provides control of 24 points, including 16 software-configurable universal points. Point count includes: 3 Universal Input (UI), 9 Universal I/O (U), 4 Super Universal I/O (X), 3 Analog Output (AOV), 5 Digital Output (DO). PXC-36 The PXC-36 provides control of 36 local points, including 24 software-configurable universal points. Point count includes: 18 Universal I/O (U), 6 Super Universal I/O (X), 4 Digital Input (DI), and 8 Digital Output (DO). The PXC-36 offers the flexibility of expanding the total point count through a self-forming Island Bus. With the addition of a TX-I/O Power Supply, up to four TX-I/O modules can be supported. For more information, see the TX-I/O Product Range Technical Specification Sheet (149-476).
  • 7. Ethernet or RS-485 ALN • Support for APOGEE P2 ALN through TCP/IP or RS-485 networks. FLN Support ● The PXC-16 and PXC-24 “F” models with an FLN license support up to 32 P1 FLN devices when the ALN is connected to TCP/IP. ● The PXC-36 with an FLN license supports up to 96 P1 FLN devices when the ALN is connected to RS-485 or TCP/IP. ● A Wireless FLN may also be used to replace the traditional P1 FLN cabling with wireless communication links that form a wireless mesh network. Additional hardware is required to implement the Wireless FLN. P1 FLN Operation The PXC-16 and PXC-24 can be configured as a programmable P1 FLN device. In the P1 FLN mode, the PXC Compact functions as an equipment controller with customized programming and default applications. Available Options
  • 8. Virtual AEM Support • The Virtual AEM license allows the PXC Compact to connect an RS-485 APOGEE Automation Level Network or individual field panels to a P2 Ethernet network without additional hardware. Extended Temperature Operation • PXC-24 "R" models support extended temperature operation, allowing for rooftop installations. Field Panel GO The PXC-36 supports Field Panel GO. The Field Panel GO license provides a Web-based user interface for your APOGEE® Building Automation System. It is an ideal solution for small or remote facilities with field panels on an Ethernet TCP/IP Automation Level Network (ALN). Available Options
  • 9. PXC Compact Series PXC16.2-P.A PXC Compact, 16 point, RS-485 ALN PXC16.2-PE.A PXC Compact, 16 point, Ethernet/IP ALN PXC24.2-P.A PXC Compact, 24 point, RS-485 ALN PXC24.2-PE.A PXC Compact, 24 point, Ethernet/IP ALN PXC24.2-PEF.A PXC Compact, 24 point, Ethernet/IP or RS-485 ALN, P1 FLN or Remote Ethernet/IP (Virtual AEM) option PXC24.2-PEF32.A PXC Compact, 24 point, Ethernet/IP, P1 FLN enabled PXC24.2-PR.A PXC Compact, 24 point, RS-485 ALN, rooftop PXC24.2-PER.A PXC Compact, 24 point, Ethernet/IP ALN, rooftop PXC24.2-PERF.A PXC Compact, 24 point, Ethernet/IP or RS-485 ALN, rooftop, P1 FLN or Remote Ethernet/IP (Virtual AEM) option PXC36-PE.A PXC Compact, 36 point, Ethernet/IP or RS-485 ALN PXC36-PEF.A PXC PXC Compact, 36 point, Ethernet/IP or RS-485 ALN, Island Bus, P1 FLN PXC 12D,12ED,22D,22ED,36ED ect
  • 10. Memory Size and Typical Battery Backup Time Memory Size and Typical Battery Backup Time. Compact Model RAM Flash ROM Total Memory Typical Battery Backup RAM and Real Time Clock Data1 PXC-16 and PXC- 24 16 MB 8 MB 24 MB Non-rooftop models: 180 days (accumulated) Rooftop models: 330 days (accumulated) PXC-16 and PXC- 24 “F” and “F32” 32 MB 8 MB 40 MB Non-rooftop models (accumulated): 110 days (accumulated) Rooftop models: (accumulated): 200 days (accumulated) PXC-36 64 MB 16 MB 80 MB 60 days (accumulated)
  • 11. Technical data Power Requirements • Operating voltage • Power Consumption (Maximum) • AC Power and Digital Outputs • Communication and all other I/O • 24 Vac ±20% input @ 50/60 Hz PXC-16: 18 VA @ 24 Vac PXC-24: 20 VA @ 24 Vac PXC-36: 35 VA 24 Vac NEC Class 1 Power Limited NEC Class 2 Dimensions (L × W × D) • PXC-16 and PXC-24 • PXC-36 10.7" × 5.9" × 2.45" (272 mm × 150 mm × 62 mm) 11.5" × 5.9" × 3.0" (293 mm × 150 mm × 77 mm)
  • 12. Technical data Digital Input Dedicated Points • PXC-16: Points 12-13 • PXC-36: Points 25-28 Contact Closure Sensing Dry Contact/Potential Free inputs only Does not support counter inputs Open Circuit Voltage: 24 Vdc Short Circuit Current: 10 mA Configurable Points • PXC-16: Points 1-8 • PXC-24: Points 1-16 • PXC-36: Points 1-24 Contact Closure Sensing Dry Contact/Potential Free inputs only Digital Input (10 ms settling time) Supports counter inputs up to 20 Hz, minimum pulse duration 20 ms (open or closed Digital Output Dedicated Points • PXC-16: Points 14-16 • PXC-24: Points 20-24 • PXC-36: Points 29-36 Class 1 Relay Form-C (NO and NC contacts) 125 Vac, 4A 250 Vac, 2A Configurable Points using an external relay • PXC-24: Points 13-16 • PXC-36: Points 1-6 0 to 24 Vdc, 22 mA max.
