The document provides calculations and analysis for lighting and acoustic design of two spaces - a quiet reading area and young adult area - within the Sentul Community Library.
For the quiet reading area on the second floor: Daylight factor is calculated at 4.9% providing good lighting. Artificial lighting calculation determines 25 fluorescent lamps are needed to achieve 300 lux. Permanent supplementary lighting is proposed with three switches.
For the young adult area on the first floor: Daylight factor is 8.7% risking glare and overheating. 24 LED downlights are calculated to provide 300 lux. Permanent supplementary lighting is proposed with two switches.
External noise calculations find sound levels exceeding limits for both spaces during peak hours