  • 13. Technical data Analog Output PXC-16: Points 9-11 PXC-24: Points 17-19 0 to 10 Vdc @ 1 mA max. Resolution: 11 mV Initial Accuracy: ±2% of full range (32°F to 122°F (0°C to 50°C) ambient) Configurable Points, 0 to 10 Vdc PXC-16: Points 4-8 PXC-24: Points 4-16 PXC-36: Points 1-24 0 to 10 Vdc @ 1 mA max. Resolution: 11 mV Initial Accuracy: ±2% of full range (32°F to 122°F (0°C to 50°C) ambient) Configurable Points, 0 to 20 mA PXC-24: Points 13-16 PXC-36: Points 1-6 0 to 20 mA @ 650 Ω max. Resolution: 22 µA Initial Accuracy: ±2% of full range (32°F to 122°F (0°C to 50°C) ambient
  • 14. Technical data Analog Input Configurable Points PXC-16: Points 1-8 PXC-24: Points 1-16 PXC-36: Points 1-24 Voltage (0-10 Vdc) Resolution: 2.2 mV Current (4-20 mA) Resolution: 4.4 µA 1K Ni RTD @ 32°F (Siemens, JCI, DIN Ni 1K) Resolution: 0.05 C 1K Pt RTD (375 or 385 alpha) @ 32°F Resolution: 0.08 C (375), 0.13 C (385) 10K NTC Type 2 or Type 3 Thermistor Resolution: 0.02 C to 0.10 C100K NTC Type 2 Thermistor Resolution: 0.14 C to 0.02 C
  • 15. Operating Environment Ambient operating temperature 32°F to 122°F (0°C to 50°C) Ambient operating temperature with rooftop (extended temperature) option -40°F to 158°F (-40°C to 70°C) Relative Humidity PXC-16 and PXC-24: 5 to 95% rh non-condensing PXC-36: 5 to 95% rh non-condensing Mounting Surface PXC-16 and PXC-24: Direct equipment mount, building wall, or structural member PXC-36: Building wall or a secure structure Technical data
  • 16. Processor and Clock Speed • PXC-16 and PXC-24: Freescale MPC852T, 100 MHz • PXC-36: Freescale MPC885, 133 MHz Memory • PXC-16 and PXC-24: 24 MB (16 MB SDRAM, 8 MB Flash ROM) • PXC-16/24 “F” and “F32”: 40 MB (32 MB SDRAM, 8 MB Flash ROM) • PXC-36: 80 MB (64 MB SDRAM, 16 MB Flash ROM) Battery backup of Synchronous Dynamic (SD) RAM (field replaceable) • Non-rooftop Models: AA (LR6) 1.5 Volt Alkaline (non-rechargeable) • PXC-16 and PXC-24: 180 days (accumulated) • PXC-36: 60 days (accumulated) • Rooftop (Extended Temperature) Models: AA (LR6) 3.6 Volt Lithium (non- rechargeable) • 330 days (accumulated) Battery backup of Real Time Clock • Non-rooftop Models: 10 years • Rooftop (Extended Temperature) Models: 18 months Processor, Battery, and Memory
  • 17. A/D Resolution (analog in) 16 bits /A Resolution (analog out) 10 bits Ethernet/IP Automation Level Network (ALN) 10Base-T or 100Base-TX compliant RS-485 Automation Level Network (ALN) 1200 bps to 115.2 Kbps RS-485 P1 Field Level Network (FLN) on selected models, license required 4800 bps to 38.4 Kbps Human-Machine Interface (HMI) Advanced User Mode RS-232 compliant, 1200 bps to 115.2 Kbps USB Device port (for non-smoke control applications only) Prior to June 2013 USB 1.1 (12 Mbps) and 2.0 (480 Mbps), Type B female connector. Self-powered, does not use or supply USB power. USB 1.0 (1.5 Mbps) and 1.1 (12 Mbps). USB Host port on selected models (for ancillary smoke control applications only). Prior to June 2013 USB 1.0 (1.5 Mbps), 1.1 (12 Mbps), and 2.0 (480Mbps), Type A female connector. USB unit loads (5V, 500 mA). USB 1.0 (1.5 Mbps) and 1.1 (12 Mbps), Type A female connector. Communication